A-5 Environmental Separation. The requirements provided in Part5 pertain to the separation of environmentally dissimilar
spaces. Most obvious is the need to separate indoor conditioned spaces from unconditioned spaces, the outdoors or the ground.
Thereare also cases where separation is needed between interior spaces which are intended to provide different environments.
(Seealso NotesA-5.1.1.1.(1) andA-5.1.2.1.(1).)
A-5.1.1.1.(1) Scope. Part5 provides explicit requirements related to the transfer of heat, air, moisture and sound in various
forms. Control of the ingress of radon and other soil gases is addressed by the requirements related to air leakage.
A-5.1.2.1.(1) Application. Subsection1.3.3.of DivisionA specifies that Part5 applies to all buildings except those within the
scope of Part9 or the scope of the National Farm Building Code of Canada. Because of their intended use, many buildings need only
provide a limited degree of separation from the outdoor environment, the ground, or between interior spaces. The provisions in Part 5
are written to allow exemptions for these buildings.
Part5 applies to building elements that separate dissimilar environments and to site conditions that may affect environmental loading
on the building envelope.
The provisions address
the design and construction, or selection, of building components, such as windows and doors,
the design and construction of building assemblies, such as walls, floors and roofs,
the design and construction of the interfaces between the above-mentioned elements, and
the design or selection, and installation, of site materials, components and assemblies, such as backfill and drainage, and grading.
Part5 applies not only to building elements that separate indoor space from outdoor space, but also to those elements that separate
indoor space from the ground and that separate adjacent indoor spaces having significantly different environments.
Indoor spaces that require separation include interior conditioned spaces adjacent to indoor unconditioned spaces, and adjacent
interior conditioned spaces that are intended to provide different environments. An extreme example of the last would be a wall that
separates an indoor ice rink from a swimming pool.
Some building elements are exposed to exterior environmental loads but do not separate dissimilar environments. Solid guards on
exterior walkways are one example. Such constructions are subject to the application of Part 5.
A-5.1.4.1. Application of Structural Design to Other Building Elements. Part 4, as currently written, applies
primarily to buildings as a whole and to structural members. Requirements defining structural loads and design to accommodate or
resist those loads, however, apply not only to buildings as a whole and components that are traditionally recognized as structural
members, but also apply to other elements of the building that are subject to structural loading. This is addressed to some extent in
Part4 by the requirements that pertain, for example, to wind loads on cladding. A range of structural loads and effects, as defined in
Subsection4.1.2., may be imposed on non-loadbearing elements such as backing walls, roofing, interior partitions and their
connections. These must generally be addressed using the same load determination and structural design procedures as used for
structural members.
Responsibility for the structural design of buildings as a whole and their structural members is commonly assigned to the engineer of
record. The application of Part4 reflects this, and as such, “non-structural” elements are not explicitly identified in the Part 4
provisions. Rather the application of Part4 to these elements is specified in cross-references from other Parts of the Code, e.g.Part 5,
which recognizes the fact that the structural design of these elements is often carried out by engineers other than the enginee
r of record.
Part4 does not generally apply to the structural design of building services, such as heating, ventilating, air-conditioning, plumbing,
electrical, electronic or fire safety systems, though these may be subject to structural loads. It does, however, apply to the design of the
connections of building services to address earthquake loads (seeArticle4.1.8.18.).
A-5.1.4.1.(2) Materials, Components and Assemblies with Multiple Functions. Where materials, components or
assemblies are used to fulfill multiple functions, the designer may have to take into account their function with regard to structural
loads, heat transfer, air leakage, vapour diffusion, and protection from precipitation, surface and ground water, and sound
transmission. Materials should be selected taking into account the environmental loads to which they will be subjected, their physical
and chemical characteristics, and their installation. Design and construction details should satisfy all intended functions and ensure
continuity within and between assemblies, without adversely impacting adjacent materials, components or assemblies. The designer
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
should also anticipate unintended consequences when materials that may fulfill multiple functions are used. For example, building
membranes consisting of modified bitumen compounds, which are commonly used to control both water ingress and air leakage,
alsotypically have low vapour transmission characteristics. Similarly, extruded polystyrene boards, which are used as thermal
insulation, may also act as a component of an air barrier assembly, thus requiring wind loads to be considered.
An increasing number of manufactured systems are being used to serve more than one (and sometimes all) of the functions of an
environmental separator: examples include pre-engineered building systems, exterior insulation finish systems, insulated metal panel
systems, windows, other fenestration assemblies, and insulated precast concrete wall panels. These systems consist of combinations of
pre-manufactured and/or site-built components, which are supposed to be assembled in a prescribed manner.
Ensuring compliance with one Section of Part 5 may impact compliance with other Sections of Part 5: for example, air barriers that are
integral to some systems may also act as vapour barriers and impact condensation control. By extension, ensuring compliance with the
requirements of Part5 may impact compliance with other Parts of the code
: for example, increasing the thickness of the insulation to
improve an assembly’s thermal performance may impact its compliance with Part3 with regard to fire resistance.
Compliance with a standard listed in Section 5.9. does not ensure that a system is appropriate for the intended application.
Thedesigner should consider all relevant criteria, beyond the standard tests, when selecting an appropriate product for a project.
A-5.1.4.1.(5) Past Performance as Basis for Compliance with Respect to Structural Loads. As discussed in
NoteA-5.1.4.1., a range of structural loads and effects can be imposed on materials, components and assemblies in environmental
separators and assemblies exposed to the exterior. In many instances, compliance with Sentence 5.1.4.1.(1) for structural loads must be
determined based on the loads and calculation methods described in Part 4 as specified in Sentence 5.1.4.1.(3) and the referenced
Subsection 5.2.2., e.g. for cladding. In practice, compliance for some materials, components or assemblies of environmental separators
and assemblies exposed to the exterior is determined by relying on provisions governing the use of alternative solutions (such as
Clause 1.2.1.1.(1)(b)of Division A).
For some very common building elements and installations, however, there is a very large body of evidence of proven performance over
a long period of time. In these cases, imposing the degree of analysis, or documentation of performance, required by Part 4 or
Section 2.3.of Division C would be unnecessary and onerous. Clause 5.1.4.1.(5)(b) is intended to address these particular cases.
