The British Columbia Building Code | Section 3.6. | Service Facilities Pt 1
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
Section 3.6. Service Facilities
3.6.1. General
3.6.1.1. Scope
1) The provisions of this Section apply to horizontal service spaces, vertical service spaces, attic or roof spaces, ducts, 
crawl spaces, shaft spaces, service rooms, and mechanical penthouses, and facilities contained therein.
3.6.1.2. Electrical Wiring and Equipment
1) The installation of electrical wiring and electrical equipment shall conform to the requirements of the 
Electrical Safety Regulation.
3.6.1.3. Lightning Protection Systems
1) A lightning protection system, when provided, shall conform to the requirements of CAN/CSA-B72-M, 
“Installation Code for Lightning Protection Systems.”
3.6.1.4. Storage Use Prohibition
1) Service spaces shall not be designed to facilitate subsequent use as storage space.
3.6.1.5. Appliances Installed outside a Building
1) A fuel-fired appliance installed on the roof of a building or in another location outside the building shall be 
installed not less than
a) 1.2m from a property line, measured horizontally, and 
b) 3m from an adjacent wall of the same building if that wall contains any opening within 3 storeys above and 
5m horizontally from the appliance, unless every opening within these limits is protected by 
i) a closure having a fire-protection rating not less than 45min determined in accordance with 
Article3.1.8.4., or
ii) a wired glass assembly permitted for use in a vertical fire separation and described in D-2.3.15. in 
Appendix D.
3.6.2. Service Rooms
3.6.2.1. Fire Separations around Service Rooms
1) Except as permitted by Sentences(2),(8),(9) and(10), fuel-fired appliances shall be installed in service rooms 
separated from the remainder of the building by fire separations having a fire-resistance rating not less than 1h.
2) Except as required by Sentence(3), a fuel-fired appliance that serves only one room or suite is not required to 
be installed in a service room separated from the remainder of the building.
3) A solid-fuel-burning appliance shall not be located in a repair garage, a storage garage, or any other location 
where it could be exposed to flammable vapours or gases, unless
a) it is enclosed in a service room that is separated from the remainder of the building by a fire separation having a 
fire-resistance rating not less than 1h,
b) it is supplied with combustion air directly from outside the building, and
c) the heat that it generates is supplied indirectly to the space served by means of ducts or piping.
4) A service room containing an incinerator shall be separated from the remainder of the building by a fire 
separation having a fire-resistance rating not less than 2 h.
5) Equipment that uses a liquid having a flash point below 93.3°C shall be installed in a service room separated 
from the remainder of the building by a fire separation having a fire-resistance rating not less than 1h.
Effective December 10, 2018 to December 11, 2019
Part 3 – Fire Protection, Occupant Safety and Accessibility Division B: Acceptable Solutions
Division B 
6) Electrical equipment that is required to be located in a service room according to the Electrical Safety 
Regulation shall be installed in a service room separated from the remainder of the building by a fire separation having 
a fire-resistance rating not less than 1h.
7) Except as permitted by Sentence(8), in a storey that is not sprinklered throughout, a service room that contains 
service equipment other than that addressed by Sentences(1) to(6) shall be separated from the remainder of the 
building by a fire separation having a fire-resistance rating not less than 1h.
8) Where a service room contains a limited quantity of service equipment, and the service equipment neither 
constitutes a fire hazard nor is essential to the operation of fire safety systems in the building, the requirements for a 
fire separation shall not apply.
9) A fire separation is not required between a fireplace and the space it serves.
10) A fire separation is not required between a roof-top appliance and the building it serves.
3.6.2.2. Service Rooms under Exits
1) A service room containing service equipment subject to possible explosion, such as boilers operating in excess 
of 100kPa (gauge) and some types of refrigerating machinery and transformers, shall not be located directly under a 
required exit.
3.6.2.3. Service Equipment
1) A service room containing space heating, space cooling and service water heating appliances is permitted to 
contain other service equipment such as electrical service equipment.
