The Quebec Building Code | AMENDMENTS TO THE CODE

The Quebec Building Code | AMENDMENTS TO THE CODE

DIVISION 3 AMENDMENTS TO THE CODE

AMENDMENTS TO THE CODE

O.C. 294-2008, s. 1.

  • The Code is amended in Division A

    (1) by replacing Article 1.1.1.1. by the following:

    1.1.1.1. Application of the NPC

    1. The NPC applies to the construction work performed on a plumbing system in every building and facility intended for use by the public as provided in section 3.02 of Chapter III of the Construction Code made pursuant to the Building Act (chapter B-1.1).

    2. In accordance with the NBC, every building shall, except as provided by Sentence (3), have plumbing facilities.

    3. If a hot water system is required under the NBC, the facility shall

    1. provide an adequate hot water supply, and

    2. be installed in conformance with this Chapter.”;

    1. in Article 1.2.1.1., by replacing Clause (b) of Sentence (1) by the following:

      “(b) using alternative solutions that will achieve at least the minimum level of performance required by Division B in the areas defined by the objectives and functional statements attributed to the applicable acceptable solutions approved by the Régie du bâtiment in accordance with section 127 of the Building Act (chapter B-1.1) (see Appendix A.).”;

    2. in Sentence (1) of Article 1.4.1.2.,

      1. by inserting the following after the definition of “Combustible”:

        Construction Code means the Construction Code made pursuant to the Building Act (chapter B-1.1).”;

      2. by inserting “, retention pit” after “sump” in the definition of “Storm building drain”; (b.1) by replacing the definition of “Storey” by the following:

        Storey (as applying to plumbing) means the interval between 2 successive floor levels, including mezzanine floors, or between a floor level and roof that contain at least one plumbing fixture.”;

      3. by replacing the definition of “Potable” by the following:

        Potable means water intended for human consumption.”

      4. by replacing the definition of “Suite” by the following:

        Suite* means a single room or series of rooms of complementary use, operated under a single tenancy and includes dwelling units, individual guest rooms in motels, hotels, rooming houses, boarding houses, dormitories and single-family dwellings, as well as individual stores and individual or complementary rooms for business and personal services occupancies.”;

      5. by replacing the definition of “Occupancy” by the following:

        Occupancy* means the use or intended use of a building or part thereof.”;

      6. by replacing the definition of “Public use” by the following:

      Public use (as applying to the classification of plumbing fixtures) means fixtures installed in locations other than those designated as private use.”;

      (3.1) by adding the following objectives at the end of Sentence (1) of Article 2.2.1.1: “OE Environment

      An objective of the NPC is to limit the probability that, as a result of the design or installation of the

      plumbing system, the environment will be exposed to an unacceptable risk.

      OE1 Resources

      An objective of the NPC is to limit the probability that, as a result of the design or installation of the plumbing system, resources will be used in a manner that will have an unacceptable impact on the environment. The risks of unacceptable impact on the environment due to use of resources addressed in this Code are those caused by

      OE1.2 – Excessive use of water”;

    3. in Article 3.2.1.1., by inserting the following in Sentence (1) after the functional statement “F21 To limit or accommodate dimensional change.”:

      F23 To maintain equipment in place during structural movement.”;

    4. in Article 3.2.1.1., by inserting the following in Sentence (1) after the functional statement “F46 To minimize the risk of contamination of potable water.”:

      F60 To control the accumulation and pressure of surface water, groundwater and sewage.

      F61 To resist the ingress of precipitation, water or moisture from the exterior or from the ground.”; (5.1) in Article 3.2.1.1., by adding the following functional statement at the end of Sentence (1): “F130 To limit the excessive use of water.”;

    5. in note A-1.4.1.2.(1) of Appendix A, by replacing Figure A-1.4.1.2.(1)-L by the following:




    1

    O.C. 961-2002, s. 5; O.C. 294-2008, s. 1; O.C. 939-2009, s. 5; O.C. 30-2014, s. 3.

  • The Code is amended in Division B,

    (1) in Table 1.3.1.2. of Article 1.3.1.2.,

    1. by inserting the following references:


      |


      |


      |


      |


      |

      |

      ANSI/CSA

      |

      ANSI Z21.10.1-

      |

      Gas Water Heaters

      |

      2.2.10.13.(1)

      |

      |


      |

      2004/CSA 4.1-2009

      |

      - Volume I, Storage

      |


      |

      |


      |


      |

      Water Heaters with

      |


      |

      |


      |


      |

      Input Ratings of

      |


      |

      |


      |


      |

      75,000 Btu Per

      |


      |

      |


      |


      |

      Hour or Less

      |


      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      ANSI/CSA

      |

      ANSI Z21.10.3-

      |

      Gas Water Heaters

      |

      2.2.10.13.(1)

      |

      |


      |

      2011/CSA 4.3-2011

      |

      - Volume III,

      |


      |

      |


      |


      |

      Storage Water

      |


      |

      |


      |


      |

      Heaters with Input

      |


      |

      |


      |


      |

      Ratings Above 75,000

      |


      |

      |


      |


      |

      Btu Per Hour,

      |


      |

      |


      |


      |

      Circulating and

      |


      |

      |


      |


      |

      Instantaneous

      |


      |

      |       |          |           |         |

      ”;

      before the reference:


      |

      |


      ANSI/CSA

      |

      |


      ANSI Z21.22-

      |

      |


      Relief Valves for

      |

      |


      2.2.10.11.(1)

      |

      |

      |


      |

      1999/CSA 4.4-M99

      |

      Hot Water Supply

      |


      |

      |


      |

      (Addenda 1 and 2)

      |

      Systems

      |


      |

      |       |          |           |         |

      ”;

    2. by replacing the reference:


      |


      |


      |




      |


      |

      |

      ASME/CSA

      |

      ASME A112.18.1-

      |

      Plumbing

      Supply


      |

      2.2.10.6.(1)

      |

      |


      |

      05/CAN/CSA-

      |

      Fittings

      (For


      |

      2.2.10.7.(1)

      |

      |


      |

      B125.1-05

      |

      Plumbing

      Fixture

      and

      |


      |

      |

      |

      |

      Water-Connected

      |

      |

      |

      |

      |

      Receptors)

      |

      |

      |       |          |           |         |

      ”;

      by the following references:


      |

      |

      |

      |

      |

      | ASME

      | A112.1.2-2004

      | Air Gaps in

      |

      2.2.10.22.(1) |

      |

      |

      | Plumbing Systems

      |

      |

      |       |          |           |         |

      |

      |

      |

      |

      |

      | ASME

      | A112.3.1-2007

      | Stainless Steel

      |

      2.2.6.10.(3) |

      |

      |

      | Drainage Systems

      |

      |

      |

      |

      | for Sanitary DWV,

      |

      |

      |

      |

      | Storm, and Vacuum

      |

      |

      |

      |

      | Applications,

      |

      |

      |

      |

      | Above and Below-

      |

      |

      |

      |

      | Ground

      |

      |

      |       |          |           |         |

      |

      |

      |

      |

      |

      | ASME

      | A112.6.3-2001

      | Floor and Trench

      |

      2.2.10.19.(2) |

      |

      |

      | Drains

      |

      |

      |       |          |           |         |

      |

      |

      |

      |

      |

      | ASME

      | A112.6.4-2003

      | Roof, Deck, and

      |

      2.2.10.20.(1) |

      |

      |

      | Balcony Drains

      |

      |

      |       |          |           |         |

      |

      |

      |


      |

      |

      | ASME/CSA

      | ASME A112.18.1-

      | Plumbing

      Supply

      |

      2.2.10.6.(1) |

      |

      | 05/CAN/CSA-

      | Fittings


      |

      2.2.10.7.(1) |

      |

      | B125.1-05

      |


      |

      2.2.10.7.(4) |

      |       |          |           |         |

      ”;

    3. by inserting the following reference:


      |

      |


      ASME

      |

      |


      B16.11-2009

      |

      |


      Forged Fittings,

      |

      |


      2.2.6.10.(2)

      |

      |

      |


      |


      |

      Socket-Welding and

      |


      |

      |


      |


      |

      Threaded

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |

      |

      |

      |

      |

      ASME

      | B16.4-2006

      | Gray Iron Threaded

      | 2.2.6.5.(1)

      |

      |


      |

      | Fittings, Classes

      |

      |

      |


      |

      | 125 and 250

      |

      |

      |       |          |           |         |

      ”;

    4. by inserting the following reference:


      |


      |


      |



      |


      |

      |

      ASSE

      |

      1072-2007

      |

      Performance


      |

      2.2.10.24.(1)

      |

      |


      |


      |

      Requirements

      for

      |


      |

      |


      |


      |

      Barrier Type

      Floor

      |


      |

      |

      |

      |

      Drain Trap Seal

      |

      |

      |

      |

      |

      Protection Devices

      |

      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |

      |

      |

      |

      |

      ASSE

      | 1051-2009

      | Individual and

      | 2.2.10.16.(1)

      |

      |


      |

      | Branch Type Air

      |

      |

      |


      |

      | Admittance Valves

      |

      |

      |


      |

      | for Sanitary

      |

      |

      |


      |

      | Drainage Systems

      |

      |

      |       |          |           |         |

      ”;

    5. by inserting the following reference:


      |


      |




      |


      |


      |

      |

      ASTM

      |

      A

      312/A

      312M-09

      |

      Standard

      |

      2.2.6.10.(1)

      |

      |


      |




      |

      Specification for

      |


      |

      |


      |




      |

      Seamless, Welded,

      |


      |

      |


      |




      |

      and Heavily Cold

      |


      |

      |


      |




      |

      Worked Austenitic

      |


      |

      |


      |




      |

      Stainless Steel Pipes

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |




      |


      |


      |

      |

      ASTM

      |

      A

      53/A

      53M-07

      |

      Pipe, Steel, Black

      |

      2.2.6.7.(4)

      |

      |


      |




      |

      and Hot-Dipped,

      |


      |

      |


      |




      |

      Zinc-Coated,

      |


      |

      |


      |




      |

      Welded and

      |


      |

      |


      |




      |

      Seamless

      |


      |

      |       |          |           |         |

      ”;

    6. by inserting the following reference:


      |


      |



      |


      |


      |

      |

      ASTM

      |

      A

      778-01(2009)e1

      |

      Standard

      |

      2.2.6.10.(1)

      |

      |


      |



      |

      Specification for

      |


      |

      |


      |



      |

      Welded,

      |


      |

      |


      |



      |

      Unannealed

      |


      |

      |


      |



      |

      Austenitic Stainless

      |


      |

      |


      |



      |

      Steel Tubular

      |


      |

      |


      |



      |

      Products

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |

      |

      |

      |

      |

      ASTM

      | A 518/A 518M-99

      | Corrosion-Resistant

      | 2.2.8.1.(1)

      |

      |


      |

      | High-Silicon Iron

      |

      |

      |


      |

      | Castings

      |

      |

      |       |          |           |         |

      ”;

    7. by inserting the following references:


      |

      |


      BNQ

      |

      |


      NQ


      2622-126-2009

      |

      |


      Reinforced

      |

      |


      2.2.5.3.(1)

      |

      |

      |


      |



      |

      Concrete and

      |


      |

      |


      |



      |

      Unreinforced

      |


      |

      |


      |



      |

      Concrete Pipes and

      |


      |

      |


      |



      |

      Monolithic Lateral

      |


      |

      |


      |



      |

      Connections for

      |


      |

      |


      |



      |

      Evacuation of

      |


      |

      |


      |



      |

      Domestic

      |


      |

      |


      |



      |

      Wastewater and

      |


      |

      |


      |



      |

      Storm Water

      |


      |

      |       |          |           |         |

      |

      |


      BNQ

      |

      |


      NQ


      3623-085-2002

      |

      |


      Ductile-Iron Pipe

      |

      |


      2.2.6.4.(1)

      |

      |

      |


      |



      |

      for Water Pressure

      |


      |

      |


      |



      |

      Piping Systems -

      |


      |

      |


      |



      |

      Characteristics and

      |


      |

      |


      |



      |

      Test Methods

      |


      |

      |       |          |           |         |

      |

      |


      BNQ

      |

      |


      NQ 3624-027-2000

      |

      |


      Tuyaux et raccords

      |

      |


      2.2.5.5.(1)

      |

      |

      |


      |

      (Modificatif N°

      |

      en polyéthylène

      |


      |

      |


      |

      1/03)

      |

      (PE) - Tuyaux pour

      |


      |

      |


      |


      |

      le transport des

      |


      |

      |


      |


      |

      liquides sous

      |


      |

      |


      |


      |

      pression -

      |


      |

      |


      |


      |

      Caractéristiques et

      |


      |

      |


      |


      |

      méthodes d’essais

      |


      |

      |       |          |           |         |

      |

      |


      BNQ

      |

      |


      NQ


      3624-120-2006

      |

      |


      Polyethylene (PE)

      |

      |


      2.2.5.10.(1)

      |

      |

      |


      |



      |

      Pipe and Fittings -

      |


      |

      |


      |



      |

      Smooth Inside Wall

      |


      |

      |


      |



      |

      Open Profile Pipes

      |


      |

      |


      |



      |

      for Storm Sewer and

      |


      |

      |


      |



      |

      Soil Drainage -

      |


      |

      |


      |



      |

      Characteristics and

      |


      |

      |


      |



      |

      Test Methods

      |


      |

      |       |          |           |         |

      |

      |


      BNQ

      |

      |


      NQ 3624-130-1997

      |

      |


      Unplasticized


      |

      |


      2.2.5.10.(1)

      |

      |

      |


      |

      (Amendment No.