Because the constructions are so widely accepted throughout the industry and the body of evidence is so substantial (though not
necessarily documented in an organized fashion), there should be no question that detailed analysis or documentation is unnecessary.
Whether compliance of a particular material, component or assembly may be determined based on past performance depends not only
on the type of material, component or assembly, but also on its intended function, the particular loads to which it will be subject and
the magnitude of those loads. Because the possible combinations and permutations are infinite, only guidelines can be provided as to
when past performance is a reasonable basis for determining compliance.
In determining compliance based on past performance, the period of past performance considered should be a substantial number of
years. For example, 30years is often used to do life-cycle cost analysis of the viability of investments in building improvements.
Thisperiod is more than long enough for most deficiencies to show up. There should be no question as to the structural adequacy of a
material, component or assembly that has been successfully used in a given application for such a period.
The determination of compliance may be based on past performance only where the function of the material, component or assembly
is identical to that of the materials, components or assemblies used as a reference, and where the expected loads do not exceed those
imposed on the reference materials, components or assemblies. For example, the acceptance of gypsum board, and its fastening,
to serve as part of the backing wall supporting cladding cannot be based on the performance of gypsum board that has served only as
an interior finish.
The determination of compliance may be based on past performance only where the properties of the material, component or
assembly are identical or superior to those of the materials, components or assemblies used as a reference. For example, where a
component of a certain gauge of a particular metal has provided acceptable performance, the same component made of the same metal
or a stronger one would be acceptable.
Compliance with respect to various loads may be determined individually. A particular material may have to be designed to Part 4 to
establish acceptable resistance to wind or earthquake loads, for example, but past performance may be adequate to determine that the
material and normal fastening will support the material’s dead load and will resist loads imposed by thermal and moisture-related
expansion and contraction.
Past performance is a reasonable basis for determining compliance for lighter materials, components or assemblies not subject to wind
load; for example, semi-rigid thermal insulation installed in wall assemblies where other materials, components or assemblies are
installed to resist air pressure loads.
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
Past performance is an appropriate basis for determining compliance for some smaller elements that will be subject to wind loads but
are continually supported or fastened behind elements that are designed for wind loads, for example, standard flashing over wall
penetrations.
It should be noted that this particular approach to demonstrating compliance pertains only to the resistance or accommodation of
structural loads described in Part4. The resistance or accommodation of environmental loads, resistance to deterioration, and material
compatibility must still be addressed in accordance with Part5.
A-5.1.4.1.(6)(b) and (c) Accommodating Movement. It is well understood that the deflection of the backing assembly in
a wall can have significant effects on the performance of the cladding. For example, CSA S304, “Design of Masonry Structures,”
specifies the maximum deflection criteria for backing assemblies to masonry veneer. Clauses 5.1.4.1.(6)(b) and(c) are written in very
general terms in recognition of the fact that not only can the deflection of cladding affect the performance of the backing assembly,
but that the excessive deflection of any element has the potential to adversely affect the performance of any adjacent element.
Similarly, inter-storey drift has the potential to adversely affect the performance of components and assemblies of environmental
separators. CSA O86, “Engineering Design in Wood,” specifies a method for calculating building movement due to changes in
moisture content. The effects of movement should be avoided or accommodated.
A-5.1.4.2. Deterioration. Environmental loads that must be considered include but are not limited to: sound, light and other
types of radiation, temperature, moisture, air pressure, acids and alkalis.
Mechanisms of deterioration include:
structural (impact, air pressure)
hygrothermal (freeze-thaw, differential movement due to thermal expansion and contraction, ice lensing)
electrochemical (oxidation, electrolytic action, galvanic action, solar deterioration)
biochemical (biological attack, intrusion by insects and rodents).
Information on the effects of deformations in building elements can be found in the Commentary entitled Effects of Deformations in
Building Components in the “User’s Guide – NBC 2015, Structural Commentaries (Part 4 of Division B).”
Resistance to deterioration may be determined based on field performance, accelerated testing or compliance with guidelines provided
by evaluation agencies recognized by the authority having jurisdiction. Guidance can be found in CSA S478, “Guideline on Durability
in Buildings.”
Building components should be designed with some understanding of the length of time over which they will effectively perform their
intended function. Actual service life will depend on the materials used and the environment to which they are exposed. Thedesign
should take into consideration these factors, the particular function of the component and the implications of premature failure,
the ease of access for maintenance, repair or replacement, and the cost of repair or replacement.
Many buildings are designed such that access for maintenance, repair or replacement is not possible without damaging – or seriously
risking damaging – other building elements. This can become a considerable deterrent to proper maintenance thus compromising the
performance of the subject materials, components and assemblies, or other elements of the building. In cases where it is known or
expected that maintenance, repair or replacement is likely to be required for certain elements before such time as the building
undergoes a major retrofit, special consideration should be given to providing easy access to those elements. Anchorage points for
maintenance personnel should be considered during the design of multi-storey buildings, including those of wood-frame construct
ion,
as adding them post-construction can be difficult.
Where the use of a building or space, or the services for a building or space, are changed significantly, an assessment of the impact of
the changes on the environmental separators should be conducted to preclude premature failures that could create hazardous
conditions.
A-5.2.1.1.(3) Soil Temperatures. In theory, soil temperatures are needed to determine the conformance of a design to the
requirements related to heat transfer and vapour diffusion. In practice, standard construction in a particular area may have proven to
perform quite adequately and detailed calculations of soil temperature are unnecessary. (Seealso Sentence5.2.1.3.(2).)
A-5.2.1.2.(1) Interior Environmental Loads. The interior environmental conditions required depend on the intended use
of the spaces in the building as defined in the building program. Spaces in different types of buildings and different spaces within a
single building may impose different loads on the separators between interior and exterior spaces and between adjacent interior spaces.
Theseparators must be designed to withstand the expected loads.
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
A-5.2.2.1.(2)(c) Determination of Structural Loads and Effects. As regards materials, components and assemblies and
their interfaces that are installed in buildings to which Part5 applies, the effects of earthquake loads on their ability to resist or
accommodate environmental loads are generally only taken into account in the design of post-disaster buildings. For all other
buildings, damage to building components during seismic events is anticipated and these buildings are not intended to be functional
after the event. However, for post-disaster buildings, seismic effects must be taken into account in the design for environmental
separation, as these buildings are required to have an adequate degree of functionality after the design event to meet their intended
function (see Article 4.1.8.13. for deflections and drift limits for post-disaster buildings).
