The Quebec Building Code | AMENDMENTS TO STANDARDS

The Quebec Building Code | AMENDMENTS TO STANDARDS

DIVISION 7 AMENDMENTS TO STANDARDS

AMENDMENTS TO STANDARDS

O.C. 875-2003, s. 1; O.C. 991-2018, s. 1.

  • CSA Standard B108 is amended

    1. by replacing the first paragraph in Clause 2 by the following:

      “The documents incorporated by reference into this Code are those indicated below and include any subsequent amendments and editions that may be published.

      Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Code is then the document as adopted by that chapter or regulation.”;

    2. in Clause 3

      1. by replacing the first sentence of the Clause by the following:

        “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by replacing the definition “Approved” by the following:

        Approved: approved or authorized by the Régie du bâtiment du Québec under sections 2.06 and 2.07 of the Construction Code or section 127 or 128 of the Building Act (chapter B-1.1).”;

      3. by replacing the definition “Authority having jurisdiction” by the following: “Authority having jurisdiction: Régie du bâtiment du Québec.”;

      4. by striking out the definition “Certified”;

    3. by adding the following after Clause 6.21:

      “6.22. Every tank used to store and transport compressed natural gas shall be designed, manufactured, tested and marked in accordance with the most recent edition of CSA Standard B51, including any subsequent amendments to the Act respecting pressure vessels (chapter A-20.01) and its regulations that may be published.”.

      O.C. 875-2003, s. 1; O.C. 1172-2005, s. 2; O.C. 120-2006, ss. 1 and 4; O.C. 991-2018, s. 1.

  • CSA Standard B149.1 is amended

    1. by replacing Clause 1.1 by the following:

      “1.1. This Code applies to

      1. gas installations where gas is to be used for fuel purposes, subject to paragraph b;

      2. piping and tubing systems extending from the termination of the gas undertaking’s installations for natural gas or from the distributor’s liquefied petroleum gas tanks; the termination of the gas undertaking’s installations is the point where its piping ends;

      3. natural gas vehicle refuelling appliances and their equipment, excluding storage installations;

      4. gas engines and turbines.”;

    2. by revoking Clause 1.2;

    3. by replacing Clause 1.3 by the following:

      “1.3. Where the term “gas” is used, the requirements of this Code apply equally to and include any of the following gases, type or mixture of them: natural gas, biomethane, manufactured gas and mixtures of propane gas and air, propane, propylene, butanes (normal butane or isobutane) and butylenes.

      Where the term “natural gas” is used, the requirements of this Code apply equally to and include the following gases, type or mixtures of them: natural gas, biomethane and mixtures of propane gas and air.

      Where the term “propane” is used, the requirements of this Code apply equally to and include the following gases, type or mixture of them: propane, propylene, butanes (normal butane or isobutane) and butylenes.”;

    4. by replacing the first paragraph of Clause 2 by the following:

      “The documents incorporated by reference into this Code are those indicated below and include any subsequent amendments and editions that may be published.

      Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Code is then the document as adopted by that chapter or regulation.”;

    5. in Clause 3

      1. by replacing “The following definitions shall apply in this Code:” after the note by “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by replacing the definition “Approved” by the following:

        Approved: approved or authorized by the Régie du bâtiment du Québec under sections 2.06 and 2.07 of the Construction Code or section 127 or 128 of the Building Act (chapter B-1.1).”;

      3. by replacing the definition “Authority having jurisdiction” by the following:

        «Authority having jurisdiction: Régie du bâtiment du Québec.»;

      4. by striking out the definition “Certified”;

      5. by inserting the following after “Gas hose”:

        Gas undertaking (natural gas): undertaking for the distribution of natural gas.”;

      6. by inserting the following after the definition “Dirt pocket (dust pocket)”: “Distributor: undertaking for the distribution of liquefied petroleum gas.”;

      7. by replacing the definition “Installer” by the following:

        Installer: contractor or owner-builder holding the appropriate licence issued under the Building Act.”;

    6. by revoking Clause 4.2;

    7. by replacing Clause 6.7.2(b) by the following:

      “(b) in a chimney, flue, laundry chute, garbage chute or, in the case of an elevator, dumbwaiter or small dumbwaiter, in a sleeve, machine location, machine room, control site or control room;”;