      |

      Poly(Vinyl


      |


      |

      |


      |

      1/90) (Amendment

      |

      Chloride) (PVC)


      |


      |

      |


      |

      No. 2/01)

      |

      Rigid Pipe and


      |


      |

      |


      |


      |

      Fittings, 150 mm

      in

      |


      |

      |

      |

      |

      Diameter or Smaller,

      |

      |

      |

      |

      |

      for Underground

      |

      |

      |

      |

      |

      Sewage

      |

      |

      |

      |

      |

      Applications

      |

      |

      |                                  

      |

      |                                               

      |

      |                                                       

      |

      |                                              

      |

      |

      |

      | BNQ

      | NQ 3624-135-2000

      | Unplasticized

      | 2.2.5.10.(1)

      |


      |

      |

      |

      Poly(Vinyl

      |

      |

      |

      |

      |

      Chloride) [PVC-U]

      |

      |

      |

      |

      |

      Pipe and Fittings -

      |

      |

      |

      |

      |

      Pipes of 200 mm to

      |

      |

      |

      |

      |

      600 mm in

      |

      |

      |

      |

      |

      Diameter for

      |

      |

      |

      |

      |

      Underground

      |

      |

      |

      |

      |

      Sewage and Soil

      |

      |

      |

      |

      |

      Drainage -

      |

      |

      |

      |

      |

      Characteristics and

      |

      |

      |

      |

      |

      Test Methods

      |

      |

      |       |          |           |         |

      |


      |



      |


      |


      |

      |

      BNQ

      |

      NQ

      3624-250-2000

      |

      Unplasticized

      |

      2.2.5.8.(1)

      |

      |


      |



      |

      Poly(Vinyl

      |


      |

      |


      |



      |

      Chloride) [PVC-U]

      |


      |

      |


      |



      |

      Pipe and Fittings

      - |


      |

      |


      |



      |

      Rigid Pipe for

      |


      |

      |


      |



      |

      Pressurized

      |


      |

      |


      |



      |

      Water Supply and

      |


      |

      |


      |



      |

      Distribution -

      |


      |

      |


      |



      |

      Characteristics

      |


      |

      |


      |



      |

      and Test Methods

      |


      |

      |       |          |           |         |

      |


      |



      |


      |


      |

      |

      BNQ

      |

      NQ

      3632-670-2005

      |

      Backwater Valves

      |

      2.2.10.18.(1)

      |

      |


      |



      |

      and Check Valves

      |


      |

      |


      |



      |

      Made of Cast Iron

      |


      |

      |


      |



      |

      or Thermoplastique

      |


      |

      |


      |



      |

      Used in Drainage

      |


      |

      |


      |



      |

      Systems -

      |


      |

      |


      |



      |

      Characteristics and

      |


      |

      |


      |



      |

      Test Methods

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |

      |


      AWWA

      |

      |


      ANSI/AWWA

      |

      |


      Ductile-Iron Pipe,

      |

      |


      2.2.6.4.(1)

      |

      |

      |


      |

      C151/A21.51-2002

      |

      Centrifugally Cast,

      |


      |

      |


      |


      |

      for Water

      |


      |

      |       |          |           |         |

      ”;

    8. by replacing the reference:


      |


      |

      |

      |


      |

      |

      CCBFC

      | NRCC 53301

      | National Building

      |

      1.1.1.1.(3) (3)

      |








      |

      |

      |

      Code

      - Canada

      |

      1.4.1.2.(1) (3) |

      |

      |

      |

      2010


      |

      2.1.3.1.(1) |

      |

      |

      |



      |

      2.2.5.12(2) |

      |

      |

      |



      |

      2.2.5.12.(3) |

      |

      |

      |



      |

      2.2.6.7.(3) |

      |

      |

      |



      |

      2.4.3.1.(1) |

      |

      |

      |



      |

      2.4.10.4.(1) |

      |       |          |           |         |

      ”;

      by the following reference:


      |


      |

      |

      |


      |

      |

      CCBFC

      | NRCC 53301

      | National Building

      |

      1.1.1.1.(2) (4)

      |

      |


      |

      | Code of Canada 2010

      |

      1.1.1.1.(3) (4)

      |

      |


      |

      |

      |

      1.4.1.2.(1) (4)

      |

      |

      |

      |

      |

      2.1.3.1.(1) |

      |

      |

      |

      |

      2.1.4.1.(1) |

      |

      |

      |

      |

      2.2.5.12.(2) |

      |

      |

      |

      |

      2.2.5.12.(3) |

      |

      |

      |

      |

      2.2.6.7.(3) |

      |

      |

      |

      |

      2.4.3.1.(1) |

      |

      |

      |

      |

      2.4.10.4.(1) |

      |       |          |           |         |

      ”;

    9. by inserting the following reference:









      |

      |


      CSA

      |

      |


      CAN/CSA-B45.8-

      |

      |


      Terrazzo Plumbing

      |

      |


      2.2.2.2.(10)

      |

      |

      |


      |

      02

      |

      Fixtures

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B45.5-

      |

      |


      Plastic Plumbing

      |

      |


      2.2.2.2.(6)

      |

      |

      |


      |

      02

      |

      Fixtures

      |


      |

      |       |          |           |         |

      ”;

    10. by inserting the following reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B45.11-

      |

      |


      Glass Plumbing

      |

      |


      2.2.2.2.(9)

      |

      |

      |

      |


      |

      |

      04

      |

      |

      Fixtures

      |

      |


      |

      |

      |       |          |           |         |

      ”;

      after the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B45.10-

      |

      |


      Hydromassage

      |

      |


      2.2.2.2.(7)

      |

      |

      |

      |


      |

      |

      01

      |

      |

      Bathtubs

      |

      |


      |

      |

      |       |          |           |         |

      ”;

      (j.1) by replacing the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B64.4-07

      |

      |


      Reduced pressure

      |

      |


      2.10.10.(1)

      |

      |

      |


      |


      |

      Principle (RP)

      |


      |

      |


      |


      |

      Backflow Preventers

      |


      |

      |       |          |           |         |

      by the following references:









      |

      |


      CSA

      |

      |


      CAN/CSA-B64.4-07

      |

      |


      Reduced pressure

      |

      |


      2.10.10.(1)

      |

      |

      |


      |


      |

      Principle (RP)

      |

      2.6.2.4.(2)

      |

      |


      |


      |

      Backflow Preventers

      |

      2.6.2.4.(4)

      |

      |       |          |           |         |


      (j.2) by replacing the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B64.5-07

      |

      |


      Double Check Valve

      |

      |


      2.10.10.(1)

      |

      |

      |


      |


      |

      (DCVA) Backflow

      |


      |

      |


      |


      |

      Prenventers

      |


      |

      |       |          |           |         |


      by the following references:


      |

      |


      CSA

      |

      |


      CAN/CSA-B64.5-07

      |

      |


      Double Check Valve

      |

      |


      2.10.10.(1)

      |

      |

      |


      |


      |

      (DCVA) Backflow

      |

      2.6.2.4.(2)

      |

      |


      |


      |

      Prenventers

      |


      |

      |       |          |           |         |


      (j.3) by replacing the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B64.6-07

      |

      |

      | Dual Check valve (DuC)|


      2.2.10.10.(1)

      |

      |

      |


      |


      |

      Backflow Preventers |


      |

      |       |          |           |         |


      by the following references:


      |

      |


      CSA

      |

      |


      CAN/CSA-B64.6-07

      |

      |

      | Dual Check valve (DuC)|


      2.2.10.10.(1)

      |

      |

      |


      |


      |

      Backflow Preventers |

      2.6.2.4.(2)

      |

      |       |          |           |         |

      (j.4) by replacing the reference:


      |

      |


      CSA

      |

      |


      B64.10.07

      |

      |


      Selection and

      |

      |


      2.6.2.1.(3)

      |

      |

      |


      |


      |

      Installation of

      |


      |

      |


      |


      |

      Backflow Preventers

      |


      |

      |       |          |           |         |


      by the following references:


      |

      |


      CSA

      |

      |


      B64.10.07

      |

      |


      Selection and

      |

      |


      2.6.2.1.(3)

      |

      |

      |


      |


      |

      Installation of

      |

      2.6.2.1.(4)

      |

      |


      |


      |

      Backflow Preventers

      |


      |

      |       |          |           |         |


    11. by inserting the following reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      B64.10.1-07

      |

      Selection and

      |

      2.6.2.1.(4)

      |

      |


      |


      |

      Installation of

      |


      |

      |


      |


      |

      Backflow

      |


      |

      |


      |


      |

      Preventers/

      |


      |

      |


      |


      |

      Maintenance and

      |


      |

      |


      |


      |

      Field Testing of

      |


      |

      |


      |


      |

      Backflow

      |


      |

      |


      |


      |

      Preventers

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |


      |



      |


      |

      |

      CSA

      |

      B64.10-07

      |

      Selection and


      |

      2.6.2.1.(3)

      |

      |


      |


      |

      Installation

      of

      |


      |

      |


      |


      |

      Backflow


      |


      |

      |


      |


      |

      Preventers


      |


      |

      |       |          |           |         |

      ”;

    12. by replacing the reference:


      |

      |


      CSA

      |

      |


      B70-06

      |

      |

      | Cast Iron Soil Pipe, |


      2.2.6.1.(1)

      |

      |

      |


      |


      |

      Fittings, and Means |

      2.4.6.4.(2)

      |

      |       |          |           |         |

      ”;

      by the following references:


      |


      |


      |

      |


      |

      |

      CSA

      |

      B70-06

      |

      Cast Iron Soil Pipe, |

      2.2.6.1.(1)

      |

      |


      |


      |

      Fittings, and Means |

      2.2.10.18.(1)

      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      CSA

      |

      B79-08

      |

      Floor Drains, Area

      |

      2.2.10.19.(1)

      |

      |


      |


      |

      Drains, Shower

      |


      |

      |


      |


      |

      Drains, and

      |


      |

      |


      |


      |

      Cleanouts in

      |


      |

      |


      |


      |

      Residential

      |


      |

      |


      |


      |

      Construction

      |


      |

      |       |          |           |         |

      ”;

      (l.1) by replacing the reference:


      |

      |


      CSA

      |

      |


      B125.3-05

      |

      |


      Plumbing


      Fittings

      |

      |


      2.2.10.6.(1)

      |

      |

      |


      |


      |



      |

      2.2.10.7.(2)

      |

      |


      |


      |



      |

      2.2.10.10.(2)

      |

      |       |          |           |         |

      by the following reference:










      |


      |


      |



      |


      |

      |

      CSA

      |

      B125.3-05

      |

      Plumbing

      Fittings

      |

      2.2.10.6.(1)

      |

      |


      |


      |



      |

      2.2.10.7.(2)

      |

      |


      |


      |



      |

      2.2.10.7.(3)

      |

      |


      |


      |



      |

      2.2.10.7.(5)

      |

      |


      |


      |



      |

      2.2.10.10.(2)

      |

      |


      |


      |



      |

      2.2.10.21.(1)

      |

      |       |          |           |         |


    13. by inserting the following reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      B140.12-03

      |

      Oil-Burning

      |

      2.2.10.13.(1)

      |

      |


      |

      (R2008)

      |

      Equipment: Service

      |


      |

      |


      |


      |

      Water Heaters for

      |


      |

      |


      |


      |

      Domestic Hot

      |


      |

      |


      |


      |

      Water, Space

      |


      |

      |


      |


      |

      Heating, and

      |


      |

      |


      |


      |

      Swimming Pools

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-

      |

      Polypropylene (PPR)

      |

      2.2.5.15.(1)

      |

      |


      |

      B137.11-05

      |

      Pipe and Fittings

      |


      |

      |


      |


      |

      for Pressure

      |


      |

      |


      |


      |

      Applications

      |


      |

      |       |          |           |         |

      ”;

      (m.1) by replacing the reference:









