The Ontario Building Code | Closures
9.10.13.1. Closures
(1) Except as provided in Article 9.10.13.2., openings="http://thehandyforce.com/windows/" title ="Window installer in Toronto">openings in required fire separations shall be protected with a closureconforming to Table 9.10.13.1. and shall be installed in conformance with nfpa 80, "Fire doors and Other opening Protectives", unless otherwise specified in this Part.
Table 9.10.13.1.
Fire-Protection Ratings for Closures
Forming Part of Sentence 9.10.13.1.(1)
Item | Column 1 Required Fire-Resistance Rating of Fire Separation | Column 2 Required Fire-Protection Rating of Closure |
1. | 30 or 45 min | 20 min(1) |
2. | 1 h | 45 min(1) |
3. | 1.5 h | 1 h |
4. | 2 h | 1.5 h |
5. | 3 h | 2 h |
6. | 4 h | 3 h |
Notes to Table 9.10.13.1.:
(1) See Article 9.10.13.2.