However, it is important to note that earthquake effects must be taken into account in the seismic design of all building materials,
components and assemblies and their interfaces covered by Article4.1.8.18. to address life safety and the structural protection
of buildings.
A-5.2.2.2. Resistance to Wind and Other Air Pressure Loads. The wind load provisions apply to roofing and other
materials subject to wind-uplift loads.
Note that, although Article5.2.2.2. is specifically concerned with wind loads and directly references only one Article from Part 4,
Sentence5.2.2.1.(1) references all of Part4 and would invoke Article4.1.7.10. for example, which is concerned with air pressure loads
on interior walls and partitions.
A-5.2.2.2.(4) Membrane Roofing Systems. Wind loads for membrane roofing systems must be calculated in accordance
with Part4. The tested uplift resistance and factored load should satisfy the requirements of the Commentary entitled Limit States
Design in the “User’s Guide – NBC 2015, Structural Commentaries (Part 4 of Division B).”
The test method described in CAN/CSA-A123.21, “Dynamic Wind Uplift Resistance of Membrane-Roofing Systems,” applies only
to membrane roofing systems whose components’ resistance to wind uplift is achieved by fasteners or adhesives. It does not apply to
roofing systems that use ballasts, such as gravel or pavers, to secure the membrane against wind uplift.
In the case of membrane roofing systems in which the waterproof membrane is attached to the structural deck using mechanical
fasteners, the wind-induced forces and the roofing system’s response are time- and space-dependent and, thus, dynamic in nature.
Further information on the design and evaluation of such systems can be found in “A Guide for the Wind Design of Mechanically
Attached Flexible Membrane Roofs,” published by NRC.
The wind uplift resistance obtained from the test method in CAN/CSA-A123.21 is limited to configurations with specific fastener or
adhesive patterns. To extrapolate the test data to non-tested configurations, refer to ANSI/SPRI WD-1, “Wind Design Standard
Practice for Roofing Assemblies,” for a rational calculation procedure. However, in using this extrapolation procedure, wind loads
should be calculated in accordance with the BCBC
. NRC’s guide for wind design referenced above provides further guidance and
examples of wind load calculations.
A-5.3. Heat Transfer. In addressing issues related to health and safety, Section5.3. calls up levels of thermal resistance needed
to minimize condensation on or within environmental separators, and to ensure thermal conditions appropriate for the building use.
Energy regulations, where they exist, specify levels of thermal resistance required for energy efficiency or call up energy performance
levels, which relate to levels of thermal resistance. Where Part 5 calls for levels of thermal resistance higher than those required by the
energy regulations, the requirements of Part 5 take precedence.
A-5.3.1.1. Required Resistance to Heat Transfer. The control of heat flow is required wherever there is an intended
temperature difference across the building assembly. The use of the term “intended” is important since, whenever interior space is
separated from exterior space, temperature differences will occur.
The interior of an unheated warehouse, for example, will often be at a different temperature from the exterior due to solar radiation,
radiation from the building to the night sky and the time lag in temperature change due to the thermal mass of the building and its
contents. If this temperature difference is not “intended,” no special consideration need be given to the control of heat flow.
If the warehouse is heated or cooled, thus making the temperature difference “intended,” some consideration would have to be given to
the control of heat flow.
It should be noted, however, that in many cases, such as with adjacent interior spaces, there will be an intended temperature difference
but the difference will not be great. In these cases, the provisions to control heat flow may be little or no more than would be provided
by any standard interior separator. That is, materials typically used in the construction of partitions may provide the separation needed
to meet the requirements of Section 5.3. without adding what are generally considered to be “insulating” materials.
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
A-5.3.1.2. Material and Component Properties and Condensation. Total prevention of condensation is generally
unnecessary and its achievement is rarely a certainty at design conditions. Part 5, therefore, requires that condensation be minimized.
The occurrence of condensation should be sufficiently rare, or the quantities accumulated should be sufficiently small and dry rapidly
enough, to avoid material deterioration and the growth of mould and fungi.
The Harmonized North American Fenestration Standard, AAMA/WDMA/CSA101/I.S.2/A440, “NAFS – North American
Fenestration Standard/Specification for Windows, Doors, and Skylights,” identifies procedures to determine the condensation
resistance and thermal transmittance of windows, doors and skylights though testing for condensation resistance is presented as
optional in the standard. As such, a fenestration product that meets the standard’s requirements on air leakage, water penetration,
uniform load and other performance requirements may not meet the condensation resistance performance level needed for a given
application. Only the physical test procedure presented in CSA A440.2, “Fenestration Energy Performance,” can be used to establish
the temperature index(I) value, which denotes condensation resistance performance evaluation criteria. It is recommended that
designers specify I values for a given application to minimize the potential for condensation. Further guidance on the selection of the
correct Ivalue is provided in CSA A440.3, “User Guide to CSA A440.2-14, Fenestration Energy Performance.”
The scope of AAMA/WDMA/CSA 101/I.S.2/A440, which is referenced in Subsection 5.9.2., includes skylights and tubular
daylighting devices (TDD). Where skylights and TDDs pass through unconditioned space, their wells and shafts may become the
environmental separator and would therefore have to comply with the requirements of Part 5.
A-5.3.1.2.(1) Use of Thermal Insulation or Mechanical Systems for Environmental Control. The level of thermal
resistance required to avoid condensation on the warm side of an assembly or within an assembly (at the vapour barrier), and to permit
the maintenance of indoor conditions appropriate for the occupancy depends on
the occupancy
the exterior design air temperature
the interior design air temperature and relative humidity
the capacity of the heating system, and
the means of delivering heat.
To control condensation on the interior surface of an exterior wall, for example, the interior surface must not fall below the dew point
of the interior air. If, for instance, the interior air is 20°C and 35% RH, the dew point will be 4°C. If the interior air is 20°C and
55%RH, the dew point will be 11°C.