      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B181.1-06

      |

      Acrylonitrile-

      |

      2.2.5.10.(1)

      |

      |


      |


      |

      Butadiene-Styrene

      |

      2.2.5.11.(1)

      |

      |


      |


      |

      (ABS) Drain, Waste,

      |

      2.2.5.12.(1)

      |

      |


      |


      |

      and Vent Pipe and

      |


      |

      |


      |


      |

      Pipe Fittings

      |


      |

      |       |          |           |         |


      by the following reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B181.1-06

      |

      Acrylonitrile-

      |

      2.2.5.10.(1)

      |

      |


      |


      |

      Butadiene-Styrene

      |

      2.2.5.11.(1)

      |

      |


      |


      |

      (ABS) Drain, Waste,

      |

      2.2.5.12.(1)

      |

      |


      |


      |

      and Vent Pipe and

      |

      2.2.10.18.(1)

      |

      |


      |


      |

      Pipe Fittings

      |


      |

      |       |          |           |         |


      (m.2) by replacing the reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B181.2-06

      |

      Polyvinylchloride

      |

      2.2.5.10.(1)

      |

      |


      |


      |

      (PVC) and Chlorinated

      |

      2.2.5.11.(1)

      |

      |


      |


      |

      Polyvinylchloride

      |

      2.2.5.12.(1)

      |

      |


      |


      |

      (CPVC) Drain, Waste,

      |


      |

      |


      |


      |

      and Vent Pipe and

      |


      |

      |


      |


      |

      Pipe Fittings

      |


      |

      |       |          |           |         |


      by the following reference:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B181.2-06

      |

      Polyvinylchloride

      |

      2.2.5.10.(1)

      |

      |


      |


      |

      (PVC) and Chlorinated

      |

      2.2.5.11.(1)

      |

      |


      |


      |

      Polyvinylchloride

      |

      2.2.5.12.(1)

      |

      |


      |


      |

      (CPVC) Drain, Waste,

      |

      2.2.10.18.(1)

      |

      |


      |


      |

      and Vent Pipe and

      |


      |

      |


      |


      |

      Pipe Fittings

      |


      |

      |       |          |           |         |

      (m.3) by replacing the reference:









      |

      |


      CSA

      |

      |


      CAN/CSA-B182.1-06

      |

      |


      Plastic Drain and

      |

      |


      2.2.5.10.(1)

      |

      |

      |


      |


      |

      Sewer Pipe and Pipe

      |


      |

      |


      |


      |

      Fittings

      |


      |

      |       |          |           |         |


      by the following reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-B182.1-06

      |

      |


      Plastic Drain and

      |

      |


      2.2.5.10.(1)

      |

      |

      |


      |


      |

      Sewer Pipe and Pipe

      |

      2.2.10.18.(1)

      |

      |


      |


      |

      Fittings

      |


      |

      |       |          |           |         |


    14. by inserting the following references:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B481

      |

      Grease Interceptors

      |

      2.2.3.2.(3)

      |

      |


      |

      Series-07

      |


      |

      2.4.4.3.(1)

      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-B483.1-

      |

      Drinking Water

      |

      2.2.10.17.(1)

      |

      |


      |

      07

      |

      Treatment Systems

      |

      2.2.10.17.(2)

      |

      |


      |


      |


      |

      2.2.10.17.(3)

      |

      |


      |


      |


      |

      2.2.10.17.(4)

      |

      |


      |


      |


      |

      2.2.10.17.(5)

      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-C22.2

      |

      Construction and

      |

      2.2.10.13.(1)

      |

      |


      |

      110-94 (R2009)

      |

      Test of Electric

      |


      |

      |


      |


      |

      Storage-Tank Water

      |


      |

      |


      |


      |

      Heaters

      |


      |

      |       |          |           |         |

      ”;


      |


      |


      |



      |


      |

      |

      CSA

      |

      CAN/CSA-B602-05

      |

      Mechanical


      |

      2.2.10.4.(2)

      |

      |


      |


      |

      Couplings for


      |


      |

      |


      |


      |

      Drain, Waste,

      and

      |


      |

      |


      |


      |

      Vent Pipe and


      |


      |

      |


      |


      |

      Sewer Pipe


      |


      |

      |       |          |           |         |

      ”;

    15. by replacing the references:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-F379.1-

      |

      Solar Domestic

      |

      2.2.10.13.(1)

      |

      |


      |

      88

      |

      Hot Water Systems

      |


      |

      |


      |


      |

      (Liquid to

      |


      |

      |


      |


      |

      Liquid Heat Transfer)

      |


      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-F383-87

      |

      Installation Code

      |

      2.6.1.8.(1)

      |

      |


      |


      |

      for Solar Domestic

      |


      |

      |


      |


      |

      Hot Water Systems

      |


      |

      |       |          |           |         |

      ”;

      by the following references:


      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-F379.1-

      |

      Packaged Solar

      |

      2.2.10.13.(1)

      |

      |


      |

      09

      |

      Domestic Hot

      |


      |

      |


      |


      |

      Water Systems

      |


      |

      |


      |


      |

      (Liquid-to-Liquid

      |


      |

      |


      |


      |

      Heat Transfer)

      |


      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      CSA

      |

      CAN/CSA-F383-08

      |

      Installation of

      |

      2.6.1.8.(1)

      |

      |


      |


      |

      Packaged Solar

      |


      |

      |


      |


      |

      Domestic Hot

      |


      |

      |


      |


      |

      Water Systems

      |


      |

      |


      |


      |


      |


      |

      |       |          |           |         |

      ”;

    16. by inserting the following references:









      |


      |


      |


      |


      |

      |

      ISO

      |

      ISO 11143-2008

      |

      Amalgam

      |

      2.2.3.2.(4)

      |

      |


      |


      |

      Separators

      |


      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      MSS

      |

      SP-58-2009

      |

      Pipe Hangers and

      |

      2.2.10.23.(1)

      |

      |


      |


      |

      Supports -

      |


      |

      |


      |


      |

      Materials, Design,

      |


      |

      |


      |


      |

      Manufacture,

      |


      |

      |


      |


      |

      Selection,

      |


      |

      |


      |


      |

      Application and

      |


      |

      |


      |


      |

      Installation

      |


      |

      |       |          |           |         |

      ”;

      after the reference:


      |

      |


      CSA

      |

      |


      CAN/CSA-G401-07

      |

      |


      Corrugated Steel

      |

      |


      2.2.6.8.(1)

      |

      |

      |


      |


      |

      Pipe Products

      |


      |

      |       |          |           |         |

      ”;

    17. by inserting the following references:


      |


      |



      |


      |


      |

      |

      NSF

      |

      NSF/ANSI

      53-2009

      |

      Drinking Water

      |

      2.2.10.17.(4)

      |

      |


      |



      |

      Treatment Units

      - |


      |

      |


      |



      |

      Health Effects

      |


      |

      |       |          |           |         |

      |


      |



      |


      |


      |

      |

      NSF

      |

      NSF/ANSI

      55-2009

      |

      Ultraviolet

      |

      2.2.10.17.(1)

      |

      |


      |



      |

      Microbiological

      |


      |

      |


      |



      |

      Water Treatment

      |


      |

      |


      |



      |

      Systems

      |


      |

      |       |          |           |         |

      |


      |


      |


      |


      |

      |

      NSF

      |

      NSF/ANSI 62-2009

      |

      Drinking Water

      |

      2.2.10.17.(3)

      |

      |


      |


      |

      Distillation Systems

      |


      |

      |       |          |           |         |

      ”;

      Updated to March 1 2021


      |


      |


      |


      |


      |

      |

      NFPA

      |

      13D-2007

      |

      Installation of

      |

      2.6.3.1.(3)

      |

      |


      |


      |

      Sprinkler Systems

      |


      |

      |


      |


      |

      in One- and Two-

      |


      |

      |


      |


      |

      Family Dwellings

      |


      |

      |


      |


      |

      and Manufactured

      |


      |

      |


      |


      |

      Homes

      |


      |

      |       |          |           |         |

      ”;

      1. in Article 1.3.2.1

        1. by replacing “8614 Catalpa Avenue, suite 1007, Chicago, Illinois 60656-1116” in “ASPE…American Society of Plumbing Engineers (8614 Catalpa Avenue, Suite 1007, Chicago, Illinois 60656-1116 U.S.A.; www.aspe.org)” by “6400 Shafer Ct., Suite 350, Rosemont, IL 60018-4914”;

        2. by inserting the following after “AWWA…American Water Works Association (6666 West Quincy Avenue, Denver, Colorado 80235 U.S.A.; www.awwa.org)”:

          “BNQ...Bureau de normalisation du Québec (333, rue Franquet, Québec, Québec G1P 4C7; www.bnq.qc.ca)”;

        3. by replacing “NBC… National Building Code of Canada 2005 (see CCBFC)” by the following:

          NBC... National Building Code of Canada within the meaning of section 1.01 of Chapter I of the Construction Code, as amended by this Chapter”;

        4. by inserting the following after “CSA...CSA Group (5060 Spectrum Way, Suite 100, Mississauga, Ontario L4W 5N6; www.csagroup.ca)”:

          ISO...“International Organization for Standardization (1, ch. de la Voie-Creuse, CP 56 - CH-1211, Geneva 20, Switzerland; www.iso.org) ”;

          MSS...“Manufacturers Standardization Society of the Valve and Fittings Industry (127 Park Street, N.E., Vienna, Virginia 22180 U.S.A.; www.mss-hq.com)”;

        5. by inserting the following after “NPC... National Plumbing Code of Canada 2005 (see CCBFC)” and “NRC-NRCC… National Research Council of Canada (Ottawa, Ontario K1A 0R6; www.nrc-cnrc.gc.ca)” respectively:

        “NQ... Québec standard” and;

        “NSF...NSF International (PO Box 130140, Ann Arbor, Michigan 48113-0140, U.S.A.; www.nsf.com)”;

      2. (paragraph revoked);

      3. by adding the following after Subsection 2.1.3.:

      “2.1.4. Structural Movement

            1. Structural Movement

              1. Plumbing systems of buildings subject to Chapter I of the Construction Code and to which Part 4 of Division B of the NBC applies shall be designed and installed to accommodate the maximum relative structural movement provided for in the construction of the building. (See Article 4.1.3.5., Subsection 4.1.8., Sentence 4.1.3.3.(2) and Appendix Note A-6.2.1.3. of Division B of the NBC for information on the types of structural movements that may be encountered.)”;

      (4.1) in Article 2.2.2.2., by adding the following after Sentence (8):

      (9) Every glass lavatory must conform to CAN/CSA-B45.11, Glass Plumbing Fixtures:

      (10) Every terrazzo plumbing fixture must conform to CAN/CSA-B45.8, Terrazzo Plumbing Fixtures.”;

      (5) in Article 2.2.3.1.,

      1. by replacing Sentence (1) by the following:

        (1) Subject to Sentence 2.4.5.1.(5), every trap shall

        1. have a trap seal depth of not less than 50 mm,

        2. be so designed that failure of the seal walls will cause exterior leakage,

        3. have a water seal that does not depend on the action of moving parts, and

        4. subject to Sentence 2.4.3.7.(2), have a constant semi-circular curvature. (See Appendix A.)

      2. by striking out Sentence (2);

      3. by adding the following after Sentence (5):

      (6) A deep trap seal must be a minimum of 100 mm.”;”;

      (6) by adding the following after Sentence (2) in Article 2.2.3.2.:

      (3) Every grease interceptor must conform to CAN/CSA-B481 Series, Grease Interceptors.

      (4) Every amalgam separator must conform to ISO 11143, Amalgam Separators.”;”; (6.1) in Article 2.2.4.2., by replacing Sentence (1) by the following:

      (1) Subject to Article 2.4.3.7., a single or double sanitary T fitting shall not be used in a nominally horizontal pipe, except that a single sanitary T fitting may be used to connect a vent pipe.”;”;

      (6.2) by adding “The prohibition also applies to any combination of 45 ° elbows displaying the same characteristics.” at the end of Sentence (1) of Article 2.2.4.3.;”;

      1. in Article 2.2.5.3., by inserting the following after Clause (b) of Sentence (1):

        “(c) NQ 2622-126, Reinforced Concrete and Unreinforced Concrete Pipes and Monolithic Lateral Connection for Evacuation of Domestic Wastewater and Storm Water.”;

      2. in Article 2.2.5.5., by replacing Sentence (1) by the following:

        “(1) Polyethylene water pipe, tubing, and fittings must conform to Series 160 of

        1. CAN/CSA-B137.1, Polyethylene (PE) Pipe, Tubing, and Fittings for Cold-Water Pressure Services, or

          Updated to March 1 2021

        2. NQ 3624-027, Tuyaux et raccords en polyéthylène (PE) – Tuyaux pour le transport des liquides sous pression – Caractéristiques et méthodes d’essais.”;”;

      3. in Article 2.2.5.8., by replacing Clause (a) of Sentence (1) by the following: “(a) conform to

      1. CAN/CSA-B137.3, Rigid Polyvinyl Chloride (PVC) Pipe and Fittings for Pressure Applications, or

      2. NQ 3624-250, Unplasticized Poly(Vinyl Chloride) [PVC-U] Pipe and Fittings - Rigid Pipe for Pressurized Water Supply and Distribution - Characteristics and Test Methods, and”;

      (10) in Article 2.2.5.10.,

      1. by striking out “or” at the end of Clause (f) of Sentence (1);

      2. by adding the following after Clause (g) of Sentence (1):

      “(h) NQ 3624-120, Polyethylene (PE) Pipe and Fittings - Smooth Inside Wall Open Profile Pipes for Storm Sewer and Soil Drainage - Characteristics and Test Methods,

      1. NQ 3624-130, Unplasticized Poly(Vinyl Chloride) (PVC) Rigid Pipe and Fittings, 150 mm in Diameter or Smaller, for Underground Sewage Applications, or

      2. NQ 3624-135, Unplasticized Poly(Vinyl Chloride) [PVC-U] Pipe and Fittings - Pipes of 200 mm to 600 mm in Diameter for Underground Sewage and Soil Drainage - Characteristics and Test - Methods.”;”;

      1. (paragraph revoked);

      2. in Article 2.2.6.4., by replacing Sentence (1) by the following:

        “(1) Cast-iron water pipes shall conform to

        1. ANSI/AWWAC151/A21.51, Ductile-Iron Pipe, Centrifugally Cast, for Water, or

        2. NQ 3623-085, Ductile-Iron Pipes for Water Pressure Piping Systems - Characteristics and Test Methods.”;

        (12.1) in Article 2.2.6.7.,

        1. by replacing, “Sentences (2) and (3)” in Sentence (1) by “Sentence (2)”;

        2. by striking out Sentence (3);”;

      3. by adding the following after Article 2.2.6.9.:

      2.2.6.10. Stainless Steel Pipes

      1. In water distribution systems, stainless steel pipes must be of the 304, 304L, 316 or 316L type and conform to

        1. ASTM-A312/A312M, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes, or

        2. ASTM-A778, Standard Specification for Welded, Unannealed Austenitic Stainless Steel Tubular Products.

      2. In water distribution systems, fittings must be of the 304, 304L, 316 or 316L type and conform to ASME B16.11, Forged Fittings, Socket-Welding and Threaded.

