The Ontario Building Code | Smoke Alarms

3.2.4.22. Smoke Alarms

(1) Except as permitted by Sentence (6), smoke alarms conforming to CAN/ulc-S531, "Smoke Alarms", shall be installed in each dwelling unit and, except for care, care and treatment or detention occupancies required to have a fire alarm system, in each sleeping room not within a dwelling unit.

(2) At least one smoke alarm shall be installed on each storey and mezzanineof a dwelling unit.

(3) On any storey of a dwelling unit containing sleeping rooms, a smoke alarmshall be installed in,

(a) each sleeping room, and

(b) a location between the sleeping rooms and the remainder of the storey, and if the sleeping rooms are served by a hallway, the smoke alarmshall be located in the hallway.

(4) A smoke alarm shall be installed on or near the ceiling.

(5) Except as permitted by Sentence (6), smoke alarms required by Sentence (1) shall,

(a) be installed with permanent connections to an electrical circuit,

(b) have no disconnect switch between the overcurrent device and the smoke alarm, and

(c) in case the regular power supply to the smoke alarm is interrupted, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of not less than seven days in the normal condition, followed by 4 min of alarm.

(6) Suites of residential occupancyare permitted to be equipped with smoke detectorsin lieu of smoke alarms, provided the smoke detectors,

(a) are capable of independently sounding audible signals within the individual suites,

(b) except as provided by Sentence (7), are installed in conformance with CAN/ulc-S524, "installation of Fire Alarm Systems", and verified in conformance with CAN/ulc-S537, "Verification of Fire Alarm Systems", and

(c) form part of the fire alarm system.

(7) Smoke detectors permitted to be installed in lieu of smoke alarms as provided in Sentence (6) are not required under Clause (6)(b) to sound an alarm throughout the rest of the building, provided they sound localized alarms within individual suites and otherwise meet the requirements of Clause (6)(b).

(8) If more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wireref ="http://thehandyforce.com/electrical/" title ="Electricians in East York">wired so that the actuation of one smoke alarm will cause all smoke alarms within thedwelling unit to sound.

(9) A smoke alarm required by Sentence (1) shall be installed in conformance with CAN/ulc-S553, "installation of Smoke Alarms".

(10) Except as permitted by Sentence (11), a manually operated silencing device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that it will silence the signal emitted by the smoke alarmfor a period of not more than 10 min, after which the smoke alarm will reset and again sound the alarm if the level of smoke in the vicinity is sufficient to reactuate the smoke alarm.

(11) Suites of residential occupancy equipped with smoke detectors installed in conformance with CAN/ulc-S524, "installation of Fire Alarm Systems", as part of the fire alarm system in lieu of smoke alarms as permitted by Sentence (6), need not incorporate the manually operated silencing device required by Sentence (10).

(12) The sound patterns of smoke alarms shall,

(a) meet the temporal patterns of alarm signals, or

(b) be a combination of temporal pattern and voice relay.

(13) Smoke alarms required by Sentence (1) shall have a visual signalling component conforming to the requirements in 18.5.3. (light, Color and Pulse Characteristics) of nfpa 72, "National Fire Alarm and Signaling Code".

(14) The visual signalling component required by Sentence (13) need not,

(a) be integrated with the smoke alarm provided it is interconnected to it,

(b) be on battery backup, or

(c) have synchronized flash rates, when installed in a dwelling unit.

(15) The luminous intensity for visual signalling components required by Sentence (13) that are installed in sleeping rooms shall be a minimum of 175 cd.

Note: On July 1, 2017, Article 3.2.4.22. of Division B of the Regulation is amended by adding the following Sentence: (See: O. Reg. 139/17, s. 29)

(16) Smoke alarms required in suitesin a retirement home or smoke detectors permitted to be installed in lieu of smoke alarms as provided in Sentence (6) shall upon actuation provide an audible and visual signal to staff serving those suites, so that the suite containing the actuated smoke alarm or smoke detectorcan be easily identified.