7.3.7.2. Tests of Potable water Systems
(1) Every potable water system shall be capable of,
(a) withstanding without leakage a water pressure that is at least 1 000 kPa for at least 1 h, or
(b) withstanding for at least 2 h without a drop in pressure an air pressure that is at least 700 kPa.