      3. In a drainage system, stainless steel pipes and fittings must be of the 316L type, or of the 304 type if installed above ground, and conform to ASME A112.3.1, Stainless Steel Drainage Systems for Sanitary DWV, Storm, and Vacuum Applications, Above and Below-Ground.”;

      1. (paragraph revoked);

      2. in Article 2.2.10.5., by inserting “, except at the point of connection to a standpipe system” after “water systems” in Sentence (1);

      (15.1) by replacing Article 2.2.10.7. by the following:

      2.2.10.7. Water Temperature Control

      (see Appendix A)

      1. Except as provided in Sentences (2) to (4), valves supplying shower heads or bathtubs must be of the pressure-balanced, thermostatic, or combination pressure-balanced/thermostatic type and conform to ASME A112.18.1/CSA B125.1, Plumbing Supply Fittings.

      2. Valves supplying only bathtubs need not be of one of the types referred to in Sentence (1) if the hot water supply is controlled by a thermostatic-mixing valve or an automatic temperature-limiting device conforming to CSA B125.3, Plumbing Fittings.

      3. Valves supplying only shower heads need not be of one of the types referred to in Sentence (1) if the water supply is controlled by an automatic compensating valve conforming to CSA B125.3, Plumbing Fittings.

      4. Except as provided in Sentence (5), valves supplying shower heads or bathtubs of a care occupancy or private seniors’ residence within the meaning of the Act respecting health services and social services (chapter S-4.2) must be of the thermostatic or combination pressure-balanced/thermostatic type and conform to ASME A112.18.1/CSA B125.1, Plumbing Supply Fittings. For the purposes of this Article, “care occupancy” means a building or part of a building housing persons who, because of their physical or mental state, need medical care or treatment.

      5. Valves supplying only bathtubs of a care occupancy or private seniors’ residence need not be of one of the types referred to in Sentence (4) if the hot water supply is controlled by a thermostatic-mixing valve or an automatic temperature-limiting device installed within the limits of a bathroom and conforming to CSA B125.3, Plumbing Fittings.

      6. Valves, mixing valves and limiting devices covered by Sentences (1) to (3) must be adjusted to provide a water outlet temperature that does not exceed 49 °C. Those covered by Sentences (4) and (5) must be adjusted to provide a water outlet temperature that does not exceed 43 °C.”

      (16) in Article 2.2.10.13.,

      1. by striking out “Solar Domestic” in the title;

      2. by replacing Sentence (1) by the following:

      “(1) Service water heaters must conform to

      1. ANSI Z21.10.1/CSA 4.1, Gas Water Heaters - Volume I, Storage Water Heaters With Input Ratings of 75,000 Btu Per Hour or Less,

        Updated to March 1 2021

      2. ANSI Z21.10.3/CSA 4.3, Gas Water Heaters - Volume III, Storage Water Heaters With Input Ratings Above 75,000 Btu Per Hour, Circulating and Instantaneous,

      3. CAN/CSA-C22.2 No. 110, Construction and Test of Electric Storage-Tank Water Heaters,

      4. CSA B140.12, Oil-Burning Equipment: Service Water Heaters for Domestic Hot Water, Space Heating, and Swimming Pools, or

      5. CAN/CSA-F379.1, Solar Domestic Hot Water Systems (Liquid to Liquid Heat Transfer).”;”;

      (17) by adding the following after Article 2.2.10.16.:

      “2.2.10.17. Potable Water Treatment Unit

      1. Potable water disinfection units using ultraviolet designed to meet the requirements of the Regulation respecting the quality of drinking water, (chapter Q-2, r. 40), shall conform to one of the following standards:

        1. NSF/ANSI 55, Ultraviolet Microbiological Water Treatment Systems, or

        2. CAN/CSA B483.1, Drinking Water Treatment Systems, if they are designed to be installed at the point of use.

      2. Reverse osmosis potable water treatment systems installed at the point of use and designed to meet the requirements of the Regulation respecting the quality of drinking water shall conform to CAN/CSA B483.1, Drinking Water Treatment Systems.

      3. Potable water distillation systems designed to meet the requirements of the Regulation respecting the quality of drinking water shall conform to one of the following standards:

        1. NSF/ANSI 62, Drinking Water Distillation Systems; or

        2. CAN/CSA B483.1, Drinking Water Treatment Systems, if they are designed to be installed at the point of use.

      4. Potable water treatment units not referred to in Sentences (1) to (3) and designed to meet the requirements of the Regulation respecting the quality of drinking water shall conform to one of the following standards:

        1. NSF/ANSI 53, Drinking Water Treatment Units - Health Effects, or

        2. CAN/CSA B483.1, Drinking Water Treatment Systems, if they are designed to be installed at the point of use.

      5. Potable water treatment units not referred to in Sentences (1) to (4) shall conform to CAN/CSA B483.1, Drinking Water Treatment Systems.”;

            1. Backwater Valves

              1. Backwater valves shall conform to

                1. CSA B70, Cast Iron Soil Pipe, Fittings, and Means of Joining,

                2. CAN/CSA-B181.1, Acrylonitrile-Butadiene-Styrene (ABS) Drain, Waste, and Vent Pipe and Pipe Fittings,

                3. CAN/CSA-B181.2, Polyvinylchloride (PVC) and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings,

                4. CAN/CSA-B182.1, Plastic Drain and Sewer Pipe and Pipe Fittings, or

                5. NQ 3632-670, Backwater Valves and Check Valves Made of Cast Iron or Thermoplastic Used in Drainage Systems Characteristics and Test Methods.

            2. Floor Drains and Shower Drains

              1. Floor drains, including emergency floor drains, and shower drains installed in an individual house shall conform to CSA B79, Floor Drains, Area Drains, Shower Drains, and Cleanouts in Residential Construction.

              2. Floor drains, including emergency floor drains, and shower drains installed in an occupancy other than an individual house shall conform to ASME A112.6.3, Floor and Trench Drains.

            3. Roof Drains

              (1) Roof drains shall conform to ASME A112.6.4, Roof, Deck, and Balcony Drains.

            4. Trap Seal Primer Devices

              (1) Trap seal primer devices shall conform to CSA B125.3, Plumbing Fittings.

            5. Air Gaps


              (1) Prefabricated air gaps shall conform to ASME A112.1.2, Air Gaps in Plumbing Systems (For Plumbing Fixtures and Water-Connected Receptors).

            6. Pipe Hangers and Supports


      (1) Prefabricated pipe hangers and supports shall conform to MSS SP-58, Pipe Hangers and Supports – Materials, Design, Manufacture, Selection, Application, and Installation.”;

      2.2.10.24 Floor Drain Trap Seals


      (1) Floor drain trap seals used to maintain trap seal depth must be certified in accordance with ASSE 1072, Performance Requirements for Barrier Type Floor Drain Trap Seal Protection Devices.

      1. (paragraph revoked);

        (18.1) by replacing “à l’intérieur d’un bâtiment” in Sentence (2) of Article 2.3.3.12. of the French text by “sous un bâtiment”;

      2. by replacing Sentence (3) of Article 2.3.4.1. by the following:

        (3) Every wall-mounted fixture and every valve must be supported so that no strain is transmitted to the piping.

        (19.1) by replacing “a water pressure test or an air pressure test” in Sentence (1) of Article 2.3.6.1. by “a water pressure test, smoke pressure test or air pressure test”;

        (19.2) by inserting “, smoke test” after “air pressure test” in Sentence (1) of Articles 2.3.6.2. and 2.3.6.3.; (19.3) by adding the following after Article 2.3.6.7.:

        “2.3.6.8. Smoke Tests

        1. Where a smoke test is made

          1. smoke from smoke-generating machines must be forced into the system, and

            Updated to March 1 2021

          2. a pressure equivalent to a 25 mm water column must be maintained for 15 min without the addition of more smoke.”;

      3. in Article 2.4.2.1.,

      1. by striking out “and at the end of Clause (d) and “or at the end of Subclause (v) of Clause (e) of Sentence (1);

      2. by inserting the following after Subclause (vi) of Clause (e) of Sentence (1): “(vii) a drain or overflow from a swimming or wading pool and deck floor drains,

        1. a drain from an ice machine;

        2. a drain from a heating, air-conditioning or ventilation system;

      3. by replacing Sentence (2) by the following:

      “(2) Where the upper vertical part of an offset soil-or-waste stack receives water from fixtures from more than one storey, a connection in that offset soil-or-waste stack shall not be less than

      1. 1.5 m downstream from the base of the upper section of the soil-or-waste stack or from another connection receiving sewage from another soil-or-waste stack connected to the offset, and

      2. 600 mm higher or lower than the nominally horizontal offset in the upper or lower vertical section of an offset soil-or-waste stack.

      (See Appendix A.)”;

      (d) by replacing Sentences (4) and (5) by the following:

      (4) Every connection at the bottom of a soil-or-waste stack must be more than

      1. 1.5 m in a building drain or a branch receiving sewage from the soil-or-waste stack, and

      2. 600 mm from the top of the building drain or branch to which the soil-or-waste stack is connected. (See Appendix A.)

      1. Every trap arm of a bathtub, shower, bidet, floor drain or service sink installed on the floor must have a nominally horizontal part not less than 450 mm in developed length. The developed length of the trap arm of a floor drain must be increased to 1.5 m if it is connected not more than 3 m downstream from the bottom of a soil-or-waste stack or a leader.

        (See Appendix A.)

      2. Where a change of direction greater than 45 ° occurs in a soil-or-waste pipe that serves more than one clothes washer or domestic kitchen sink, and in which pressure zones are created by detergent suds, no soil- or-waste pipe must serve for connecting other soil-or-waste pipe over a length not less than

        1. 40 times the size of the soil-or-waste pipe or 2.44 m maximum vertical, whichever is less, before changing direction, and

        2. 10 times the size of the nominally horizontal soil-or-waste pipe after changing direction. (See Appendix A.)

      3. Where a vent pipe is connected into the suds pressure zone referred to in Sentence (6), no other vent pipe must be connected to that vent pipe within the height of the suds pressure zone.

        (See Appendix A.);

        (20.1) in Article 2.4.2.3.,

        1. by striking out “and” at the end of Clause (a) of Sentence (1);

        2. by replacing “air break” in Clause (b) of Sentence (1) by “air break, and”;

        3. by inserting the following after Clause (b) of Sentence (1):

          “(c) is located in the same room or suite.”;

        4. by striking out “and” at the end of Clause (a) of Sentence (2);

        5. by replacing “(see A-2.4.2.1.(1)(a)(ii) and (e)(vi)) in Appendix A).” in Clause (b) of Sentence (2) by “(see A-2.4.2.1.(1)(a)(ii) and (e)(vi)) in Appendix A), and”;

        6. by inserting the following after Clause (b) of Sentence (2):

      “(c) is located in the same room or suite.”;

      (g) by replacing “2.4.2.1.(1)(e)(iii) to (vi)” in Sentence (3) by “2.4.2.1.(1)(e)(iii) to (ix)”;

      1. by striking out “and” at the end of Clause (a) of Sentence (3);

      2. by replacing “are connected to it.” in Clause (b) of Sentence (3) by “are connected to it, and”;

      3. by inserting the following after Clause (b) of Sentence (3):

      “(c) is located in the same room or suite.”;

      (20.2) in Article 2.4.3.5., by adding the following after Sentence (1):

      (2) The number and type of fixtures that may be part of macerating toilet systems must comply with the manufacturer’s recommendations of those systems.”;

      (20.3) in Article 2.4.3.6., by replacing “that connects the sump well to the drainage system” in Clause (b) of Sentence (1) by “that connects the pit to the sump well”;

      (21) by adding the following after Article 2.4.3.6.:

      “2.4.3.7. Retention Pit (See Appendix A.)


      1. A retention pit must be made in one piece, be leakproof and smooth inside. Its length shall not be less than 600 mm and its minimum width shall not be less than 450 mm, the length being taken in the direction of its fixture drain. A round retention pit shall be not less than 600 mm in size.