Where the exterior design temperature is mild, such as in south coastal British Columbia, the interior RH during the heating season
may well be around 55%. With an exterior temperature of −7°C, the materials in the environmental separator would have to provide a
mere RSI0.082 to avoid condensation on the interior surface. Depending on the specific properties of the material, this RSI might be
provided by 10-mm plywood. Therefore, materials generally recognized as thermal insulation would not be required only to limit
condensation on the warmer side of the building envelope.
In other areas of the Province, however, exterior design temperatures are much lower. In these cases, maintaining temperatures inboard
of the vapour barrier above the dew point will require insulation or increased heat delivery to the environmental separator. Direct
delivery of heat over the entire surface of the environmental separator is generally impractical. Indirect heat delivery may not be
possible without raising the interior air temperatures above the comfort level. In any case, increased heat delivery would often entail
excessive energy costs.
In addition to controlling condensation, interior surface temperatures must be warm enough to avoid occupant discomfort due to
excessive heat loss by radiation. Depending on the occupancy of the subject spaces, this may require the installation of insulation even
where it is not needed to control condensation.
A-5.3.1.3.(2) Position of Materials Providing Thermal Resistance. For a material providing thermal resistance to be
effective, it must not be short-circuited by convective airflow through or around the material. The material must therefore be either
the component of the air barrier system providing principal resistance to air leakage, or
installed in full and continuous contact with a continuous low air permeance component.
A-5.4.1.1. Resistance to Air Leakage. An air barrier system in above-grade building components and assemblies separating
conditioned space from the exterior will reduce the likelihood of condensation due to air leakage, discomfort from drafts, the
infiltration of dust and other pollutants, and interference in the performance of building services, such as HVAC and plumbing.
These problems can all lead to serious health or safety hazards.
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
Currently, the most obvious and significant problems are due to moisture-related material deterioration, such as rot and corrosion,
which can lead to the failure of component connections. The infiltration of dust and other pollutants can lead to a wide range of health
problems. Where the separator is subject to high moisture levels, the pollutants may include fungus spores. Interference with the
performance of building services can lead to unhealthy conditions and potentially hazardous conditions during the heating season in
many regions of the province
.
There are few buildings intended for human occupancy where the interior space is conditioned but where an air barrier system is not
required. Some industrial buildings, for example, may be exempt. This would depend, however, on the particular levels of interior
conditioning provided, ventilation levels, protection provided for the workers, and the tolerance of the building’s construction to the
accumulation of condensation and potential precipitation ingress.
Some industrial buildings are provided with only limited conditioning, for example radiant heating, and ventilation levels are sufficient
to reduce relative humidity to a level at which condensation will not accumulate to a degree that is problematic. Conversely, some
industrial buildings, due to the processes they contain, operate at very high temperatures and high ventilation levels. In these cases,
the building envelope will be maintained at temperatures that will avoid condensation. In both examples above, either the ventilation
rates or protective gear required in the work environment would protect the occupants from unacceptable levels of pollutants.
Where adjacent interior environments are sufficiently different, controlling airflow between those spaces is necessary to maintain
conditions. Referring again to the industrial building examples above, assemblies separating office space from the work floor would
likely require an air barrier system.
The word “minimize” is used in Clause5.4.1.1.(1)(c) because not all moisture accumulation in an assembly need be of concern.
Incidental condensation is normal but should be sufficiently rare and in sufficiently limited quantities and should dry rapidly enough
to avoid material deterioration and the growth of mould or fungi.
An air barrier system is required in components and assemblies in contact with the ground to control the ingress of radon, and may be
required to control the ingress of other soil gases such as methane.
In addition to an air barrier system, other measures may be required to reduce the radon concentration to a level below the guideline
specified by Health Canada. Further information on protection from radon ingress can be found in:
“Radon: A Guide for Canadian Homeowners” (CMHC/HC),
“Guide for Radon Measurements in Public Buildings (Schools, Hospitals, Care Facilities, Detention Centres)” (HC), and
EPA 625/R-92/016, “Radon Prevention in the Design and Construction of Schools and Other Large Buildings.”
A-5.4.1.2.(1) and (2) Air Leakage through the Air Barrier System.
The current requirements specify only a maximum air leakage rate for the material in the air barrier system that provides the principal
resistance to air leakage.
Research and in-situ testing of installed air barrier systems have shown that the bulk of air leakage occurs through joints (between air
barrier materials) and junctions (between air barrier components).
Ideally, a maximum air leakage rate for the complete air barrier system would be specified. The maximum acceptable rate will
ultimately depend on warm and cold side temperatures and humidity conditions, and on the susceptibility of the environmental
separator to moisture-related deterioration. Recommended maximum leakage rates for the air barrier system in an exterior envelope in
most locations in Canada are shown in Table A-5.4.1.2.(1) and (2). These values are for air barrier systems in opaque, insulated
portions of the building envelope. They are not for whole buildings, as windows, doors and other openings are not included.
TheTable is provided for guidance when testing air barrier systems as portions of an envelope.
Determining the leakage rate of a particular assembly, however, is problematic. There is little information available on the airtightness
of the many air barrier systems used in building construction, and testing requires specialized equipment and expertise. Depending on
the type of test,
Table A-5.4.1.2.(1) and (2)
Recommended Maximum Air Leakage Rates
Forming Part of Note A-5.4.1.2.(1) and (2)
Warm Side Relative Humidity at 21°C Recommended Maximum System Air Leakage Rate, L/(s·m
2
) at 75 Pa
< 27% 0.15
27 to 55% 0.10
> 55% 0.05
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
testing may not represent the performance of the complete installed system,
the location of deficiencies may be difficult to identify, and
rectification of deficiencies may not be feasible.
Despite the difficulties, when using a system whose performance is not known, it is recommended that tests be conducted. Testing
options include:
laboratory tests of small sections of the air barrier system, including the joints and intersections of different assemblies
laboratory tests of large wall sections
in-situ tests of characteristic envelope areas.
A-5.5.1.1. Required Resistance to Vapour Diffusion. Resistance to vapour diffusion is required to reduce the likelihood
of condensation within building assemblies, and the consequent potential for material deterioration and fungal growth. Deterioration
such as rot and corrosion can lead to the failure of building components and connections, and interfere with the performance of
building services. Some fungi can have very serious effects on health.