    8. by replacing Clause 6.9.3 by the following:

      “6.9.3. Welding of gas piping shall be performed in compliance with a welding method established and complying with Clauses 7.6, 7.7 and 7.11 of CAN/CSA Standard Z662 by a welder holding the appropriate qualification certificate issued under the Act respecting workforce vocational training and qualification (chapter F-5).”;

    9. by inserting the following after Clause 7.1.3:

      “7.1.4. Boilers converted to gas shall be in compliance with Clauses 9.4.1 and 9.4.2 of CSA Standard B149.3.”;

    10. by replacing Clause 8.2.1 by the following:

      “8.2.1. Subject to the exceptions referred to in the second paragraph and in Clause 8.2.3, an outdoor air supply sized in accordance with Clause 8.2.2 shall be provided to either an enclosure or a structure in which appliances are installed.

      Except for boilers, water heaters and pool heaters that include a finned-tube heat exchanger, an outdoor air supply shall not be required in structures built before 1986 where the doors and windows of that structure have not been replaced after 1985 and the volume of the enclosure or the structure in which the appliances are installed is greater than 50 ft3 per 1,000 Btu/h (4.84 m3 per kW) of the total heat input of all the appliances in the enclosure or the structure.”;

    11. by striking out “and the Structure Complies with Clause 8.2.1 (a) or (b)” and “and Tables 8.3 and 8.4” in the heading of Table 8.1;

    12. by striking out “and the Structure Complies with Clause 8.2.1 (a) or (b)” in the heading of Table 8.2;

    13. by replacing Clause 8.2.3 by the following:

      “8.2.3. An outdoor air supply shall not be required for a mechanically vented water heater with a heat input of 50,000 Btu/h (14.64 kW) or less where there are no other appliances that require an air supply installed in the enclosure or the structure, it is not used to heat the structure, and the volume of the enclosure or the structure is greater than 50 ft3 per 1,000 Btu/h (4.84 m3 per kW) of its heat input.”;

    14. by revoking Clauses 8.2.4 and 8.2.5 and Tables 8.3 and 8.4;

    15. by striking out in Clause 8.2.6 “, provided that the structure is not constructed as described in Clause 8.2.1(a) and does not comply with Clause 8.2.1(b). Otherwise, the volume of the enclosure shall be used.”;

    16. by striking out the reference to Clause 8.2.4 in Clauses 8.3.1, 8.3.3 and 8.3.4;

    17. by inserting the following after Clause 8.13.3:

      “8.13.4. The tables in Annex C shall be used in accordance with the General Venting Requirements (GVR) specified in that Annex.”;

    18. by adding the following paragraph at the end of Clause 8.14.8:

      “Notwithstanding paragraph (g), a vent shall not terminate less than 6 feet (1.8 m) under an awning window.”;

    19. by inserting the following after Clause 8.18.23:

      “8.18.24. The total length of a vent connector shall comply with that provided for in Table C.9 of Annex C or be sized in accordance with a calculation prepared by an engineer.”;

    20. by replacing “in accordance with Clause 8.2.1” in Clause C.2.2 General Venting Requirements (GVR) of Annex C by “after 1985 or where the doors and windows were replaced after 1985”.

      O.C. 875-2003, s. 1; O.C. 120-2006, ss. 1 and 5; O.C. 991-2018, s. 1.

  • CSA Standard B149.2 is amended

    1. by replacing Clauses 1.1 and 1.2 by the following:

      “1.1. This Code applies to

      1. installations intended to store, handle or transfer liquefied petroleum gas; and

      2. installations intended to use liquefied petroleum gas.”;

    2. in Clause 2

      1. by replacing the first paragraph by the following:

        “The documents incorporated by reference into this Code are those indicated below and include any subsequent amendments and editions that may be published.

        Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Code is then the document as adopted by that chapter or regulation.”;

      2. by inserting the following after the reference “NFPA 30B-2011 Code for the Manufacture and Storage of Aerosol Products”:

        “NFPA 68, Standard on Explosion Protection by Deflagration Venting, 2013 Edition.”;

    3. in Clause 3

      1. by replacing “The following definitions shall apply in this Code:” after the note by “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by replacing the definition “Approved” by the following:

        Approved: approved or authorized by the Régie du bâtiment du Québec under sections 2.06 and 2.07 of the Construction Code or section 127 or 128 of the Building Act (chapter B-1.1).”;

      3. by replacing the definition “Authority having jurisdiction” by the following:

        «Authority having jurisdiction: Régie du bâtiment du Québec.»;

      4. by striking out the definition “Certified”;

      5. by inserting the following after the definition “Kiosk”:

        Liquefied petroleum gas: propane, propylene, butanes (normal butane or isobutane), butylene or a mixture of those gases.”;

      6. by replacing the definition “Installer” by the following:

        Installer: contractor or owner-builder holding an appropriate licence issued under the Building Act.”;

    4. by revoking Clause 4.2;

    5. by revoking Clause 5.2.11;

    6. by replacing Clause 6.5.10.2(c) by the following:

      “(c) an explosion relief panel in compliance with standard NFPA 68; or”;

    7. by replacing Clause 7.17.3(e)(iii) by the following:

      “(iii) an explosion relief panel in compliance with standard NFPA 68; or”.

      O.C. 875-2003, s. 1; O.C. 120-2006, ss. 1 and 6; O.C. 991-2018, s. 1.

  • CSA Standard B149.3 is amended

    1. by replacing “D (informative)” in “Annexes” in the Table of Contents by “D (mandatory)”;

    2. by revoking Clause 1.2;

    3. by replacing the first paragraph of Clause 2 by the following:

      “The documents incorporated by reference into this Code are those indicated below and include any subsequent amendments and editions that may be published.

      Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Code is then the document as adopted by that chapter or regulation.”;

    4. in Clause 3

      1. by replacing “The following definitions shall apply in this Code:” after the note by “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by replacing the definition “Approved” by the following:

        Approved: approved or authorized by the Régie du bâtiment du Québec under sections 2.06 and 2.07 of the Construction Code or section 127 or 128 of the Building Act (chapter B-1.1).”;

      3. by replacing the definition of “Authority having jurisdiction” by the following: “Authority having jurisdiction: Régie du bâtiment du Québec.”;

    5. by replacing Clause 5.4.3 by the following:

      “5.4.3. When an electronic-type fuel-air ratio control (FARC) system is used, it shall be in compliance with standard ISO 23552-1 or the provisions of Annex D.”;

    6. by replacing “(informative)” in the title of Annex D by “(mandatory)”;

    7. by replacing the note in Annex D by the following:

      Note: This Annex is a mandatory part of this Code.”;

    8. by replacing the first two paragraphs of Clause D.2 in Annex D by the following:

      “These Guidelines provide a listing of the features that shall be incorporated with electronic-type fuel-air ratio control (FARC) systems.

      The provisions shall be satisfied.”.

      O.C. 875-2003, s. 1; O.C. 1172-2005, s. 3; O.C. 120-2006, s. 7; O.C. 991-2018, s. 1.

  • CSA Standard Z276 is amended

    1. by replacing “D (informative)” in “Annexes” in the Table of Contents by “D (mandatory)”;

    2. by replacing Clause 1.1 by the following:

      “1.1. This Standard applies to fixed and mobile facilities intended for the liquefaction, storage, vaporization, transfer or handling of liquefied natural gas regardless of their locations and for the distribution of the liquefied natural gas.”;

    3. by replacing Clause 1.2.2 by the following:

      “1.2.2. This Standard includes non-mandatory guidelines for small LNG facilities (see the definition of “small facility” in Chapter 3 and Annex B) and mandatory guidelines for LNG vehicle fuelling stations employed for fleet or public LNG vehicle fuel dispensing operations (see the definition of “fuelling station” in Clause D.2 and Annex D). If Annex D cannot be complied with, the facility shall be approved by the Régie du bâtiment du Québec according to the conditions it sets under sections 127 and 128 of the Building Act (chapter B-1.1).”;

    4. by revoking Clause 1.2.3;

    5. by revoking Clause 1.3;

    6. by replacing the first paragraph of Clause 2 by the following:

      “The documents incorporated by reference into this Standard are those indicated below and include any subsequent amendments and editions that may be published.

      Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Standard is then the document as adopted by that chapter or regulation.”;

    7. in Clause 3

      1. by replacing the first sentence of the Clause by the following:

        “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by inserting the following definition before “Authority having jurisdiction”:

        Approved: approved or authorized by the Régie du bâtiment du Québec under sections 2.06 and 2.07 of the Construction Code or section 127 or 128 of the Building Act.”;

      3. by replacing the definition “Authority having jurisdiction” by the following:

        «Authority having jurisdiction: Régie du bâtiment du Québec.»;

    8. by replacing “informative” in the title of Annex D by “mandatory”;

    9. by replacing the notes in Annex D by the following:

      Note: This Annex constitutes a mandatory part of this Standard.”.

      O.C. 875-2003, s. 1; O.C. 120-2006, ss. 1 and 8; O.C. 991-2018, s. 1.

  • CAN/CSA Standard Z662 is amended

    1. by replacing Clause 1.1 by the following:

      “1.1. This Standard covers intraprovincial gas pipeline systems to the extremity of the operator’s installations, that is, the point where the operator’s piping ends.”;

    2. by replacing the first paragraph of Clause 2.1 by the following:

      “The documents incorporated by reference into this Standard are indicated below and include any subsequent amendments and editions that may be published.

      Despite the first paragraph, where a document indicated below is adopted by reference by a chapter of the Construction Code (chapter B-1.1, r. 2) or the Safety Code (chapter B-1.1, r. 3), or by another regulation of the Board, the document incorporated by reference into this Standard is then the document as adopted by that chapter or regulation.”;

    3. in Clause 2.2

      1. by replacing the first sentence of the Clause by the following:

        “Unless the context indicates otherwise, the following definitions shall apply in this Code:”;

      2. by striking out the definition “Construction”;

      3. by replacing the definition of “Contractor” by the following:

        Contractor: a contractor or an owner-builder within the meaning of section 7 of the Building Act (chapter B-1.1), who carries out or has carried out construction work covered by this Standard.”;

      4. by adding the following after the definition “Ductile cast iron”:

        Easily accessible: within reach for the operation, replacement, maintenance or inspection without having to climb, remove an obstacle or use a mobile ladder.”;

    4. by inserting the following after Clause 10.6.4.4:

      “10.6.5. Right of way encroachment where high pressure gas pipeline is installed (operated at more than 30% of their SMYS)

            1. Except for agricultural work carried out at a maximum depth of 30 cm, no soil disturbance may be carried out in a right of way unless prior written authorization has been obtained from the operator.

              For the purposes of this Clause, “soil disturbance” means all work, operations or activities, above ground or underground, causing a movement or a shift of soil or ground cover, including in particular the following activities: excavation, trench, vertical drilling, dethatching, soil levelling, tree planting, soil aeration, mechanical stone collection, rutting and installation of fence posts, bars, rods, stakes or anchors.

            2. No building (including a shed) or other object permanently fixed may be erected in a right of way.

            3. No flammable material, solid or liquid residue, refuse, waste or effluent may be deposited or stored in a right of way.

            4. Except for vehicles travelling on a public road crossing the right of way, only vehicles belonging to an operator or authorized by an operator may travel on that right of way for inspection, maintenance or leak detection purposes.”;

    5. by inserting the following after Clause 12.2:

      “12.2.1. The service line of a building shall come out of the ground before entering the building and it shall be equipped with a service shut-off valve outside the building.

      However, if the location where the service line comes out of the ground presents a danger and the service line cannot be protected, it shall enter the building below ground level and be equipped with an underground service shut-off valve located outside the building and with another service shut-off valve inside, as near as possible to the foundation wall.

      Where buildings are connected by a common area, service lines may serve their respective building through the common area provided they are equipped with a service shut-off valve identified and connected to a common service line equipped with a main service shut-off valve above ground.

      However, an identification indicating the presence of natural gas and the location of the service shut-off valves shall be present outside near the main entrance to each of the buildings served.

          1. The service shut-off valves above ground shall be easily accessible for their operation.

          2. Before supplying gas to an installation, an operator shall affix to the building, above or within a radius of not more than one metre from any service entrance, a distinctive mark visible at all times.”.


      O.C. 875-2003, s. 1; O.C. 991-2018, s. 1.