      2. The fixture drain of the retention pit shall be not less than 3 inches in size and be protected by a reversed sanitary T fitting with a cleanout at the end or by a running trap with cleanout. The fixture drain shall be 4 inches in size if the retention pit receives storm water. Despite the foregoing, for a single-family house, the fixture drain may be 3 inches in size.

      3. A reversed sanitary T fitting shall be located inside the retention pit and the running trap may be located inside or outside the retention pit. In the last case, the trap cleanout shall be extended to the floor level. The retention pit must have a running trap where it is connected to an oil interceptor.

        Updated to March 1 2021

      4. The lower end of the reversed sanitary T fitting shall be placed 200 mm or more from the bottom of the retention pit. For a running trap, the upper end of the trap shall be placed not less than 300 mm from the bottom of the retention pit.

      5. The retention pit shall be covered, at the floor or ground level, by a cast iron or steel cover not less than 6 mm thick or any other material conforming to the Code.

      6. The fixture drain of a retention pit exposed to frost shall have a trap inside the building, unless it drains into another retention pit that is not exposed.

      7. The fixture drain of a retention pit shall be directly connected to the drainage system and drain into it by gravity or in the manner described in Article 2.4.6.3.

      8. The invert of a discharge pipe connected to a retention pit shall be higher than the crown of the fixture drain.

      9. A retention pit must have a fixture drain 3 inches in size for a draining area not more than 370 m2. For a

        fixture drain more than 3 inches in size, the drained area may be increased by 280 m2 per additional inch.

      10. A check valve is permitted to be installed inside a retention pit provided it is extended by a length equal to the length of the valve.

      11. The requirements relating to the fall and ventilation of trap arms do not apply to the fixture drain

        serving a retention pit.”;

      12. Retention pits to which a subsoil drainage pipe is connected must have

      1. an air-tight cover, and

      2. a vent pipe at least 11/2 inches in size if the content of the retention pit is pumped. (21.1) in Article 2.4.4.1., by adding the following after Sentence (1):

      (2) Every beauty parlour lavatory must be equipped with a hair interceptor.

      (3) Every fixture that can receive dental amalgam waste must have an amalgam interceptor.”;

      (21.2) in Article 2.4.4.3., by inserting “and its choice must be made according to CAN/CSA-B481 Series, “Grease Interceptors”” before “(See Appendix A.)” in Sentence (1);

      (21.3) in Article 2.4.4.4., by replacing Sentence (1) by the following:

      (1) Where a fixture or equipment discharges corrosive or acid waste, it must discharge into a neutralizing or dilution tank that is connected to the sanitary drainage system through a trap. (See Appendix A.)”;”;

      (22) by replacing Article 2.4.5.3. by the following:

      “2.4.5.3. Connection of Subsoil Drainage Pipe to a Drainage System

      (1) Where a subsoil drainage pipe is connected to a drainage system, the connection shall be made on the upstream side of a trap with a cleanout, a trapped sump or a retention pit. (See Appendix A.)”;

      1. in Article 2.4.5.4., by adding the following after Sentence (1):

        “(2) No sanitary drainage system or combined building drain shall have a building trap.”;

      2. by replacing Article 2.4.5.5. by the following:

        2.4.5.5. Trap seals

        1. Provision must be made for maintaining the trap seal of a floor drain by

          1. the use of a trap seal primer,

          2. using the drain as a receptacle for an indirectly connected drinking fountain,

          3. using a floor drain trap seal, or

          4. other equally effective means. (See Appendix A.)

        2. Water from the trap seal of a floor drain in a dwelling unit need not be maintained by a trap seal primer. (See Appendix A.)”.”;

          (24.1) by adding the following after Sentence (7) of Article 2.4.6.3.:

          (8) Every sump or receiving tank to which a subsoil drainage pipe is connected must have

          1. an air tight cover, and

          2. a vent pipe at least 11/2 inches in size if the sump or tank is pumped.”.”;

      (25) in Article 2.4.6.4.,

      1. by replacing Sentences (2) and (3) by the following:

        “(2) A backwater valve may be installed in a building drain provided that

        1. it is a “normally open” design, and

        2. it does not serve more than one dwelling unit.


      (3) Subject to Sentences (4) and (5), where a fixture, a retention pit, a sump or running trap is located below the level of the adjoining street, a gate valve or a backwater valve must be installed on every drain connected to a building drain or a branch.”;

      (2) by striking out Sentence (6);”;

      1. by striking out Article 2.4.6.5.;

        (26.1) in Article 2.4.7.1., by adding the following after Sentence (9):

        “(10) In a separate system, a storm building drain must be located to the left of the sanitary building drain, towards the street, from the building.”;

        (26.2) in Article 2.4.10.4., by replacing Sentence (4) by the following:

        “(4) Where the height of the parapet is more than 150 mm or exceeds the height of the adjacent wall flashing, emergency roof overflows or scuppers described in Clause (2)(c) shall be provided.”;”;

      2. in Article 2.5.2.1.,

        1. by replacing “Table 2.5.2.1.” in Clause (a) of Sentence (1) by “Article 2.5.8.1.”;

        2. by replacing Clause (d) of Sentence (1) by the following:

          “(d) the trap arms of the water closets connected to a vertical pipe are connected downstream from all other fixtures,”;

          (b.1) by replacing Clause (e) of Sentence (1) by the following:

          “(e) trap arms and fixture drains do not exceed 2 inches in size when connected to a wet vent that extends above more than 1 storey, except for connections from emergency floor drains in accordance with Sentence 2.5.1.1.(3);”;

          (b.2) by replacing “;Table 2.5.2.1”; in Clause (f) of Sentence (1) by “Article 2.5.8.1.”;”;;

        3. by replacing Clause (j) of Sentence (1) by the following:

        “(j) the portion of the soil-or-waste stack having a wet vent that extends through more than one storey is the same size from its bottom to the uppermost connection of a fixture;”;

        “(c.1) by replacing “limited.” in Clause (k) by “limited”; (c.2) by adding the following after Clause (k):

        “(l) it is extended as a stack vent or as a continuous vent, and

        (m) trap arms are connected separately and directly to the wet vent.”;

        (d) (subparagraph revoked);

        (27.1) in Article 2.5.4.4., by replacing “d’au moins 1,5 m” in Sentence (1) of the French text by “de plus de 1,5 m”;

        (27.2) in Article 2.5.6.2., by adding the following after Sentence (3):

        “(4) The plumbing venting system may not be used in other systems.”;

        (27.3) in Article 2.5.6.5., by replacing “it penetrates the roof,” in Clause (a) of Sentence (6) by “it penetrates the roof, except pipes 4 inches and bigger that may be of the same size,”;

      3. in Article 2.5.8.1.,

        1. by replacing “Table 2.5.8.1.” in Sentence (1) by “Tables 2.5.8.1.A. and 2.5.8.1.B.”;

        2. by inserting the following before Table 2.5.8.1.:

          Table 2.5.8.1.A.

          Maximum Permitted Hydraulic Loads Drained to a Wet Vent Serving Fixtures on the Same Storey

          Forming Part of Sentence 2.5.8.1.(1)

          |

          |


          Size of Wet Vent for


          a


          Maximum Hydraulic Load,

          |

          |

          |

          |

          Storey,

          inches

          fixture

          units

          |

          |

          |





          |

          |

          1

          1/4

          1


          |

          |

          1

          1/2

          2


          |

          |

          2


          5


          |

          |

          3


          18


          |

          |

          |

          4


          120


          |

          |






          ”;


        3. by replacing the title of Table 2.5.8.1. by “Table 2.5.8.1.B.”;

        (28.1) in Article 2.5.8.4., by replacing Sentence (5) by the following:

        “(5) At least one soil-or-waste stack or vertical soil-or-waste pipe must extend into a stack vent or into a vent pipe that is terminated in open air. That soil-or-waste stack or vertical soil-or-waste pipe must be as far as possible from the building sewer and have a minimum size of 3 inches up to the outlet on the roof.”;

        (28.2) in Article 2.5.9.2., by replacing “shall only be used” in Sentence (1) by “may only be installed”;

      4. in Article 2.6.1.1., by adding the following after Sentence (2):

      “(3) In a hot water distribution system with a recirculation loop, the temperature of the water in the loop shall not be less than 55 oC when the water is circulating. (See A-2.6.1.12.(1) in Appendix A).

      1. The recirculation loop referred to in Sentence (3) may operate intermittently.

      2. The recirculation loop referred to in Sentence (3) may be replaced by a self-regulating heat tracing system.”;

      (29.1) in Article 2.6.1.6.,

      1. by replacing “Every” in Sentence (1) by “Subject to Sentences (3) and (4), every”;

      2. by adding the following after Sentence (2):

      “(3) The maximum water consumption of water closets must be 6.0 L/flush.

      1. The maximum water consumption of urinals must be 1.9 L/flush.

      2. Automatic flush tank urinals are prohibited.”;

      (30) in Article 2.6.1.7.,

      (1) in Sentence (1)

      1. by striking out “and” at the end of Clause (a);

      2. by replacing “distribution system.” in Clause (b) by “distribution system, and”;

      3. by adding the following after Clause (b):

      “(c) that has a drain complying with the requirements of Sentence (5).”;

      1. in Sentence (10)

        1. by replacing “The” in the part preceding Clause (a) by “Subject to Clause (d), the”;

        2. by replacing “25 mm” in Clause (a) by “75 mm”;

        3. by replacing “, and” in Clause (b), by “, without being less than 1 1/4 inches;”;

        4. by inserting the following after Clause (c):

      “(d) not be required to have a fixture drain where the relief valve discharge pipe conforms to Sentence (5).”;

      1. in Article 2.6.1.9., by replacing Sentence (1) by the following:

        “(1) Water distribution systems shall be protected against water hammers by prefabricated water-hammer arresters.

        (See Appendix A.)”;

        (31.1) by striking out Article 2.6.1.10.;

        (31.2) in Article 2.6.1.11., by replacing “by Article 2.6.2.6.” in Sentence (1) by “by Sentence 2.6.2.1.(3)”;

      2. in Article 2.6.1.12., by replacing Sentence (1) by the following:

      (1) The temperature control device of water heaters shall be set so that the temperature of stored water is not less than 60 °C. (See Appendix A.)”;

      1. in Article 2.6.2.1., by adding the following after Sentence (3):

        “(4) In the case of backflow preventers that, according to CSA B64.10, Selection and Installation of Backflow Prevention Devices, require testing after installation, the person testing the backflow preventers must hold a certificate issued in accordance with section 5 of CSA B64.10.1, Selection and Installation of Backflow Preventers/Maintenance and Field Testing of Backflow Preventers, by an organization or association certified by AWWA. ;

      2. in Article 2.6.2.4.,

        (a) by replacing Sentence (2) by the following:

        “(2) Subject to Sentence (4), potable water system connections to fire sprinkler and standpipe systems shall be protected against backflow caused by backsiphonage or back pressure in conformance with the following Clauses:

        1. residential partial flow-through fire sprinkler/standpipe systems in which the pipes and fittings are constructed of potable water system materials shall be protected by a dual check valve backflow preventer conforming to one of the following standard:

          Updated to March 1 2021

          1. CSA B64.6.1, Dual Check Valve, Backflow Preventers for Fire Systems (DuCF), or

          2. CSA B64.6, Dual Check Valve, (DuC) Backflow Preventers,

        2. Class 1 fire sprinkler/standpipe systems shall be protected by a single check valve backflow preventer or by a dual check valve backflow preventer, provided that the systems do not use antifreeze or other additives of any kind and that the pipes and fittings are constructed of potable water system materials. The backflow preventer shall conform to one of the following standards:

          1. CSA B64.9, Single Check Valve Backflow Preventers, for Fire Protection Systems (SCVAF), or

          2. CSA B64.6, Dual Check Valve (DuC) Backflow Preventers,

        3. Class 1 fire sprinkler/standpipe systems not covered by Clause (b) as well as Class 2 and Class 3 fire sprinkler/standpipe systems shall be protected by a double check valve backflow preventer, provided that the systems do not use antifreeze or other additives of any kind. The backflow preventer shall conform to one of the following standards:

          1. CSA B64.5.1, Double Check Valve Backflow Preventers for Fire Protecton Systems (DCVAF), or

          2. CSA B64.5, Double Check Valve (DCVAF) Backflow Preventers,


        4. Class 1, Class 2 and Class 3 fire sprinkler/standpipe systems in which antifreeze or other additives are used shall be protected by a reduced pressure principle backflow preventer installed on the portion of the system that uses the additives and the balance of the system must be protected as required by Clause (b) or (c). The backflow preventer shall conform to one of the following standards:

          1. CSA B64.4.1, Reduced Pressure Principle Backflow Preventers for Fire Protection Systems (RPF), or

          2. CSA B64.4, Reduced Pressure Principle (RP) Backflow Preventers,

        5. Class 4 and Class 5 fire sprinkler/standpipe systems shall be protected by a reduced pressure principle

          backflow preventer conforming to one of the following standards:

