7.2.5.10. Plastic pipe, Fittings and Solvent cement Used Underground

(1) Plastic pipe, fittings and solvent cement used underground outside abuilding or under a buildingin a drainage system shall be certified to,

(a) ASTM F628, "Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste and Vent Pipe With a Cellular Core",

(b) CAN/CSA-B181.1, "Acrylonitrile-Butadiene-Styrene (ABS) Drain, Waste, and Vent Pipe and Pipe Fittings",

(c) CAN/CSA-B181.2, "Polyvinylchloride (PVC) and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings",

(d) CAN/CSA-B182.1, "Plastic Drain and Sewer Pipe and Pipe Fittings",

(e) CAN/CSA-B182.2, "PSM Type Polyvinylchloride (PVC) Sewer Pipe and Fittings",

(f) CAN/CSA-B182.4, "Profile Polyvinylchloride (PVC) Sewer Pipe and Fittings",

(g) CAN/CSA-B182.6, "Profile Polyethylene (PE) Sewer Pipe and Fittings for Leak-Proof Sewer Applications",

(h) CAN/CSA-B137.2, "Polyvinylchloride (PVC) Injection-Moulded Gasketed Fittings for Pressure Applications", or

(i) CAN/CSA-B137.3, "Rigid Polyvinylchloride (PVC) Pipe and Fittings for Pressure Applications".

(2) Except as permitted in Clauses (h) and (i), plastic pipe used as described in Sentence (1) shall have a stiffness equal or greater than 320 kPa.