3.6.2.4. Incinerator Rooms
1) A service room containing an incinerator shall not contain other fuel-fired appliances.
3.6.2.5. Combustible Refuse Storage
1) Except as required by Sentence3.6.3.3.(9), a room for the storage of combustible refuse shall be
a) separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 1h, 
and
b) sprinklered.
(SeeNoteA-3.6.2.5.(1).)
3.6.2.6. Door Swing for Service Rooms
1) A 
swing-type door from a service room containing a boiler or incinerator shall swing outward from the room, 
except that the door shall swing inward if the door opens onto a corridor or any room used for an assembly occupancy. 
(Seealso Sentence3.4.4.4.(7).)
3.6.2.7. Electrical Equipment Vaults
1) An electrical equipment vault required by the Electrical Safety Regulation shall conform to Sentences(2) 
to(8).
2) An electrical equipment vault referred to in Sentence(1) shall be separated from the remainder of the building 
by a fire separation of solid masonry or concrete construction having a fire-resistance rating not less than
a) 3h if the vault is not protected by an automatic fire extinguishing system, or
b) 2h if the vault is protected by an automatic fire extinguishing system.
3) If a building is sprinklered throughout, an electrical equipment vault referred to in Sentence(1) need not be 
sprinklered provided
a) the vault is designed for no purpose other than to contain the electrical equipment, and
b) the vault contains a smoke detector which will actuate the building fire alarm system in the event of a fire in 
the vault.
Effective December 10, 2018 to December 11, 2019
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
4) Only pipes or ducts necessary for fire protection or the proper operation of the electrical installation shall 
penetrate the fire separation referred to in Sentence(2).
5) Explosion-relief devices and vents or other protective measures conforming to Sentence3.3.1.20.(3) shall be 
provided for an electrical equipment vault referred to in Sentence(1) that contains dielectric-liquid-filled electrical 
equipment. (SeeNoteA-3.6.2.7.(5).)
6) An electrical equipment vault referred to in Sentence(1) shall be provided with a ventilation system designed 
in conformance with Part6 to prevent the ambient temperature in the vault from exceeding 40°C.
7) The ventilation system required by Sentence(6) shall be separate from the system for the remainder of the 
building and shall be designed so that it is automatically shut off in the event of a fire in the vault.
8) The floor of an electrical equipment vault referred to in Sentence(1) shall be liquid tight and surrounded by 
liquid tight walls and sills of sufficient height to confine within the vault all of the liquid from the largest item of 
electrical equipment, but to a height of not less than 100mm.
9) Electrical equipment vaults shall be secured against unauthorized entry.
3.6.2.8. Emergency Power Installations
1) Where a generator intended to supply emergency power for lighting, fire safety and life safety systems is 
located in a building, except where such building is used solely for the purpose of housing the generator and its 
ancillary equipment, it shall be located in a room that
a) is separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 
2h, and
b) contains only the generating set and equipment related to the emergency power supply system.
3.6.3. Vertical Service Spaces and Service Facilities
3.6.3.1. Fire Separations for Vertical Service Spaces
1) Except as provided in Articles3.6.3.3. and3.6.3.5. and Section3.5., a vertical service space shall be separated 
from all other portions of each adjacent storey by a fire separation having a fire-resistance rating conforming to 
Table3.6.3.1. for the fire-resistance rating required by Subsection3.2.2. for
a) the floor assembly above the storey, or
b) the floor assembly below the storey, if there is no floor assembly above.
(SeeNoteA-3.6.3.1.(1).)
2) A vertical service space that does not extend through the roof of a building shall be enclosed at the top with 
construction having a fire-resistance rating not less than that required for the vertical service space walls.
3) A vertical service space that does not extend to the bottom of a building shall be enclosed at the lowest level 
with construction having a fire-resistance rating not less than that required for the vertical service space walls.
4) A vent from a vertical service space not extending to the roof shall be enclosed within the building with 
construction having a fire-resistance rating not less than that required for the vertical service space walls.
Table 3.6.3.1.
