The Ontario Building Code | Branch Vents, Headers, Continuous Vents and Circuit Vents
7.5.8.3. Branch vents, Headers, Continuous vents and circuit Vents
(1) Branch vents, headers, circuit vents and continuous vents shall be sized in accordance with Table 7.5.8.3., unless they are individual vents or dual vents.
Table 7.5.8.3.
Sizing of Branch vents, Headers, Continuous vents and circuit Vents
Forming Part of Article 7.5.8.3.
Item | Column 1 | Column 2 | Column 3 | Column 4 | Column 5 | Column 6 | Column 7 | Column 8 | Column 9 |
| Total Hydraulic Load Served by vent, fixture units |
|
|
|
|
|
| ||
|
| 1 ¼ | 1 ½ | 2 | 3 | 4 | 5 | 6 | 8 |
|
|
|
|
|
| ||||
1. | 2 | 9 | NL | NL | NL | NL | NL | NL | NL |
2. | 8 | 9 | 30 | 61 | NL | NL | NL | NL | NL |
3. | 20 | 7.5 | 15 | 46 | NL | NL | NL | NL | NL |
4. | 24 | 4.5 | 9 | 30 | NL | NL | NL | NL | NL |
5. | 42 | NP | 9 | 30 | NL | NL | NL | NL | NL |
6. | 60 | NP | 4.5 | 15 | 120 | NL | NL | NL | NL |
7. | 100 | NP | NP | 11 | 79 | 305 | NL | NL | NL |
8. | 200 | NP | NP | 9 | 76 | 275 | NL | NL | NL |
9. | 500 | NP | NP | 6 | 55 | 215 | NL | NL | NL |
10. | 1 100 | NP | NP | NP | 15 | 61 | 215 | NL | NL |
11. | 1 900 | NP | NP | NP | 6 | 21 | 61 | 215 | NL |
12. | 2 200 | NP | NP | NP | NP | 9 | 27 | 105 | 335 |
13. | 3 600 | NP | NP | NP | NP | 7.5 | 18 | 76 | 245 |
14. | 5 600 | NP | NP | NP | NP | NP | 7.5 | 18 | 76 |
Notes to Table 7.5.8.3.:
(1)NL means not limited.
(2)NP means not permitted.
(2) For the purposes of Table 7.5.8.3., the length of a branch vent shall be its developed length from the most distant soil or waste pipe connection to a vent stack, stack vent, headeror open air.
(3) For the purposes of Table 7.5.8.3., the length of a header shall be its developed lengthfrom the most distant soil or waste pipe connection to open air.
(4) For the purposes of Table 7.5.8.3., the length of a circuit vent shall be its developed length from the horizontal soil or waste pipe connection to a vent stack, stack vent, headeror open air.
(5) For the purposes of Table 7.5.8.3., the length of a continuous vent shall be its developed length from the vertical soil or waste pipe connection to a vent stack, stack vent, headeror open air.