The Ontario Building Code | Group A, Division 3, up to 2 Storeys, Sprinklered

3.2.2.31. Group A, Division 3, up to 2 Storeys, Sprinklered

(1) A building classified as Group A, Division 3 is permitted to conform to Sentence (2) provided,

(a) except as permitted by Sentence 3.2.2.7.(1), the building shall be sprinklered,

(b) it is not more than 2 storeys in building height, and

(c) it has a building area not more than,

(i) 12 000 m2if 1 storey in building height, or

(ii) 6 000 m2if 2 storeys in building height.

(2) Except as permitted by Clause (c) and Article 3.2.2.16., the building referred to in Sentence (1) shall be of noncombustible construction, and,

(a) floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,

(b) mezzaninesshall have a fire-resistance rating not less than 1 h, and

(c) loadbearingwalls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly, except that arches are permitted to be of heavy timber construction.