          1. CSA B64.4.1, Reduced Pressure Principle Backflow Preventers for Fire Protection Systems (RPF), or

          2. CSA B64.4, Reduced Pressure Principle (RP) Backflow Preventers,

        6. Class 6 fire sprinkler/standpipe systems shall be protected by a double check valve backflow preventer

          conforming to one of the following standards:

          1. CSA B64.5.1, Double Check Valve Backflow Preventers for Fire Protection Systems (DCVAF), or

          2. CSA B64.5, Double Check Valve (DCVA) Backflow Preventers, or

        7. where a potentially severe health hazard may be caused by backflow, Class 6 fire sprinkler/standpipe systems shall be protected by a reduced pressure principle backflow preventer conforming to one of the following standards:

        1. CSA B64.4.1, Reduced Pressure Principle Backflow Preventers, for Fire Protection Systems (RPF), or

        2. CSA B64.4, Reduced Pressure Principle (RP) Backflow Preventers. (See Appendix A.);

        (b) by replacing Sentence (4) by the following:

        “(4) Where a reduced pressure principle backflow preventer is required on a water service pipe at a fire service connection located on the same premises as the fire service pipe in Class 3, 4, 5 and 6 fire sprinkler/ standpipe systems, a reduced pressure principle backflow preventer shall also be required on the fire service connection and conform to one of the following standards:

        1. CSA B64.4.1, Reduced Pressure Principle Backflow Preventers for Fire Protection Systems (RPF);

        2. CSA B64.4, Reduced Pressure Principle (RP) Backflow Preventers.”;

        (34.1) in Article 2.6.3.2., by replacing “in Table 2.6.3.2.A.” in Sentence (2) by “in Table 2.6.3.2.A.,

        2.6.3.2.B. or 2.6.3.2.C.”;

        (34.2) in Table 2.6.3.2.A. of Article 2.6.3.2.,

        1. by replacing


          |


          |


          |


          |


          |


          |


          |


          |


          |

          |

          Bathtub

          |


          |


          |


          |


          |


          |


          |


          |

          |

          with 3/4

          |

          3/4

          |

          7.5

          |

          7.5

          |

          10

          |

          7.5

          |

          7.5

          |

          10

          |

          |

          inch

          |


          |


          |


          |


          |


          |


          |


          |

          |

          spout

          |


          |


          |


          |


          |


          |


          |


          |

          |     |    |    |     |    |    |    |    |



          by the following:


          |


          |


          |


          |


          |


          |


          |


          |


          |

          |

          Bathtub

          |


          |


          |


          |


          |


          |


          |


          |

          |

          with 3/4

          |

          3/4

          |

          2.25

          |

          2.25

          |

          3

          |

          4.5

          |

          4.5

          |

          6

          |

          |

          inch

          |


          |


          |


          |


          |


          |


          |


          |

          |

          spout

          |


          |


          |


          |


          |


          |


          |


          |

          |     |    |    |     |    |    |    |    |

        2. by striking out the following:


          |


          |


          |


          |

          |


          |


          |

          |


          |

          |

          Urinal,

          |


          |


          |

          |


          |


          |

          |


          |

          |

          with

          |

          3/4

          |

          (6)

          |

          - |

          (6)

          |

          (6)

          |

          - |

          (6)

          |

          |

          direct

          |


          |


          |

          |


          |


          |

          |


          |

          |

          flush

          |


          |


          |

          |


          |


          |

          |


          |

          |

          valve

          |


          |


          |

          |


          |


          |

          |


          |

          |     |    |    |     |    |    |    |    |

          |


          |


          |


          |

          |


          |


          |

          |


          |

          |

          Urinal,

          |


          |


          |

          |


          |


          |

          |


          |

          |

          with

          |

          1/2

          |

          2

          |

          - |

          2

          |

          4

          |

          - |

          4

          |

          |

          self-

          |


          |


          |

          |


          |


          |

          |


          |

          |

          closing

          |


          |


          |

          |


          |


          |

          |


          |

          |

          metering

          |


          |


          |

          |


          |


          |

          |


          |

          |

          valve

          |


          |


          |

          |


          |


          |

          |


          |

          |     |    |    |     |    |    |    |    |

          |


          |


          |


          |

          |


          |


          |

          |


          |

          |

          Water

          |


          |


          |

          |


          |


          |

          |


          |

          |

          Closet,

          |

          1

          |

          (6)

          |

          - |

          (6)

          |

          (6)

          |

          - |

          (6)

          |

          |

          with

          |


          |


          |

          |


          |


          |

          |


          |

          |

          direct

          |


          |


          |

          |


          |


          |

          |


          |

          |

          Flush

          |


          |


          |

          |


          |


          |

          |


          |

          |

          valve

          |


          |


          |

          |


          |


          |

          |


          |

          |     |    |    |     |    |    |    |    |


        3. by replacing “Table 2.6.3.2.D.” at the bottom of the Table in note (2) by “Table 2.6.3.2.B., 2.6.3.2.C. or 2.6.3.2.D.”;

        4. by striking out the following note at the bottom of the Table:


        (6) For fixture unit values for fixtures with direct flush valves, see Sentence 2.6.3.2.(4) and Tables

        2.6.3.2.B. and 2.6.3.2.C.”;

        (34.3) by replacing Tables 2.6.3.2.B. and 2.6.3.2.C. by the following:

        Table 2.6.3.2.B.

        Sizing of Water Distribution Systems for Urinals with Direct Flush Valves

        Forming Part of Sentences 2.6.3.2.(4) and 2.6.3.4.(5)

        |

        |


        Fixture or

        |

        |


        Minimum Size

        |

        |


        Private Use Hydraulic

        |

        |


        Public Use

        |

        |

        |

        Device

        |

        of Supply Pipe,

        |

        Load, fixture units

        |

        Hydraulic Load

        |

        |


        |

        inches

        |


        |

        fixture units

        |

        |

        |

        |            |         |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        | | | Cold | Hot | Total | Cold | Hot |Total|

        |        |         |    |  |    |  |  |  |

        |



        |


        |


        |

        |


        |


        |

        |


        |

        |

        Urinal

        with

        |

        3/4

        |

        -

        |

        - |

        -

        |

        5

        |

        - |

        5

        |

        |

        Direct

        flush

        |


        |


        |

        |


        |


        |

        |


        |

        |

        valve


        |

        1/2

        |

        2

        |

        - |

        2

        |

        4

        |

        - |

        4

        |

        |        |         |    |  |    |  |  |

                   |

        Table 2.6.3.2.C.

        Sizing of Water Distribution Systems for Water Closets with Direct Flush Valves

        Forming Part of Sentences 2.6.3.2.(4) and 2.6.3.4.(5)

        |


        |


        |



        |


        |

        |

        Fixture or

        |

        Minimum Size

        |

        Private Use

        Hydraulic

        |

        Public Use

        |

        |

        Device

        |

        of

        Supply

        Pipe,

        |

        Load,

        fixture

        units

        |

        Hydraulic Load

        |

        |


        |


        inches


        |




        |

        fixture units

        |

        |


        |




        |




        |


        |

        |

        |

        |            |         |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        | | | Cold | Hot | Total | Cold | Hot |Total|

        |        |         |    |  |    |  |  |  |

        |



        |


        |


        |

        |


        |

        |

        |

        |

        |

        Water

        Closet

        |


        |


        |

        |


        |

        |

        |

        |

        |

        with

        direct

        |

        1

        |

        6

        |

        - |

        6

        |

        10 |

        - |

        10 |

        |

        flush

        valve

        |


        |


        |

        |


        |

        |

        |

        |

        |        |         |    |  |    |  |  |  |


        (34.4) in Article 2.6.3.4., by replacing “to Table 2.6.3.2.A.” in Sentence (2) by “to Tables 2.6.3.2.A.,

        2.6.3.2.B. and 2.6.3.2.C.”;

        (34.5) by striking out the note at the bottom of Table 2.6.3.4.;

        (34.6) in Article 2.6.3.5., by replacing “pipe and fitting manufacturer.” at the end of Sentence (1) by “pipe and fitting manufacturer without ever exceeding 3.0 m/s.”;

      3. in Article 2.7.3.2., by replacing “An outlet” in the part of Sentence (1) preceding Clause (a) by “Subject to Sentence (2) of Article 2.7.4.1., an outlet”;

        (35.1) in Article 2.7.4.1., by replacing Sentence (2) by the following:

        “(2) Non-potable water systems must only be used to supply

        1. water closets,

        2. urinals, or

        3. sinks in tourist establishments referred to in Chapter V.1 of the Regulation respecting the quality of drinking water (chapter Q-2, r. 40).”;

      (36) in Table 2.8.1.1. of Article 2.8.1.1.,

      1. by adding the following after Article 2.1.3.2.:

        |

        |


        2.1.4.1.


        Structural


        Movement

        |

        |

        |



        |

        |

        |(1)

        |

        |

        |

        |


        [F23,F43-OS3.4]

        |

        |

        |

        |

        |

        |

        |

        |

        |


        [F23-OH1.1]

        |

        |

        |

        |

        |

        |

        |

        |

        |


        [F23-OH2.1,OH2.4]

        |

        |

        |

        |

        |

        |

        |

        |

        |


        [F23-OH5]

        |

        |

        |

        |

        |

        |

        |

        |

        |


        [F43-OH2.1,OH2.4]

        |

        |

        |

        |

        |

        |

        |

        |

        |


        [F43-OH5]

        |

        |

        |

        |

        |

        |

        |


        [F23,F43-OP5]

        |

        |

        |                    |


        |



        ”;

        (a.0.1) by adding the following after Sentence (8) of Article 2.2.2.2.:


        |

        |

        |

        |(9)

        | [F80-OH2.1,OH2.4]

        |

        |

        |                   |

        |

        | |

        |

        | [F80-OS3.1] |

        |                    |                   |

        |

        |

        |

        |(10)

        | [F80-OH2.1,OH2.4]

        |

        |

        |                   |

        |

        | |

        |

        | [F80-OS3.1] |

        |                    |                   |

        ”;

        (a.1) by skriking out Sentence (2) of Article 2.2.3.1. and by adding the following after Sentence (5) of that Article:


        | | |

        |(6) | [F81-OH1.1] |

        |                    |                   |

        ”;

      2. by adding the following after Sentence (2) of Article 2.2.3.2.:


        |

        |

        |

        |(3)

        | [F80-OH2.1,OH2.3,OH2.4]

        |

        |                    |                   |

        |

        |

        |

        |(4)

        | [F-80-0H2.1,0H2.3,0H2.4][F43-OH5]

        |

        |                    |

                                                                                                     |

        ”;

      3. (subparagraph revoked);

        (c.1) by striking out Sentence (3) of Article 2.2.6.7.;”

      4. by adding the following after Article 2.2.6.9.:


        |

        |


        2.2.6.10.


        Stainless


        Steel


        Pipes

        |

        |

        |



        |

        |

        |(1)

        |

        |


        [F46-OH2.2]

        |

        |

        |

        |

        [F80-0P5]

        |

        |                                                                                                  

        |

        |(2)

        |                                                                                              

        |

        |


        [F46-OH2.2]

        |

        |

        |

        |

        |

        [F80-0P5]

        |

        |                                                                                                  

        |

        |(3)

        |                                                                                              

        |

        |


        [F80-OH2.1,OH2.3]

        |

        |

        |

        |

        |

        [F80-0P5]

        |

        |                    |                   |

        ”;

      5. (subparagraph revoked);

        (e.1) by replacing Sentences (1), (2), (3) and (4) of Article 2.2.10.7. by the following:



        |

        |

        |

        |(1)

        | [F30,F31,F80-OS3.1,0S3.2]

        |

        |                    |                   |

        |

        |

        |

        |(2)

        | [F31,F80-OS3.2]

        |

        |                    |                   |

        |

        |

        |

        |(3)

        | [F30,F31,F80-OS3.1,0S3.2]

        |

        |                    |                   |

        |

        |

        |

        |(4)

        | [F30,F31,F80-OS3.1,0S3.2]

        |

        |                    |                   |

        |

        |

        |

        |(5)

        | [F31,F80-OS3.2]

        |

        |                    |                   |

        |

        |

        |

        |(6)

        | [F31,0S3.2]

        |

        |                    |

                                                                                                     |

        ”;

      6. by replacing Article 2.2.10.13. by the following:


        | |

        | 2.2.10.13. Service Water Heater |

        | |

        | | |

        |(1) | [F46-OH2.2] |

        |                    |                   |

        |

        |

        |

        |

        | [F80,F81-OP5]

        |

        |                    |                   |

        |

        |

        |

        |

        | [F31,F81-OS3.2]

        |

        |                    |                   |

        |

        |

        |

        |

        | [F43-OS3.4]

        |

        |                    |                   |

        ”;

      7. by adding the following after Article 2.2.10.16.(1):


        |

        |


        2.2.10.17.