In Canada, relatively few buildings that are subject to temperature and vapour pressure differences would be constructed or operated in
such a manner that the control of vapour diffusion would not need to be addressed in their design. Assemblies enclosing certain
industrial spaces, as described in NoteA-5.4.1.1. for example, may be exempt.
For residential spaces, and most other spaces that are conditioned for human occupancy, a means of vapour diffusion control is
generally agreed to be necessary, even in the milder climates of the province
. The questions in those cases pertain to the degree of
control needed.
The word “minimize” is used in Sentence5.5.1.1.(1) because not all moisture accumulation in an assembly need be of concern.
Incidental condensation is normal but should be sufficiently rare and in sufficiently limited quantities, and should dry rapidly enough,
to avoid material deterioration and the growth of mould or fungi. Here are some references regarding the effects of fungi on health:
“Fungal Contamination in Public Buildings: Health Effects and Investigation Methods,” Health Canada
“Guidelines on Assessment and Remediation of Fungi in Indoor Environments,” New York City Department of Health and
Mental Hygiene (NYCDH)
A-5.5.1.2.(1) Vapour Barrier Materials and Installation. In the summer, many buildings are subject to conditions where
the interior temperature is lower than the exterior temperature. Vapour transfer during these periods is from the exterior to the
interior. In general, in Canada, the duration of these periods is sufficiently short, the driving forces are sufficiently low, and assemblies
are constructed such that any accumulated moisture will dissipate before deterioration will occur.
Buildings such as freezer plants, however, may operate for much of the year at temperatures that are below the ambient exterior
temperature. In these cases, the “warm” side of the assembly would be the exterior and a detailed analysis on an annual basis
is required.
Steady state heat transfer and vapour diffusion calculations may be used to determine acceptable permeance levels for the vapour
barrier and to identify appropriate positions for the vapour barrier within the building assembly.
A-5.6.1.1. Required Protection from Precipitation. Windows, cast-in-place concrete walls, and metal and glass curtain
wall systems are examples of components and assemblies that, when properly designed and constructed, are expected to prevent the
ingress of precipitation into a building. Assemblies such as roofs and veneer walls consist of materials specifically intended to screen
precipitation.
Components and assemblies separating interior conditioned space from the exterior are generally required to provide protection from
the ingress of precipitation. Components and assemblies separating interior unconditioned space from the exterior may or may not be
required to provide protection from the ingress of precipitation. Buildings such as stadia, parking garages and some seasonally occupied
buildings, for example, may not require complete protection from the ingress of precipitation. The degree of protection will depend to
a large extent on the materials selected for the building elements that will be exposed to precipitation.
The word “minimize” is used in Sentence 5.6.1.1.(1) because not all moisture ingress or accumulation in an assembly need be of
concern. The penetration of wind-driven rain past the cladding may not affect the long-term performance of the assembly, provided
the moisture dries out or is drained away before it initiates any deterioration of building materials. When the design service life of a
material or component is longer than the design service life of the overall assembly, taking into account the expected exposure to
moisture, initiating deterioration of the material should not be of concern. That is to say, provided the material or component
continues to provide the necessary level of performance for its intended service life and does not adversely affect the service life of the
assembly of which it is a part, the deterioration of the material or component is not an issue.
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
A-5.6.1.2.(1) Ice Damming. Water leakage through sloped roofs is often due to the formation of ice dams at the eaves,
which can be limited by controlling the transfer of heat to the roof through a combination of insulation and venting to dissipate heat.
SeeClause5.3.1.2.(1)(d).
A-5.6.1.2.(2) Vegetated Roofing Systems. The integrity of some assemblies installed to provide the required protection
from the ingress of precipitation in vegetated roofing systems can be compromised due to an inadequate resistance to the penetration
of plant roots and rhizomes. Additional information on vegetated roofing systems and the performance of protective materials can be
found in the German Landscape Research, Development and Construction Society’s (FLL) “Guidelines for the Planning,
Construction and Maintenance of Green Roofing” and in the National Roofing Contractors Association’s “Vegetative Roof
Systems Manual.”
A-5.6.2.1. Sealing and Drainage. Providing a surface-sealed, durable, watertight cover on the outside of a building is
difficult. Where there is a likelihood of some penetration by precipitation into a component or assembly, drainage is generally required
to direct the moisture to the exterior.
The degree of protection against precipitation ingress needed in any particular case and the approach taken to provide that protection
will depend on
the exterior loads imposed on the assembly
the materials selected for the backing assembly,
the use of the enclosed space, and
the level of maintenance that will be acceptable to the owners.
Where exterior loads are greater, it may be prudent to select a precipitation protection system whose small failures will not be as likely
to have an immediate impact on the building or its occupants. For example, drained and vented wall and vented roof assemblies are
typical for low-rise residential buildings. More robust drained and vented wall assemblies are recommended for mid- and high-rise
buildings where the cost of maintenance and repair could be high.
Where materials with a greater resistance to moisture are used in the assembly, a less rugged precipitation protection system or a less
rigorous maintenance schedule may be acceptable. This might be the case, for example, where the wall or backing wall is concrete
or masonry.
For spaces that are not intended for ongoing human occupancy, some rainwater leakage may not be of particular concern. This may be
the case for certain warehouse spaces for example, depending on how the spaces are used and conditioned.
Information on the installation of flashing to drain water to the exterior of roof and wall assemblies may be found in a number of
publications including, but not limited to:
“Architectural Sheet Metal Manual,” Sheet Metal and Air-Conditioning Contractors National Association, Inc.
“High-Rise Residential Construction Guide,” Tarion Warranty Corporation (formerly Ontario New Home Warranty Program)
Technical Notes, National Concrete Masonry Association
Roofing Specifications, Canadian Roofing Contractors’ Association
“The NRCA Roofing Manual: Membrane Roof Systems” and “The NRCA Waterproofing Manual,” National Roofing
Contractors Association
Technical Notes on Brick Construction, Brick Industry Association
Environmental separators installed in buildings of wood construction that exceed 4 storeys can be subjected to increased loading due to
the height of the building. As such, certain design considerations may require different approaches from the common ones used by
industry for buildings of 4 storeys or less. These considerations include, but are not limited to, the following:
air barrier assemblies,
fenestration selection,
protection from precipitation,
differential movement due to wood shrinkage,
roofing selection and design, and
risk of deterioration due to longer exposure of materials to the elements during construction.
