9.29.5.5. Length of Fasteners

(1) The length of fasteners for gypsum board shall conform to Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a fire-resistance rating provided it can be shown, on the basis of fire tests, that such depths are adequate for the required rating.

Table 9.29.5.5.
Fastener Penetration into wood supports

Forming Part of Sentence 9.29.5.5.(1)

Item

Column 1

Column 2

Column 3

Column 4

Column 5

Required Fire-Resistance Rating of Assembly

Minimum Penetration, mm

walls

ceilings

Nails

Screws

Nails

Screws

1.

Not required

20

15

20

15

2.

45 min

20

20

30

30

3.

1 h

20

20

45

45

4.

1.5 h

20

20

60

60