The Ontario Building Code | Hydraulic Loads Draining to Wet Vents
7.5.8.1. Hydraulic Loads Draining to Wet vents
(1) The hydraulic load that drains to a wet vent shall conform to Table 7.5.8.1.
(2) When determining the size of a wet vent, the hydraulic load from the most downstream fixture or symmetrically connected fixturesshall not be included.
Table 7.5.8.1. 
  Maximum Permitted Hydraulic Loads Drained to a Wet vent
Forming Part of Articles 7.5.2.1. and 7.5.8.1.
|    Item  |      Column 1  |      Column 2  |      Column 3  |  
|    
  |      Size of Wet vent, in.  |      Maximum Hydraulic Load, Fixture Units  |  |
|    
  |      
  |      Not Serving water Closets  |      Serving Not More Than Two water Closets  |  
|    
  |      
  |      
  |      Fixtures Other Than water Closets  |  
|    1.  |      1 ½  |      2  |      N/A  |  
|    2.  |      2  |      4  |      3  |  
|    3.  |      3  |      12  |      8  |  
|    4.  |      4  |      36  |      14  |  
|    5.  |      5  |      N/A  |      18  |  
|    6.  |      6  |      N/A  |      23  |