        Potable


        Water


        Treatment


        Units

        |

        |

        |


        |

        |

        |

        |

        |(1)

        | [F70,F81,F46-OH2.1,OH2.2,OH2.3]

        |

        |                                                                                                  

        |

        |                                                                                              

        |

        |

        |

        |(2)

        | [F70,F81,F46-OH2.1,OH2.2,OH2.3]

        |

        |                                                                                                  

        |

        |                                                                                              

        |

        |

        |

        |(3)

        | [F70,F81,F46-OH2.1,OH2.2,OH2.3]

        |

        |                                                                                                  

        |

        |                                                                                              

        |

        |

        |

        |(4)

        | [F70,F81,F46-OH2.1,OH2.2,OH2.3]

        |

        |                                                                                                  

        |

        |                                                                                              

        |

        |

        |

        |(5)

        | [F70,F81,F46-OH2.1,OH2.2,OH2.3]

        |

        |                    |                   |

        |

        |


        2.2.10.18.


        Backwater


        Valves

        |

        |

        |


        |

        |

        |

        |

        |(1)

        | [F80-OH2.1]

        |

        |                    |                   |

        |

        |


        2.2.10.19.


        Floor


        Drains


        and


        Shower


        Drains

        |

        |

        |


        |

        |

        |(1)

        |

        |


        [F80-OH2.1,OH2.4]

        |

        |

        |

        |

        |


        2.2.10.20.


        Roof


        Drains

                                                                                                         |                  |

        |

        |

        |


        |

        |

        |

        |

        |(1)

        | [F80-OP5]

        |

        |

        |

        |

        |                   |

        | |

        | [F80-OS2.1] |

        |

        |

        |


        2.2.10.21.


        Trap


        Seal


        Primers

                                                                                                         |                  |

        |

        |

        |


        |

        |

        |

        |

        |(1)

        | [F80-OH1.1]

        |

        |                    |                   |

        |

        |


        2.2.10.22.


        Air


        Gaps

        |

        |

        |


        |

        |

        |

        |

        |(1)

        | [F80-OH2.1,OH2.2,OH2.3]

        |

        |                    |                   |

        | |

        |

        |

        2.2.10.23.

        Pipe

        Hangers

        and

        Supports

        |

        |

        |

        |

        |

        |(1)

        | [F20-OH2.1]

        |

        |

        |                   |

        |

        | |

        |

        | [F20-OS3.1] |

        |

        |                   |

        |

        | |

        |

        | [F80-OP5] |

        |                    |                   |

        |






        |

        |

        2.2.10.24.

        Floor

        Drain

        Trap

        Seals

        |

        |


        |

        |

        |

        |

        |(1)

        | [F80,F82-OH1.1]

        |

        |                    |                   |

        ”;

      8. (subparagraph revoked);

      9. (subparagraph revoked);

        (i.1) by adding the following after Article 2.3.6.7.:


        | |

        | 2.3.6.8. Smoke Tests |

        | |

        | | |

        |(1) | [F81-OH1.1] |

        | |                   |

        | | |

        | | [F81-OH2.1,OH2.3] |

        |                    |                   |

        ”;

        (j) by adding the following after Sentence (5) of

        Article 2.4.2.1.:




        |

        |

        |

        |(6)

        | [F81-OH1.1]

        |

        |                    |                   |

        |

        |

        |

        |(7)

        | [F81-OH1.1]

        |

        |                    |                   |

        ”;

        (j.1) by adding the following after Sentence (1) of Article 2.4.3.5.:


        | | |

        |(2) | [F72-OH2.1] |

        |                    |                   |

        ”;

        (k) by adding the following after Article 2.4.3.6.:



        |


        |

        | 2.4.3.7. Retention Pit


        |

        |


        |

        | |


        |

        |(1) |

        |                    |

        [F60,F61-OH1.1]

        |

        |

        | |


        |

        |(2) |

        [F81-OH1.1]

        |

        | |


        |

        | |


        |

        | |

        |                    |

        [F81-OH2.1]

        ]

        |

        | |


        |

        |(3) |

        |                    |

        [F81-OH1.1]

        |

        |

        | |


        |

        |(4) |

        |                    |

        [F81-OH1.1]

        |

        |

        | |


        |

        |(5) |

        [F40-OH1.1]

        |

        | |


        |

        | |


        |

        | |

        |                    |

        [F30-OS3.1]

        |

        |

        | |


        |

        |(6) |

        [F81-OH2.1,OH2.3]

        |

        | |


        |

        | |


        |

        | |

        |                    |

        [F81-OP5]

        |

        |

        | |


        |

        |(7) |

        [F81-OH2.1,OH2.2]

        |

        | |


        |

        | |


        |

        | |

        |                    |

        [F72-OH2.1]

        |

        |

        | |


        |

        |(8) |

        |                    |

        [F81-OH2.1]

        |

        |

        | |


        |

        |(9) |

        [F72-OH2.1]

        |

        | |


        |

        | |


        |

        | |

        [F81-OS2.1]

        |

        | |


        |

        | |


        |

        | |

        |                    |

        [F81-OP5]

        |

        |

        | |


        |

        |(10) |

        |                    |

        [F81-OH2.1]

        |

        |

        | |


        |

        |(11) | [F81-OH1.1] |

        |                    |                   |

        | | |

        |(12) | [F81-OH2.1] |

        | |                   |

        | | |

        | | [F43-OH1.1] |

        |                    |                   |

        ”;

        (k.1) by adding the following after Sentence (1)

        of Article 2.4.4.1.:




        |

        |

        |

        |(2)

        | [F81-OH2.1]

        |

        |                    |                   |

        |

        |

        |

        |(3)

        | [F43-OS3.4]

        |

        |                    |                   |

        ”;

        1. by adding the following after Sentence 2.4.5.4.(1):


          | | |

          |(2) | [F81-OH2.1] |

          |                    |                   |

          ”;

        2. by adding the following after Sentence 2.4.5.5.(1):


          | | |

          |(2) | [F81-OH1.1] |

          |                    |                   |

          ”;

          (m.0.1) by adding the following after Sentence (7) of Article 2.4.6.3.:


          |

          |

          |

          |(8)

          | [F81-OH2.1]

          |

          |

          |                   |

          |

          | |

          |

          | [F43-OH1.1] |

          |                    |                   |

          ”;

          (m.0.2) by striking out Sentence (6) of Article 2.4.6.4.: (m.1) by striking out Article 2.4.6.5.”;

          (m.2) by adding the following after Sentence (9) of Article 2.4.7.1.:


          |

          |

          |

          |(10

          | [F62-OH1.1]

          |

          |

          |                   |

          |

          | |

          |

          | [F72-OH2.3] |

          |                    |                   |

          ”;

          (m.3) by adding the following after Sentence (3) of Article 2.5.6.2.:


          | | |

          |(4) | [F43-OS3.4,OH1.1] |

          |                    |                   |

          ”;

        3. by adding the following after Sentence (2) of Article 2.6.1.1.:


          |

          |(3)

          |

          |


          [F40-OH1.1]

          |

          |

          |                    |

          |

          |

          |(4)

          |

          |


          [F40-OH1.1]

          |

          |

          |                    |

          |

          |

          |(5)

          |

          |


          [F40-OH1.1]

          |

          |

          |                    |


          |



          ”;



        4. by adding the following after Sentence (2) of Article 2.6.1.6.:


          | | |

          |(3) | [F130-OE1.2] |

          |                    | |

          | | |

          |(4) | [F130-OE1.2] |

          |                    | |

          | | |

          |(5) | [F130-OE1.2] |

          |                    | | ”;

        5. by striking out Article 2.6.1.10.

      (37) (paragraph revoked);

      (37.0.1) note A-1.3.1.2.(1) in Table A-1.3.1.2.(1):

      1. by inserting the following reference:


        |


        |

        |

        |

        |

        |

        ASME

        | A112.3.1-2007

        | Stainless Steel

        | Table A-2.2.5.,

        |

        |

        |

        |

        Drainage Systems for

        | 2.2.6 and

        2.2.7.

        |

        |

        |

        |

        Sanitary DWV, Storm,

        |


        |

        |

        |

        |

        and Vacuum

        |


        |

        |

        |

        |

        Applications, Above

        |


        |

        |

        |

        |

        and Below-Ground

        |


        |

        |       |          |            |         |

        ”;

        before the reference:


        |


        |

        |

        |

        |

        |

        ASME

        | B16.3-2006

        | Malleable Iron

        | Table A-2.2.5.,

        |

        |


        |

        | Threaded Fittings,

        | 2.2.6 and 2.2.7.

        |

        |


        |

        | Classes 150 and 300

        |

        |

        |       |          |            |         |

        ”;

      2. by inserting the following reference:


        |


        |

        |

        |

        |

        |

        ASME

        | B16.11-2009

        | Forged Fittings,

        | Table A-2.2.5.,

        |

        |


        |

        | Socket-Welding and

        | 2.2.6 and 2.2.7.

        |

        |


        |

        | Threaded

        |

        |

        |       |          |            |         |

        ”;

        after the reference:


        |


        |

        |

        |

        |

        |

        ASME

        | B16.4-2006

        | Gray Iron Threaded

        | Table A-2.2.5.,

        |

        |


        |

        | Fittings, Classes

        | 2.2.6, 2.2.7.

        |

        |


        |

        | 125 and 250

        |

        |

        |       |          |            |         |

        ”;

      3. by inserting the following references:


        |


        |




        |


        |


        |

        |

        ASTM

        |

        A

        312/A

        312M-09

        |

        Standard

        |

        Table A-2.2.5.,

        |

        |


        |




        |

        Specification for

        |

        2.2.6., 2.2.7.

        |

        |


        |




        |

        Seamless, Welded,

        |


        |

        |


        |




        |

        and Heavily Cold

        |


        |

        |


        |




        |

        Worked Austenitic

        |


        |

        |


        |




        |

        Stainless Steel Pipes

        |


        |

        |       |          |           |         |

        |


        |



        |


        |


        |

        |

        ASTM

        |

        A

        778-01(2009)e1

        |

        Standard

        |

        Table A-2.2.5.,

        |

        |


        |



        |

        Specification for

        |

        2.2.6. and 2.2.7.

        |

        |


        |



        |

        Welded,

        |


        |

        |


        |



        |

        Unannealed

        |


        |

        |


        |



        |

        Austenitic Stainless

        |


        |

        |


        |



        |

        Steel Tubular

        |


        |

        |


        |



        |

        Products

        |


        |

        |       |          |           |         |


        after the reference:


        |


        |




        |


        |


        |

        |

        ASTM

        |

        A

        53/A

        53M-07

        |

        Pipe, Steel, Black

        |

        Table A-2.2.5.,

        |

        |


        |




        |

        and Hot-Dipped,

        |

        2.2.6. and 2.2.7.

        |

        |


        |




        |

        Zinc-Coated,

        |


        |

        |


        |




        |

        Welded and

        |


        |

        |


        |




        |

        Seamless

        |


        |

        |       |          |           |         |

        ”;

      4. by inserting the following reference:



      |

      |


      CSA

      |

      |


      CAN/CSA B481

      |

      |


      Grease Interceptors

      |

      |


      A-2.4.4.3.(1)

      |

      |

      |


      |

      Series 07

      |


      |


      |

      |       |          |           |         |

      after the reference:


      |


      |



      |


      |


      |

      |

      CSA

      |

      CAN/CSA

      B182.6-

      |

      Profile Polyethylene

      |

      Table A-2.2.5.,

      |

      |


      |

      06


      |

      (PE) Sewer Pipe

      |

      2.2.6. and 2.2.7.

      |

      |


      |



      |

      and Fittings For

      |


      |

      |


      |



      |

      Leak-Proof Sewer

      |


      |

      |


      |



      |

      Applications

      |


      |

      |       |          |           |         |


      (37.0.2) in Tables A-2.2.5., 2.2.6. and 2.2.7.,

      1. by replacing the reference:


        |


        | | |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        Welded

        |ASTM |2.2.6.7.|

        P

        | N

        | N

        | P

        | N

        |

        P(9)| P(9)

        |

        P(9)| P(9)

        |

        |

        and |A53/A|

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        seamless |53M |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        steel | |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        galvanized| |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        pipe | |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |     |  |    |  |  |  |  |  |  |  |  |  |


        by the following reference:


        |


        | | |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        Welded

        |ASTM |2.2.6.7.|

        P

        | N

        | N

        | P

        | N

        |

        N(9)| N(9)

        |

        N(9)| N(9)

        |

        |

        and |A53/A|

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        seamless |53M |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        steel | |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        galvanized| |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |

        pipe | |

        | |

        |

        |

        |

        |

        |

        |

        | |

        |     |  |    |  |  |  |  |  |  |  |  |  |

        ”;

      2. by adding the following references:


        | | | | | | | | | | | | |

        | Stainless | ASTM A | 2.2.6.10. | N | N | N | N | N | P | P | P | P |

        | steel | 312/A | (1) | | | | | | | | | |

        | pipes | 312M | | | | | | | | | | |

        | Type 304, | ASTM A | | | | | | | | | | |

        | 304L, 316 | 778 | | | | | | | | | | |

        | or 316L | | | | | | | | | | | |

        |     |    |     |  |  |  |  |  |  |  |  |  |

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        Stainless

        |

        ASME

        |

        2.2.6.10.

        |

        N

        |

        N

        |

        N

        |

        N

        |

        N

        |

        P

        |

        P

        |

        P

        |

        P

        |

        |

        steel

        |

        B16.11

        |

        (2)