Fire Separations for Vertical Service Spaces
Forming Part of Sentence 3.6.3.1.(1)
Fire-Resistance Rating of Fire Separation Required for Floor Assembly Minimum Fire-Resistance Rating of Vertical Service Space
less than 45 min –
45 min 45 min
1 h 45 min
1.5 h 1 h
2 h or more 1 h
Effective December 10, 2018 to December 11, 2019
Part 3 – Fire Protection, Occupant Safety and Accessibility Division B: Acceptable Solutions
Division B 
5) Only openings that are necessary for the use of the vertical service space shall be permitted through a vertical 
service space enclosure.
3.6.3.2. Foamed Plastic Protection
1) Foamed plastic insulation in a vertical service space shall be protected in conformance with Article3.1.5.14.
3.6.3.3. Linen and Refuse Chutes
1) A linen chute or refuse chute shall
a) be impervious to moisture,
b) have a smooth internal surface,
c) be corrosion-resistant,
d) be constructed of noncombustible material, and
e) be located in a shaft in which there are no services other than noncombustible drain, waste and vent piping or 
noncombustible water piping.
2) A shaft containing a linen chute or refuse chute shall have a fire-resistance rating conforming to 
Sentence3.6.3.1.(1), but not less than
a) 1h if the chute outlet for the discharge room is protected by an automatic, self-latching closure held open by 
a fusible link, or
b) 2h if no closure is provided at the chute outlet into the discharge room.
3) An interior linen chute or refuse chute shall extend not less than 1m above the roof and shall be vented above 
the roof with a vent which
a) has an unobstructed area not less than the cross-sectional area of the chute, and
b) is equipped with a cover that will open automatically, or that can be opened manually, in the event of a fire in 
the chute.
4) Intake openings for a linen chute or a refuse chute shall
a) have an area not more than 60% of the cross-sectional area of the chute, and
b) be fitted with closures designed to close automatically and latch after use.
5) Intake openings for a linen chute or a refuse chute shall be located in rooms or compartments that
a) have no dimension less than 750mm,
b) are separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 
45min,
c) are designed for no other purpose, and
d) do not open directly into an exit.
6) Sprinklers shall be installed at the top of each linen chute or refuse chute, at alternate floor levels and in the 
room or bin into which the chute discharges.
7) The room into which a linen chute discharges shall be separated from the remainder of the building by a fire 
separation with a fire-resistance rating not less than 1h.
8) A refuse chute shall be equipped at the top with spray equipment for washing-down purposes.
9) A refuse chute shall discharge only into a room or bin separated from the remainder of the building by a fire 
separation with a fire-resistance rating
 not less than 2h.
10
) The room or bin into which a refuse chute discharges shall be of sufficient size to contain the refuse between 
normal intervals of emptying, be impervious to moisture and be equipped with a water connection and floor drain for 
washing-down purposes.
11) A room into which a refuse chute discharges shall contain no service equipment that is not related to refuse 
handling and disposal.
Effective December 10, 2018 to December 11, 2019
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
3.6.3.4. Exhaust Duct Negative Pressure
1) If a vertical service space contains an exhaust duct that serves more than one fire compartment,
a) the duct shall have a fan located at or near the exhaust outlet to ensure that the duct is under negative 
pressure, and
b) the individual fire compartments shall not have individual fans that exhaust directly into the duct in the 
vertical service space.
3.6.3.5. Grease Duct Enclosures
(SeeNoteA-3.6.3.5.)
1) Except as provided in Sentence(2), fire separations enclosing grease ducts for commercial cooking operations 
shall conform to NFPA96, “Ventilation Control and Fire Protection of Commercial Cooking Operations.”
2) The fire-resistance rating of field-applied and factory-built grease duct enclosure assemblies shall be 
determined in conformance with CAN/ULC-S144, “Fire Resistance Test – Grease Duct Assemblies.”
3.6.4. Horizontal Service Spaces and Service Facilities
3.6.4.1. Scope
1) This Subsection applies to horizontal service spaces and service facilities, including ceiling spaces, duct spaces, 
crawl spaces and attic or roof spaces.
