The British Columbia Building Code | Section 6.5. | Thermal Insulation Systems
Division B: Acceptable Solutions Part 6 – Heating, Ventilating and Air-conditioning
British Columbia Building Code 2018 Division B
Section 6.5. Thermal Insulation Systems
6.5.1. Insulation
6.5.1.1. Insulation and Coverings
(See NoteA-6.3.2.5.)
1) Insulation and coverings on pipes shall comply with Article3.6.5.5.
2) Insulation and coverings on pipes shall be composed of material that will withstand deterioration from
softening, melting, mildew and mould at the operating temperature of the system.
3) Exposed piping or equipment subject to human contact shall be insulated so that the temperature of the
exposed surface does not exceed 70°C. (See NoteA-6.5.1.1.(3).)