Information on environmental separators and the loading to which they are subjected when installed in buildings of wood
construction, as well as recommendations on dealing with differential movement, can be found in the following publications,
among others:
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
“Moisture and Wood-Frame Buildings,” Canadian Wood Council
“Guide for Designing Energy-Efficient Building Enclosures for Wood-Frame Multi-Unit Residential Buildings in Marine to Cold
Climate Zones in North America,” FPInnovations and RDH Building Engineering Ltd.
A-5.7. Protection from Interior Sources of Water. Protection similar to that prescribed in Section5.7. may be required
where interior assemblies are in contact with water (such as site-built showers, steam rooms, swimming pool areas) and where adjacent
interior spaces need to be protected from the transfer of water through these assemblies.
A-5.7.1.2.(2) Drainage. Water should be directed away from the building and, ultimately, to a municipal drainage system,
drainage ditch, swale, or other acceptable water management means. This can be accomplished by setting the building grade higher
than the surrounding grades, by sloping the grade away from the building, by installing a surface water drainage system, or by a
combination of these approaches. The chosen approach should follow generally accepted guidelines, such as the Rational Method of
Stormwater Design by David B. Thompson, or other design methods acceptable to the authority having jurisdiction.
A-5.7.3.3.(1)(a) Imperfections. Examples of imperfections include shrinkage cracks, air holes, honeycombing, form-tie cone
holes, and form joint ridges.
A-5.7.3.4.(1) Dampproofing. Dampproofing refers to the application of a material or materials to an environmental
separation assembly to protect it and the interior space against the transfer of moisture due to the mechanisms of water vapour
transmission, capillary action and pressure differences other than hydrostatic pressure.
A dampproofed assembly should be designed such that it can provide short-term resistance to the ingress of water due to occasional
hydrostatic pressure from ground water.
A-5.8. Required Protection from Noise. Section 5.8. applies to the separation of dwelling units from other dwelling units
and from spaces where noise may be generated with regard to sound transmission irrespective of Clause 5.1.2.1.(1)(b), which deals
with the separation of dissimilar environments. It is understood that, at any time, there is the potential for sound levels to be quite
different in adjoining dwelling units.
A-5.8.1.2. Using ASTC in lieu of STC. A designer may choose to use an ASTC rating of equal or higher numerical value
than the required STC to show compliance where STC ratings are required.
An ASTC measurement or calculation will always yield a value equal to or lower than the STC for the same configuration, as the
ASTC includes flanking transmission.
A-5.8.1.4. Methods of Calculating ASTC. The technical concepts, terminology, and calculation procedures relating to the
detailed and simplified ASTC calculation methods are discussed in detail, with numerous worked examples, in the NRC publication
entitled “Guide to Calculating Airborne Sound Transmission in Buildings.” This Guide includes references to readily-available sources
of pertinent data.
For many common constructions, the calculations required by Article 5.8.1.4. can be performed using software tools, such as
soundPATHS, which is available on NRC’s Web site.
The simplified calculation method may not always identify the prominent flanking paths. Furthermore, it corresponds more closely
with the results of the detailed calculation method where the separating assembly and the flanking constructions are both constructed
according to the same method, i.e. either both are lightweight construction (steel or wood framing) or both are heavyweight
construction (masonry or concrete).
A-5.9.1.1.(1) Selection of Materials and Components and Compliance with Referenced Standards. It is
important to note that Sentence 5.9.1.1.(1) is stated in such a way that the selection of materials and components is not limited to
those traditionally recognized as serving particular functions or those for which a standard is identified in Table5.9.1.1. This approach
permits more flexibility than is provided by similar requirements in Part 9. As long as the selected material meets the performance
requirements stated elsewhere in Part5, the material may be used to serve the required function.
However, where the selected material or component, or its installation, falls within the scope of any of the standards listed in
Table 5.9.1.1., the material, component or installation must comply with that standard. For example, if some resistance to heat
transfer is required between two interior spaces and standard partition construction will provide the necessary resistance, the
installation of one of the “thermal insulation” materials identified in the standard list is not required. If, on the other hand, one decides
to install glass fibre insulation, the material must conform to CAN/ULC-S702, “Mineral Fibre Thermal Insulation for Buildings.”
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
A-Table 5.9.1.1. Selection and Installation of Sealants. Analysis of many sealant joint failures indicates that the
majority of failures can be attributed to improper joint preparation and deficient installation of the sealant and various joint
components. Thefollowing ASTM guidelines describe several aspects that should be considered when applying sealants in
unprotected environments to achieve a durable application:
ASTM C 1193, “Use of Joint Sealants,”
ASTM C 1299, “Selection of Liquid-Applied Sealants,” and
ASTM C 1472, “Calculating Movement and Other Effects When Establishing Sealant Joint Width.”
The sealant manufacturer’s literature should always be consulted for recommended procedures and materials.
A-5.9.2.1.(3) Airtightness and Watertightness of Windows, Doors, Skylights, Other Glazed Products and
their Components Required to have a Fire-Protection Rating. The airtightness and watertightness requirements are
waived for these products when used in such an application, in recognition of the fact that the availability of assemblies that meet both
the requirements of the applicable
standards and the requirements for fire resistance may be limited. However, control of air and water
leakage should not be ignored: measures should be taken to attempt to comply with applicable requirements.
A-5.9.2.2. Design and Construction of Windows, Doors and Skylights.
Design Values
CSAA440S1, “Canadian Supplement to AAMA/WDMA/CSA101/I.S.2/A440, NAFS – North American Fenestration
Standard/Specification for Windows, Doors, and Skylights,” requires that the individual performance levels achieved by the
product for structural resistance, water penetration resistance and air leakage resistance be reported on the product’s performance
label.
Storm Doors and Windows
Where storm doors and storm windows are not incorporated in a rated window or door assembly, they should be designed and
constructed to comply with the applicable requirements of Part5 regarding such properties as appropriate air leakage and
structural loads.