3.6.4.2. Fire Separations for Horizontal Service Spaces
1) Except as provided in Article3.6.3.5., a horizontal service space that penetrates a required vertical fire 
separation shall be separated from the remainder of the building it serves in conformance with Sentence(2).
2) If a horizontal service space or other concealed space is located above a required vertical fire separation other 
than a vertical shaft, this space need not be divided at the fire separation as required by Article3.1.8.3. provided the 
construction between this space and the space below is a fire separation with a fire-resistance rating equivalent to that 
required for the vertical fire separation, except that the fire-resistance rating is permitted to be not less than 30min if 
the vertical fire separation is not required to have a fire-resistance rating more than 45min. (SeeNoteA-3.6.4.2.(2).)
3.6.4.3. Plenum Requirements
1) A concealed space used as a plenum within a floor assembly or within a roof assembly need not conform to 
Sentence3.1.5.18.(1) and Article3.6.5.1., provided
a) all materials within the concealed space have a flame-spread rating not more than25 and a smoke developed 
classification not more than50, except for
i) tubing for pneumatic controls,
ii) optical fibre cables and electrical wires and cables with combustible insulation, jackets or sheathes that are 
used for the transmission of voice, sound or data and conform to Sentences3.1.4.3.(2) and3.1.5.21.(2),
iii) totally enclosed non-metallic raceways with an FT6 rating, when tested in accordance with 
Clause3.1.5.23.(1)(a), in buildings required to be of noncombustible construction, and
iv) totally enclosed non-metallic raceways with an FT4 rating, when tested in accordance with 
Clause3.1.5.23.(1)(a), in buildings permitted to be of combustible construction, and
b) the supports for the ceiling membrane are of noncombustible material having a melting point not below 
760°C.
2) If a concealed space referred to in Sentence(1) is used as a return-air plenum and incorporates a ceiling 
membrane that forms part of the required fire-resistance rating of the assembly, every opening through the membrane 
shall be protected by a fire stop flap that
a) stops the flow of air into the concealed space in the event of a fire, 
b) is supported in a manner that will maintain the integrity of the ceiling membrane for the duration of time 
required to provide the required fire-resistance rating,
Effective December 10, 2018 to December 11, 2019
Part 3 – Fire Protection, Occupant Safety and Accessibility Division B: Acceptable Solutions
Division B 
c) conforms to CAN/ULC-S112.2, “Fire Test of Ceiling Firestop Flap Assemblies,” and
d) activates at a temperature approximately 30°C above the normal maximum temperature that occurs in the 
return-air plenum, whether the air duct system is operating or shut down.
3.6.4.4. Attic or Roof Space Access
1) An attic or roof space more than 600mm high shall be provided with access from the floor immediately below 
by a hatchway not less than 550mm by 900mm or by a stairway.
3.6.4.5. Horizontal Service Space Access
1) A horizontal service space, consisting of ceiling and duct spaces, which is more than 1 200mm high and 
600mm wide shall have inspection doors not less than 300mm in both horizontal and vertical dimensions placed so 
that the entire interior of the duct or space can be viewed.
3.6.4.6. Crawl Space Access
1) A crawl space shall have at least one access opening not less than 550mm by 900mm.
3.6.5. Air Duct and Plenum Systems
3.6.5.1. Duct Materials
1) Except as permitted by Sentences(2) to(5) and Article3.6.4.3., all ducts, duct connectors, associated fittings 
and plenums used in air duct systems shall be constructed of steel, aluminum alloy, copper, clay, asbestos-cement or 
other noncombustible material.
2) Except as permitted by Sentence(3), ducts, associated fittings and plenums are permitted to contain 
combustible material provided they
a) conform to the appropriate requirements for Class 1 duct materials in CAN/ULC-S110, “Test for 
Air Ducts,”
b) conform to Article3.1.5.18. in a building required to be of noncombustible construction,
c) conform to Subsection3.1.9.,
d) are used only in horizontal runs in a building required to be of noncombustible construction, 
e) are not used in vertical runs serving more than 2 storeys in a building permitted to be of combustible 
construction, and
f) are not used in air duct systems in which the air temperature could be more than 120°C.
