7.5.8.1. Hydraulic Loads Draining to Wet vents
(1) The hydraulic load that drains to a wet vent shall conform to Table 7.5.8.1.
(2) When determining the size of a wet vent, the hydraulic load from the most downstream fixture or symmetrically connected fixturesshall not be included.
Table 7.5.8.1.
Maximum Permitted Hydraulic Loads Drained to a Wet vent
Forming Part of Articles 7.5.2.1. and 7.5.8.1.
Item | Column 1 | Column 2 | Column 3 |
| Size of Wet vent, in. | Maximum Hydraulic Load, Fixture Units | |
|
| Not Serving water Closets | Serving Not More Than Two water Closets |
|
|
| Fixtures Other Than water Closets |
1. | 1 ½ | 2 | N/A |
2. | 2 | 4 | 3 |
3. | 3 | 12 | 8 |
4. | 4 | 36 | 14 |
5. | 5 | N/A | 18 |
6. | 6 | N/A | 23 |