Forced Entry Test
Even though the performance label on rated windows, doors and skylights does not explicitly indicate that the product has passed
the forced entry resistance test, products are required to pass this test in order to be rated.
Installation and Field Testing of Windows, Doors and Skylights.
The installation details of windows, doors, skylights and their components must be appropriately designed and implemented for
the building envelope assembly to perform acceptably overall. The proper design of the installation details provides the
information necessary to integrate the structure and air, vapour and moisture barrier functions of windows, doors and skylights
into the overall design of the building envelope assembly. Construction should be carried out in accordance with these details to
achieve an appropriate level of long-term performance. Further guidance on installation detailing can be found in
CAN/CSA-A440.4, “Window, Door, and Skylight Installation.”
It is recommended that the performance of installed windows, doors and skylights be field tested early in the envelope
construction phase so that any discontinuities can be readily identified and corrected before construction of the building envelope
assembly is completed. Additional field testing during subsequent construction phases to monitor installation consistency is also
recommended. Field test procedures should be carried out in accordance with test standards such as ASTM E 783, “Field
Measurement of Air Leakage Through Installed Exterior Windows and Doors,” and ASTM E 1105, “Field Determination of
Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure
Difference.” Further guidance can be found in Annex D of CAN/CSA-A440.4, “Window, Door, and Skylight Installation,”
however, the performance requirements developed in AAMA/WDMA/CSA 101/I.S.2/A440, “NAFS – North American
Fenestration Standard/Specification for Windows, Doors, and Skylights,” should be used rather than the industry performance
data values listed in CAN/CSA-A440.4.
A-5.9
.2.2.(1) Two Compliance Paths. It is intended that any fenestration product that conforms to this Part may choose to
comply with either Clause (a) or Clause (b) of Sentence 5.9.2.2.(1). Even if a product is in scope of the standards referenced via Clause
(b) (NAFS and the Canadian Supplement to NAFS), the compliance path in Clause (a) may be used. However, it is not intended that
the compliance path in Clause (b) be used where fenestration products are not within the scope of the referenced standards.
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
A-5.9.2.2.(2) Other Glazed Products. Glazed products such as curtain walls or sloped glazing that are not typically
considered windows but are installed as part of a separation described in Sentence 5.9.2.1.(1) are not within the scope of the referenced
standards and therefore must conform to Subsection 5.1.4. and Sections 5.3., 5.4. and 5.6. The following are considered to be “other
glazed products”:
Curtain Wall
A curtain wall is considered to be a continuous wall cladding assembly (which may include fenestration and opaque portions)
that is hung away from the edge of the primary floor structure. Curtain wall assemblies do not generally support vertical loads
other than their own weight. Anchorage is typically provided by anchors that connect back to the floor structure. Curtain wall
assemblies can be either “stick built,” meaning each main unit is assembled on-site, or a “unitized” system, meaning
factory-assembled main units are installed and connected together on-site.
Window Wall
A window wall is considered to be a wall cladding assembly (which may include fenestration and opaque portions) that spans
from the top of a primary floor structure to the underside of the next higher primary floor structure. Window wall assemblies do
not generally support vertical loads other than their own weight. Primary provision for anchorage occurs at head and sill
connections with the adjoining floor structure. Window wall assemblies may include separate or integral floor edge covers.
Storefront
A storefront is considered to be a non-residential assembly (which may include fenestration and opaque portions) consisting of
one or more elements that could include doors, windows and curtain wall framing. Storefronts do not generally support vertical
loads other than their own weight. Storefront profiles are typically narrow, rectilinear framing members that hold a combination
of pocket glazing and applied glazing stops to securely retain the infills. Vertical framing members typically span the height of one
floor or are retained within a structural punched opening.
Storefront assemblies are designed/selected to take into account the anticipated service and exposure conditions, which may be
different than those for other portions of the building.
Glazed Architectural Structures
Glazed architectural structures are considered glazing assemblies that are supported in a non-traditional manner, such as
corner-clamped, point-supported, linear-supported and edge-clamped glazing. Structural support systems can include, but are
not limited to, tension cables, tension rods, steel and glass. Glazed architectural structures do not generally support vertical loads
other than their own weight. These assemblies are designed/selected to take into account the anticipated service and exposure
conditions, which may be different than those for other portions of the building.
Skylights that are not covered by AAMA/WDMA/CSA 101/I.S.2/A440, “NAFS – North American Fenestration
Standard/Specification for Windows, Doors, and Skylights,” are considered glazed architectural structures.
Testing of Other Glazed Products
Although other glazed products are generally not within the scope of the standards referenced in Clause 5.9.2.2.(1)(b), they can be
tested using other standards such as:
AAMA 501, “Test for Exterior Walls,”
AAMA 501.1, “Water Penetration of Windows, Curtain Walls and Doors Using Dynamic Pressure,”
AAMA 501.2, “Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped
Glazing Systems,”
AAMA 501.4, “Recommended Static Test Method for Evaluating Curtain Wall and Storefront Systems Subjected to Seismic and
Wind Induced Interstory Drifts,”
AAMA 501.5, “Thermal Cycling of Exterior Walls,” and
AAMA 501.6, “Recommended Dynamic Test Method For Determining The Seismic Drift Causing Glass Fallout From A Wall
System.”
ASTM E 283, “Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure
Differences Across the Specimen.”
ASTM E 330/E 330M, “Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air
Pressure Difference.”
Notes to Part 5 – Environmental Separation Division B: Acceptable Solutions
Division B British Columbia Building Code 2018
ASTM E 331, “Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure
Difference.”
ASTM E 547, “Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure
Difference.”
ASTM E 783, “Field Measurement of Air Leakage Through Installed Exterior Windows and Doors.”
ASTM E 1105, “Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls,
by Uniform or Cyclic Static Air Pressure Difference.”
Water Penetration
Notwithstanding that other glazed products
are not covered under the testing scope of CSAA440S1, “Canadian Supplement to
AAMA/WDMA/CSA 101/I.S.2/A440, NAFS – North American Fenestration Standard/Specification for Windows, Doors, and
Skylights,” they may
be tested at the driving rain wind pressure calculated in accordance with the procedure described therein.
