The Ontario Building Code | Group F, Division 2, up to 4 Storeys, Increased Area
3.2.2.69. Group F, Division 2, up to 4 Storeys, Increased Area
(1) A building classified as Group F, Division 2 is permitted to conform to Sentence (2) provided,
(a) it is not more than 4 storeys in building height, and
(b) it has a building area not more than the value in Table 3.2.2.69.A. or Table 3.2.2.69.B.
(2) Except as permitted by Article 3.2.2.16., the buildingreferred to in Sentence (1) shall be of noncombustible construction, and,
(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzaninesshall have a fire-resistance rating not less than 1 h,
(c) if the buildingis not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearingwalls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
Table 3.2.2.69.A.
Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area
Forming Part of Sentence 3.2.2.69.(1)
| Item | Column 1 | Column 2 | Column 3 | Column 4 |
|
| No. of Storeys | Maximum Area, m2 |
|
|
|
|
| Facing 1 Street | Facing 2 Streets | Facing 3 Streets |
| 1. | 1 | 6 000 | 7 500 | 9 000 |
| 2. | 2 | 3 000 | 3 750 | 4 500 |
| 3. | 3 | 2 000 | 2 500 | 3 000 |
| 4. | 4 | 1 500 | 1 875 | 2 250 |
Table 3.2.2.69.B.
Maximum Building Area, Group F, Division 2, up to 4 Storeys, Increased Area, Sprinklered
Forming Part of Sentence 3.2.2.69.(1)
| Item | Column 1 No. of Storeys | Column 2 Maximum Area, m2 |
| 1. | 1 | 18 000 |
| 2. | 2 | 9 000 |
| 3. | 3 | 6 000 |
| 4. | 4 | 4 500 |
In Plain Language
This article sets one of the specific size-and-construction packages available for a Group F, Division 2 buildings building: up to 4 storeys with increased area per Tables 3.2.2.69.A/B, noncombustible construction. Designers can choose whichever of the several packages in this Subsection best fits the building being planned, trading height and area against construction type, sprinklering, and fire-resistance rating requirements.