The Ontario Building Code | Combustible Piping

9.10.9.7. Combustible Piping

(1) Except as permitted in Sentences (2) to (6), combustiblepiping shall not be used where any part of a piping system partly or wholly penetrates a fire separation required to have a fire-resistance rating or penetrates a membrane that contributes to the required fire-resistance ratingof an assembly.

(2) Combustible piping not located in a vertical shaft is permitted to penetrate a fire separation required to have a fire-resistance rating or a membrane that forms part of an assembly required to have a fire-resistance rating, provided the piping is sealed at the penetration by a fire stop that has an F rating not less than the fire-resistance rating required for the fire separation.

(3) The rating referred to in Sentence (2) shall be based on CAN/ulc-S115, "Fire Tests of Firestop Systems", with a pressure differential of 50 Pa between the exposed and unexposed sides, with the higher pressure on the exposed side.

(4) Combustible drain piping is permitted to penetrate a horizontal fire separation or a membrane that contributes to the required fire-resistance ratingof a horizontal fire separation, provided it leads directly from a noncombustible water closet through a concrete floor slab.

(5) Combustible piping is permitted,

(a) on one side of a vertical fire separation provided it is not located in a vertical shaft, and

(b) to penetrate a vertical or horizontal fire separation when the fire compartment on each side of the fire separation is sprinklered.

(6) Inbuildings containing 2 dwelling units only, combustible piping is permitted on one side of a horizontal fire separation.

Note: On July 1, 2017, Sentence 9.10.9.7.(6) of Division B of the Regulation is amended by striking out "In buildings containing 2 dwelling units only" at the beginning and substituting "In a house containing two dwelling units". (See: O. Reg. 139/17, s. 102)