3) Combustible ducts which are part of a duct system conveying only ventilation air and are contained entirely 
within a dwelling unit need not comply with the requirements of Sentences(1) and(2). 
4) Duct sealants shall have a flame-spread rating not more than25 and a smoke developed classification not more 
than50.
5) Duct connectors that contain combustible materials and that are used between ducts and air outlet units shall
a) conform to the appropriate requirements for Class1 air duct materials in CAN/ULC-S110, “Test for 
Air Ducts,”
b) be not more than4m long,
c) be used only in horizontal runs, and
d) not penetrate a required fire separation. 
3.6.5.2. Vibration Isolation Connectors
1) Except as permitted by Sentence(2), vibration isolation connectors in air duct systems shall be 
noncombustible.
2) Combustible fabric vibration isolation connectors are permitted provided they
a) are not more than250mm long,
Effective December 10, 2018 to December 11, 2019
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
b) comply with the flame-resistance requirements of CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics 
and Films,” and
c) are not used in a location where they are exposed to heated air or radiation from heat sources that could cause 
the exposed surface temperature to be more than 120°C.
3.6.5.3. Tape
1) Tape used to seal joints in air ducts, plenums and other parts of air duct systems shall meet the 
flame-resistance requirements for fabric in CAN/ULC-S109, “Flame Tests of Flame-Resistant Fabrics and Films.”
3.6.5.4. Coverings, Linings, Adhesives and Insulation
1) Coverings, linings and associated adhesives and insulation for air ducts, plenums and other parts of air duct 
systems that would have an exposed surface temperature more than 120°C when exposed to heated air or radiation 
from heat sources shall be of noncombustible material.
2) Except as permitted by Sentence(3), combustible coverings and linings, including associated adhesives and 
insulation, shall have
a) a flame-spread rating not more than25 on any exposed surface or any surface that would be exposed by 
cutting through the material in any direction, and
b) a smoke developed classification not more than50.
3) The outer covering of ducts, plenums and other parts of air duct systems used within an assembly of 
combustible construction is permitted to have
a) an exposed surface flame-spread rating not more than75, and
b) a smoke developed classification not more than50.
4) Combustible coverings and linings referred to in Sentences(2) and(3) shall not flame, glow, smoulder or 
smoke when tested in accordance with the method of test in ASTM C 411, “Hot-Surface Performance of 
High-Temperature Thermal Insulation,” at the maximum temperature to which the coverings and linings are to be 
exposed in service.
5) Except as permitted by Sentence(6), foamed plastic insulation shall not be used as part of an air duct system 
or for insulating an air duct.
6) Foamed plastic insulation is permitted to be installed in a ceiling space that is used as a return air plenum 
provided the foamed plastic insulation is protected from exposure to the plenum in accordance with Article3.1.5.14.
7) Combustible coverings and linings of ducts, including associated adhesives and insulation, shall be interrupted 
where the duct penetrates a fire separation and at the immediate area of operation of heat sources in a duct system, 
including electric resistance heaters or fuel-burning heaters or furnaces.
3.6.5.5. Insulation and Coverings
1) Insulation and coverings on pipes in which the temperature of the fluid exceeds 120°C shall
a) be made of noncombustible material, or
b) not flame, glow, smoulder or smoke when tested in accordance with ASTMC411, “Hot-Surface 
Performance of High-Temperature Thermal Insulation,” at the maximum temperature to which the 
insulation or covering is to be exposed in service.
2) Except as permitted by Sentence(5), where combustible
 insulation is used on piping in a horizonta
l service 
space or a vertical service space, the insulation and coverings on that piping shall have a flame-spread rating, on any 
exposed surface and on any surface that would be exposed by cutting through the material in any direction,
a) not more than25 in a building required to be of noncombustible construction, or
b) not more than75 in a building permitted to be of combustible construction.
