The Ontario Building Code | Closures

9.10.13.1. Closures

(1) Except as provided in Article 9.10.13.2., openings="http://thehandyforce.com/windows/" title ="Window installer in Toronto">openings in required fire separations shall be protected with a closureconforming to Table 9.10.13.1. and shall be installed in conformance with nfpa 80, "Fire doors and Other opening Protectives", unless otherwise specified in this Part.

Table 9.10.13.1.
Fire-Protection Ratings for Closures

Forming Part of Sentence 9.10.13.1.(1)

Item

Column 1

Required Fire-Resistance Rating of Fire Separation

Column 2

Required Fire-Protection Rating of Closure

1.

30 or 45 min

20 min(1)

2.

1 h

45 min(1)

3.

1.5 h

1 h

4.

2 h

1.5 h

5.

3 h

2 h

6.

4 h

3 h

Notes to Table 9.10.13.1.:

(1) See Article 9.10.13.2.

In Plain Language

Closures, meaning fire-rated doors and similar assemblies used in fire separations, must meet the requirements set out in this article.

This is a plain-language summary of the 2012/2017 Ontario Building Code text above, for general understanding only and not a substitute for the Code. Always confirm current requirements against the 2024 edition (O.Reg. 163/24) or a qualified professional before construction.