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        fittings

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        Type 304,

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        304L, 316

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        or 316L

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |     |    |     |  |  |  |  |  |  |  |  |  |

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        Stainless

        |

        ASME

        |

        2.2.6.10.

        |

        P

        |

        N

        |

        N

        |

        P

        |

        N

        |

        N

        |

        N

        |

        N

        |

        N

        |

        |

        steel

        |

        A112.3.1|

        (3)

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        pipes and

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        fittings

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        Type 304

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |     |    |     |  |  |  |  |  |  |  |  |  |

        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |


        |

        |

        Stainless

        |

        ASME

        |

        2.2.6.10.

        |

        P

        |

        P

        |

        P

        |

        P

        |

        P

        |

        N

        |

        N

        |

        N

        |

        N

        |

        |

        steel

        |

        A112.3.1|

        (3)

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        pipes and

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        fittings

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        Type 316L

        |

        |


        |

        |

        |

        |

        |

        |

        |

        |

        |

        |

        |     |    |     |  |  |  |  |  |  |  |  |  |


        at the end after the reference:


        | | | | | | | | | | | | |

        | Lead waste | - |2.2.7.8.|P(5)(6) | P | N |P(5)(6) | P | N | N | N | N |

        | pipe | | | | | | | | | | | |

        |      |  |    |  |  |  |  |  |  |  |  | |

        ”;

      3. by replacing note (9) at the bottom of the Table by the following: “(9) Deleted.”;

      (37.0.3) by striking out note A-2.2.6.7.(3);”;

      (37.1) by replacing note A-2.2.10.7. by the following:

      A-2.2.10.7. Water Temperature Control. Hot water produced by a service water heater must be at a minimum temperature of 60 °C to prevent the development of potentially fatal bacteria. At that temperature, water causes second degree burns to the skin in 1 to 5 seconds. Consequently, Article 2.2.10.7. provides for the installation and adjustment of valves, mixing valves and limiting devices to provide a water outlet temperature that is lower than the temperature produced by a service water heater. Compliance with that Article reduces the risk of scalding in showers and bathtubs, where severe burns occur, and reduces the risk of thermal shock that may occur in the shower and lead to falls.

      Children, the elderly and persons with disabilities are particularly at risk of scald burns because they are not always able to remove themselves quickly from a situation that could lead to burns. At 49 °C, the time for a scald burn to occur on a healthy adult is nearly 10 minutes, whereas the time for a skin burn to occur on an elderly is 2 minutes, because the elderly’s skin is thinner and less vascularized. For those persons, a temperature of 43 °C provides a more adapted protection against burns because they can only occur after a number of hours of exposure.

      In private seniors’ residences and care occupancies, Article 2.2.10.7. provides that the valves, mixing valves and limiting devices must be adjusted to provide a maximum water outlet temperature at 43 °C. The installation of pressure-balanced valves is also prohibited, because those valves are sensitive to seasonal changes of the cold water temperature and require some settings per year in order not to exceed the prescribed temperature.

      The water outlet temperature at other fixtures, such as lavatories, sinks, laundry trays or bidets, is not addressed by Article 2.2.10.7., but a scald risk may exist at such fixtures nonetheless.”

      1. by replacing Figure A-2.4.2.1.(2) in note A-2.4.2.1.(2) by the following:

      2. by replacing note A-2.4.2.1.(4) by the following:

        “A-2.4.2.1.(4) Soil-or-Waste Pipe Connections.


        A-2.4.2.1.(5) Soil-or-Waste Pipe Connections.


        A-2.4.2.1.(6) and (7) Suds pressure zones. High sudsing detergents used in clothes washers produce suds that tend to disrupt the venting action of venting systems and can also spread through the lower portions of multi-storey drainage systems. The more turbulence, the greater the suds. One solution that avoids the creation of suds pressure zones involves connecting the suds-producing stack downstream of all other stacks and increasing the size of the horizontal building drain to achieve a greater flow of air and water. Using streamlined fittings, such as wyes, tends to reduce suds formation. Check valves or backwater valves in fixture outlet pipes have also been used to correct problem installations.



        Figure A-2.4.2.1.(6) and (7) Suds pressure zones

        Figure A-2.4.2.1.(6) and (7)

        Suds pressure zones

      3. by adding the following after note A-2.4.3.3.(1):

      “A-2.4.3.7. Retention Pit



      Figure A-2.4.3.7.

      Retention Pit.

      Figure A-2.4.3.7.

      Retention Pit.

      (40.1) by replacing note A-2.4.4.3.(1) by the following:

      A-2.4.4.3.(1) Grease Interceptors. Grease interceptors may be required when it is considered that the discharge of fats, oil or grease may impair the drainage system. Further information on the sizing, selection, location, installation and maintenance of grease interceptors can be found in CAN/CSA B481 Series.”;

      (41) in note A-2.4.5.3.(1),

      1. by striking out “A trap or sump may be provided specifically for the subsoil drains, or the trap of a floor drain or storm water sump as shown in Figure A-2.4.5.3.(1) may be used.”;

      2. by replacing Figure A-2.4.5.3.(1) by the following:


      Figure A-2.4.5.3.(1) Subsoil Drainage Connection


      Figure A-2.4.5.3.(1) Subsoil Drainage Connection

      1. by striking out note A-2.4.5.4.(1);

      2. in note A-2.4.5.5.(1), by striking out “Periodic manual replenishment of the water in a trap is considered to be an equally effective means of maintaining the trap seal in floor drains in residences.”;

      3. by adding the following after note A-2.4.5.5.(1):

        A-2.4.5.5.(2) Maintaining Trap Seals in Floor Drains in Dwelling Units. Periodic manual replenishment of the water in a trap maintains the trap seal in floor drains in dwelling units.”;

        (44.1) by striking out note A-2.4.6.4.(6);

      4. by replacing note A-2.4.8.2.(1) by the following:

        A-2.4.8.2.(1) Island Fixture Installation.


        Figure A-2.4.8.2.(1)

        Island Fixture Installation.

        Figure A-2.4.8.2.(1)

        Island Fixture Installation.

        (45.1) by replacing note A-2.4.9.3.(3) by the following:

        A-2.4.9.3.(3) Standpipe Illustration.

        Figure A-2.4.9.3.(3)

        Standpipe Illustration

        Figure A-2.4.9.3.(3)

        Standpipe Illustration

        (46) in note A-2.5.2.1.,

        1. by replacing Figure A-2.5.2.1. –C by the following:

        2. by replacing Figure A-2.5.2.1.-E by the following:

        3. by replacing Figure A-2.5.2.1.-F by the following:

        4. by replacing Figure A-2.5.2.1.-L by the following:


      (46.1) by replacing note A-2.5.5.2. by the following:

      “A-2.5.5.2. Venting of Oil Interceptors.


      (47) by replacing note A-2.6.1.12.(1) by the following:

      “A-2.6.1.12.(1) Service Water Heater. Water in a service water heater or in a distribution system that is kept at less than 60 °C permits Legionella bacteria to survive and thrive. Water heated at a temperature equal to or greater than 60 °C reduces bacterial contamination of the hot water distribution system.”;

      (48) in note A-2.6.3.1.(2),

      1. by inserting the following after the title “Method for Small Commercial Buildings”:

        ““Small commercial building” means a building of groups A, D, E, F2 or F3, as defined in Subsection 3.1.2., Division B of the NBC, not more than 3 storeys in building height according to the definition of the NBC, and having a building area not more than 600 m2.”;

      2. by replacing Table A-2.6.3.1.(2)A. by the following:


      (49) by striking out “and irrigating lawns and gardens” after “such as flushing toilets” in note A-2.7.4.1.

      O.C. 294-2008, s. 1; O.C. 939-2009, s. 6; O.C. 1202-2012, s. 1; O.C. 30-2014, s. 4; I.N. 2014-07-01.

  • The Code is amended in Division C,

    1. by striking out Article 2.2.1.1.;

    2. by replacing Subsection 2.2.2. by the following:


    2.2.2. Plans and Specifications

    2.2.2.1. Requirements

    1. A plumbing contractor or owner-builder may not begin construction work on a plumbing system to which Chapter III of the Construction Code applies unless there are plans and specifications for the work, if the total hydraulic load to be installed exceeds 180 fixture units;

    2. When required, the plans and specifications must be available on the worksite. “2.2.2.2. Content

    1. Plans shall be drawn to scale and show

      1. a plan view of the location and dimension of the drains and cleanouts, the location of fixtures and the

        water distribution system,

      2. an elevation view of the location of fixtures and traps, the dimension of drains, leaders, soil-or-waste stacks, stack vents and vent stacks as well as the water distribution system;

      3. the connection of the subsoil drainage pipe if it enters the building.”;

    (3) by adding the following after Subsection 2.2.2.:

    2.2.3. Approval of Materials

    “2.2.3.1. Approved Materials, Fixtures and Facilities used in a Plumbing System


    1. In a plumbing system, only materials, fixtures or facilities that are certified or approved by one of the following organizations may be used:

      1. Canadian Gas Association (CGA),

      2. Bureau de normalisation du Québec (BNQ),

      3. CSA International (CSA),

      4. IAPMO Research and Testing Inc. (UPC),

      5. Underwriters’ Laboratories of Canada (ULC),

      6. NSF International (NSF),

      7. Canadian General Standards Board (CGSB),

      8. Quality Auditing Institute (QAI),

      9. Intertek Testing Services NA Itd. (ETL),

      10. Underwriters Laboratories Inc. (UL),

      11. Water Quality Association (WQA),

      12. any other organization accredited by the Standards Council of Canada as a certifying organization in the field of plumbing which has notified the Board of its accreditation.


    “2.2.3.2. Sale and lease


    (1) Materials, fixtures or facilities to be used in a plumbing system must be certified or approved by an organization listed in Sentence 2.2.3.1.(1) before being sold or leased.

    “2.2.4. Declaration of Work “2.2.4.1. Application

    (1) A plumbing contractor or owner-builder must declare to the Régie du bâtiment du Québec all construction work performed and to which Chapter III of the Construction Code applies if the work pertains to a new plumbing system or requires the replacement of a service water heater or pipes.

    “2.2.4.2. Submission of the Declaration


    (1) The declaration required under Article 2.2.4.1. shall be forwarded to the Board not later than the twentieth day of the month following the date on which work starts.

    “2.2.4.3. Form


    1. The declaration of work shall be made on the form provided by the Board or on any other document prepared for that purpose.

      “2.2.4.4. Content


      The declaration shall contain

      1. the address of the site where the work is performed,

      2. the name, address and telephone number of the person for whom the work is performed,

      3. the name, address, telephone number and licence number of the plumbing contractor or ownerbuilder, where applicable,

      4. the estimated start and end dates of the construction work,

      5. the nature and type of the work,

      6. the occupancy of the building or facility intended for use by the public and the existing and planned number of storeys, and;

      7. the number of fixtures and service water heaters to be installed.

    “2.2.5. Fees Payable


    “2.2.5.1. Calculation


    1. The following fees shall be paid to the Board by the plumbing contractor or owner-builder, when the plumbing contractor declares the construction work pertaining to plumbing systems for which a declaration is required under Article 2.2.4.1.:

      1. $159.80 for a new single-family detached or semi-detached house or row house,

      2. $96.74 per dwelling unit other than those referred to in Clause (a) for the construction of a new building intended for housing or for the conversion of a building of another nature into a building intended for housing, regardless of the number of fixtures and service water heaters, or

      3. in the case of work other than work referred to in Clauses (a) and (b),

        1. $12.83 per fixture or service water heater, where the work is performed on more than one, or

        2. $22 where the work is performed on only one or no fixture or service water heater.


    2. A plumbing contractor or owner-builder shall pay the following inspection fees to the Board for the inspection of a plumbing system following the issue of a remedial notice provided for in section 122 of the Building Act (chapter B-1.1):

      1. $107.94 for the first hour or any fraction thereof,

      2. half the hourly rate established in Clause (a) for each half-hour or fraction thereof added to the first hour.

    3. A plumbing owner-builder shall pay to the Board the inspection fees fixed in Clauses (a) and (b) of Sentence (2) for the inspection of a plumbing system.

    4. For the approval of a plumbing material, fixture or facility that cannot be certified or approved by one of the organizations listed in Article 2.2.3.1., approval fees corresponding to the amounts established in Clauses (a) and (b) of Sentence (2) shall be paid to the Board.


    “2.2.5.2. Sending


    1. The fees payable under Sentence 2.2.5.1.(1) shall be included with the declaration of work required under Article 2.2.4.1.

    2. The fees payable under Sentences 2.2.5.1.(2), (3) and (4) shall be paid to the Board not later than 30 days after the billing date.”;

    (4) by replacing Subsection 2.3.1. by the following:

    2.3.1. Approval of Alternative Solutions “2.3.1.1. Conditions for Approval

    (1) The proposed alternative solutions shall be approved by the Board on the conditions it sets pursuant to section 127 of the Building Act (chapter B-1.1).”.

    (5) by striking out note A-2.3.1.”.

    O.C. 294-2008, s. 1; O.C. 939-2009, s. 7; O.C. 30-2014, s. 5.