3.2.2.73. Group F, Division 3, Any Height, Any Area
(1) Except as permitted by Articles 3.2.2.74. to 3.2.2.83., a building classified as Group F, Division 3 shall conform to Sentence (2).
(2) Except as permitted by Article 3.2.2.16., the buildingreferred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered if it is regulated by Subsection 3.2.6.,
(b) floor assemblies shall be fire separations with a fire-resistance rating not less than 2 h, except that floor assemblies are permitted to be fire separations with a fire-resistance rating not less than 1 h in a storage garagewith all storeys constructed as open-air storeys,
(c) mezzaninesshall have a fire-resistance rating not less 1 h,
(d) if the buildingis not sprinklered, roof assemblies shall have a fire-resistance rating not less than 1 h, and
(e) loadbearingwalls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.