The Ontario Building Code | Group B, Division 1, up to 3 Storeys, Sprinklered

3.2.2.37. Group B, Division 1, up to 3 Storeys, Sprinklered

(1) A building classified as Group B, Division 1 is permitted to conform to Sentence (2) provided,

(a) except as permitted by Sentence 3.2.2.7.(1) the building is sprinklered,

(b) it is not more than 3 storeys in building height, and

(c) it has a building area,

(i) that is not limited if the building is not more than 1 storey in building height,

(ii) not more than 12 000 m2 if 2 storeys in building height, or

(iii) not more than 8 000 m2 if 3 storeys in building height.

(2) Except as permitted by Article 3.2.2.16., the buildingreferred to in Sentence (1) shall be of noncombustible construction, and,

(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,

(b) mezzaninesshall have a fire-resistance rating not less than 1 h, and

(c) loadbearingwalls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.