Resistance to Condensation
Notwithstanding that other glazed products
are not fully covered under the testing scope of CSAA440.2, “Fenestration Energy
Performance,” the test method described therein can be used to evaluate their resistance to condensation, with technical
modifications to accommodate differences in the size and configuration of the specimen. It is also common practice to use one
cold cycle of AAMA 501.5, “Thermal Cycling of Exterior Walls,” to assess the potential for condensation. Both methods can be
used for mock-ups in laboratory performance evaluations, however, only the test method in CSA A440.2 should be used if a
Temperature Index is required. In most cases, the project specification documents establish the hygrothermal conditions
(i.e., exterior temperature, interior temperature, interior relative humidity) for which the potential for condensation should be
minimized. Under these conditions, the aforementioned test methods can be used to aid in the selection of the appropriate system
performance to minimize the potential for interior surface condensation. In all cases, care should be taken in the construction and
configuration of the specimen, as these parameters may have an impact on its thermal performance and resistance to
condensation. These parameters may include, without limitation, interior wall construction and finishes, heating systems,
ventilation systems, etc., to simulate the actual in-service conditions as closely as practicable.
Air Leakage Rate and Test Pressure
A
ir leakage rates and/or higher differential test pressure can be selected for specific applications of other glazed products where
tight control of airflow is required to prevent interstitial condensation (e.g., in concealed spaces), improve thermal comfort
(e.g., in hospitals, seniors’ residences), or prevent the migration of airborne contaminants (e.g.,in food and drug research,
manufacturing applications, biological laboratories). It is typical of other glazed products
to be used as the sole building envelope
component; where this is the case, a correspondingly higher degree of airtightness may be required.
In addition, higher test pressure differentials can be used to evaluate assemblies with low air leakage, such as non-operable or fixed
fenestration systems whose air leakage rates are not easily measurable at the lower standard pressure differentials.
A-5.9.2.2.(3) Loads and Procedures. For windows within the scope of the “Canadian Supplement” referred to in Sentence
5.9.2.2.(1), structural and wind loads are included and may be calculated in accordance with that standard. As an alternative,
structural and wind loads from Section 5.2. may be used to select fenestration products that are appropriate for the point of
installation. Values derived from the referenced standard, which uses a simplified calculation method, are typically higher than those
derived from calculations done in conformance with Section 5.2.
A-5.9.2.4.(3) Heat Transfer through Fire-Rated Glazed Assemblies. Thermal bridging through fire-rated glazed
assemblies should not be ignored; measures should be taken to minimize condensation consistent with the intent of
Sentence5.9.2.4.(2).
A-5.9.4.1.(1) Exterior Insulation Finish Systems (EIFS). The reference to CAN/ULC-S716.1, “Exterior Insulation and
Finish Systems (EIFS) – Materials and Systems,” in Clause5.9.4.1.(1)(b) does not preclude the use of other component materials that
may also meet the intent of the Code. For example, using mineral-fibre insulation in lieu of other rigid insulation types, mechanical
fastening methods for the insulation component in lieu of adhesive, or a type of water-resistive barrier other than a liquid-applied
water-resistive barrier could be acceptable.
The following two companion standards facilitate the application of and conformance with CAN/ULC-S716.1:
CAN/ULC-S716.2, “Exterior Insulation and Finish Systems (EIFS) – Installation of EIFS Components and Water Resistive
Barrier,” and
CAN/ULC-S716.3, “Exterior Insulation and Finish System (EIFS) – Design Application.”
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
Additional information on EIFS design and installation can be found in the EIFS Council of Canada’s “EIFS Practice Manual” and the
manufacturer’s literature.
EIFS Selection
CAN/ULC-S716.1 provides minimum performance criteria for EIFS materials and systems that are tested under specific
laboratory test protocols identified in the standard. However, compliance with this standard does not ensure that a system is
appropriate for all projects. When selecting an EIFS product, designers should consider all relevant criteria – not only those
covered by the tests in CAN/ULC-S716.1 – including, but not limited to,
building exposure
local climate characteristics (wind, precipitation, temperature variations, solar exposure)
intended building use
intended resistance to damage and deterioration
construction tolerances
constructability
Design and Construction of EIFS Drainage Cavity
The drainage capacity and thermal performance of the EIFS assembly can be affected by the dimensions and configuration of the
EIFS drainage cavity.
EIFS are installed over other building materials such as sheathing and primary structural components, which have various
construction installation tolerances. Designers should take into consideration the cumulative effects of construction tolerances
and sequencing when specifying the drainage method and the cavity dimensions and configuration in order to ensure adequate
drainage.
Designers should also take into account the impact of air movement, which varies depending on cavity size and the extent of
venting, on the EIFS’ thermal performance when reviewing the overall thermal performance of the building envelope.
ASTM C 1363, “Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus,”
presents one method for assessing the thermal performance of assemblies.
Division B: Acceptable Solutions Notes to Part 5 – Environmental Separation
British Columbia Building Code 2018 Division B
Additional information on EIFS design and installation can be found in the EIFS Council of Canada’s “EIFS Practice Manual” and the
manufacturer’s literature.
EIFS Selection
CAN/ULC-S716.1 provides minimum performance criteria for EIFS materials and systems that are tested under specific
laboratory test protocols identified in the standard. However, compliance with this standard does not ensure that a system is
appropriate for all projects. When selecting an EIFS product, designers should consider all relevant criteria – not only those
covered by the tests in CAN/ULC-S716.1 – including, but not limited to,
building exposure
local climate characteristics (wind, precipitation, temperature variations, solar exposure)
intended building use
intended resistance to damage and deterioration
construction tolerances
constructability
Design and Construction of EIFS Drainage Cavity
The drainage capacity and thermal performance of the EIFS assembly can be affected by the dimensions and configuration of the
EIFS drainage cavity.
EIFS are installed over other building materials such as sheathing and primary structural components, which have various
construction installation tolerances. Designers should take into consideration the cumulative effects of construction tolerances
and sequencing when specifying the drainage method and the cavity dimensions and configuration in order to ensure adequate
drainage.
Designers should also take into account the impact of air movement, which varies depending on cavity size and the extent of
venting, on the EIFS’ thermal performance when reviewing the overall thermal performance of the building envelope.
ASTM C 1363, “Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus,”
presents one method for assessing the thermal performance of assemblies.