3) Except as permitted by Sentence(5), insulation and coverings on piping located in rooms and spaces other 
than the service spaces described in Sentence(2) shall have a flame-spread rating not more thanthat required for the 
interior finish of the ceiling of the room or space.
Effective December 10, 2018 to December 11, 2019
Part 3 – Fire Protection, Occupant Safety and Accessibility Division B: Acceptable Solutions
Division B 
4) Except as permitted by Sentence(5), combustible insulation and covering used on piping in a building within 
the scope of Subsection3.2.6. shall have a smoke developed classification not more than100.
5) No flame-spread rating or smoke developed classification limits are required for combustible insulation and 
coverings used on piping located within a
a) concealed space in a wall,
b) floor slab, or
c) noncombustible enclosure.
3.6.5.6. Clearance of Ducts and Plenums
1) The clearance of furnace plenums from combustible material shall conform to the requirements of the 
appropriate standards referenced in Sentence6.2.1.5.(1).
2) If the plenum clearance required in accordance with Sentence(1) is not more than75mm, the clearance 
between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 450mm from the plenum, and
b) 12mm at a horizontal distance of 450mm or more from the plenum, except that this clearance is permitted 
to be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the 
supply duct from direct radiation from the furnace heat exchanger. 
(SeeNoteA-3.6.5.6.(2).)
3) If the plenum clearance required in accordance with Sentence(1) is more than 75mm but not more 
than150mm, the clearance between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 1 800mm from the plenum, and
b) 12mm at a horizontal distance of 1 800mm or more from the plenum, except that this distance is permitted 
to be reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the 
supply duct from direct radiation from the furnace heat exchanger.
(SeeNoteA-3.6.5.6.(3).)
4) If the plenum clearance required in accordance with Sentence(1) is more than 150mm, the clearance 
between a supply duct and combustible material shall be not less than
a) the required plenum clearance within a horizontal distance of 1 000mm from the plenum,
b) 150mm within a horizontal distance between 1 000mm and 1 800mm from the plenum, and
c) 25mm at a horizontal distance of 1 800mm or more from the 
plenum, exce
pt that this distance is permitted 
to be reduced to 8mm beyond a bend or offset in the duct sufficiently large to shield the remainder of the 
supply duct from direct radiation from the furnace heat exchanger.
(SeeNoteA-3.6.5.6.(4).)
5) If a register is installed in a floor directly over a pipeless furnace, a double-walled register box with not less 
than 100mm between walls, or a register box with the warm-air passage completely surrounded by the cold-air 
passage, shall be permitted instead of the clearances listed in Sentences(2),(3) and(4).
3.6.5.7. Supply, Return, Intake and Exhaust-Air Openings
1) Combustible grilles, diffusers and other devices for supply, return, and exhaust-air openings in rooms shall 
conform to the flame-spread rating and smoke developed classification requirements for the interior finish of the 
surface on which they are installed.
3.6.5.8. Return-Air System
1) Except as required by Sentences(2) and(3), return ducts shall be constructed of material having a flame-spread 
rating not more than150.
2) If any part of a return duct will be exposed to radiation from the furnace heat exchanger or other radiating part 
within the furnace, that part of a return duct directly above or within 600mm of the outside furnace casing shall be 
noncombustible.
3) Return ducts serving solid-fuel-burning furnaces shall be constructed of noncombustible material.
Effective December 10, 2018 to December 11, 2019
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
4) Combustible return ducts shall be lined with noncombustible material
a) below floor registers,
b) at the bottom of vertical ducts, and
c) under furnaces having a bottom return.
Effective December 10, 2018 to December 11, 2019
Division B: Acceptable Solutions Part 3 – Fire Protection, Occupant Safety and Accessibility
British Columbia Building Code 2018 Division B
4) Combustible return ducts shall be lined with noncombustible material
a) below floor registers,
b) at the bottom of vertical ducts, and
c) under furnaces having a bottom return.
Effective December 10, 2018 to December 11, 2019